HomeMy WebLinkAbout24-14-C Executed Contract.pdf SPECIFICATIONS
CSA 43W RAISIN CITY GROUNDWATER WELL
6425 W BOWLES AVE, RAISIN CITY, CA 93652
BUDGET /ACCOUNT: 8870 / 8400 / 91762
co
�6 Department o Public Works and Planning
O� �O p f g
FRES
CONTRACT NUMBER 24-14-C
coU�
Countyof FresnoC
O is56 O DEPARTMENT OF PUBLIC WORKS AND PLANNING
STEVEN E. WHITE, DIRECTOR
10
FRESH
October 28, 2024 Contract No. 24-14-C
ADDENDUM NO. 1 to CSA 43W Raisin City Groundwater Well, revising the Bidding and
Contract Documents as follows:
TABLE OF CONTENTS
ADD:
FEDERAL REQUIREMENTS
Federal Requirements for Federal Aid Construction Projects
ARPA Contract Provisions
NOTICE TO BIDDERS
DELETE:
A valid California Contractor's License, Class A (General Engineering), is required
for this project.
REPLACE with:
A valid California Contractor's License, Class A (General Engineering) or C-57 (Well
Drilling Contractor), is required for this project. If the California Contractor's License
is a C-57, a C-10 (Electrical Contractor) must be held by the contractor performing the
electrical work.
SPECIAL PROVISIONS
Section 8-1.04C(2) Second Order of Work
DELETE:
Complete the second order of work before the expiration of
ONE HUNDRED (100) WORKING DAYS
REPLACE with:
Complete the second order of work before the expiration of
ONE HUNDRED TWENTY (120) WORKING DAYS
Addendum No. 1 CSA 43W RAISIN CITY GROUNDWATER WELL
Contract No. 24-14-C Page 1 of 4
FEDERAL PROVISIONS
ADD: attached ARPA Contract Provisions
ADD: attached Federal Requirements for Federal Aid Construction Projects
PROPOSAL/BID BOOK: PAPER
TABLE OF CONTENTS
DELETE:
10-18 NOT USED
REPLACE with:
CERTIFICATION WITH REGARD TO THE PERFORMANCE OF PREVIOUS
10 CONTRACTS OR SUBCONTRACTS SUBJECT TO THE EQUAL OPPORTUNITY
CLAUSE AND THE FILING OF REQUIRED REPORTS
11 TITLE 49,CODE OF FEDERAL REGULATIONS,PART 29 DEBARMENT AND
SUSPENSION CERTIFICATION
12 NONLOBBYING CERTIFICATION FOR FEDERAL-AID CONTRACTS
13(A)-13(B) DISCLOSURE OF LOBBYING ACTIVITIES
14-18 NOT USED
DELETE:
INSTRUCTIONS FOR COMPLETING THE BID BOOK FOR NON-FEDERAL AID
PROJECTS
REPLACE with: attached INSTRUCTIONS FOR COMPLETING THE BID BOOK FOR
FEDERAL AID PROJECTS
ADD attached:
Certification With Regard To The Performance Of Previous Contracts Or Subcontracts
Subject To The Equal Opportunity Clause And The Filing Of Required Reports —
Proposal 10
Title 49, Code Of Federal Regulations, Part 29 - Debarment And Suspension
Certification - Proposal 11
Nonlobbying Certification For Federal-Aid Contracts - Proposal 12
Disclosure of Lobbying - Proposal 13
Addendum No. 1 CSA 43W RAISIN CITY GROUNDWATER WELL
Contract No. 24-14-C Page 2 of 4
PROPOSAL/BID BOOK: BID EXPRESS
ADD:
Certification With Regard To The Performance Of Previous Contracts Or Subcontracts
Subject To The Equal Opportunity Clause And The Filing Of Required Reports —
Proposal 10
Title 49, Code Of Federal Regulations, Part 29 - Debarment And Suspension
Certification - Proposal 11
Nonlobbying Certification For Federal-Aid Contracts - Proposal 12
Disclosure of Lobbying - Proposal 13
AGREEMENT
No changes
PROJECT DETAILS
No changes
PLANS
DELETE: Page G1
REPLACE with: attached Page G1-1
DELETE: Page C5
REPLACE with: attached Page C5-1
DELETE: Page E31
REPLACE with: attached Page E31-1
END OF ADDENDUM NO. 1
Addendum No. 1 CSA 43W RAISIN CITY GROUNDWATER WELL
Contract No. 24-14-C Page 3 of 4
-------------------------------------------------------------------------------------------------------------------
Please attach this Addendum to the inside cover of the Specifications booklet. If you
have given the Bidding and Contract Documents to someone else, please forward this
Addendum.
.'o z l
OFESS/p� Dat6 Sign d
AN I lF
coNo. C76724 r
Exp.12/31/24
�TF�FiVIL
CAL\����� --
Supervising Engineer: r
FRESNO COUNTY Sebastian Artal, PE C76724
Department of Public Works and Planning
m/a 2220 Tulare Street, Suite 720
Fresno, CA 93721-2106
Addendum No. 1 CSA 43W RAISIN CITY GROUNDWATER WELL
Contract No. 24-14-C Page 4 of 4
10/28/2024
�O QRpFESS/��l Date Signed
co
� z
w Y NO. 1 - m
EXP. 1
Consulting Engineer: cAvF
Kevin Pezzoni, E16269
PEZZONI ENGINEERING, INC.
1150 9th Street Ste. 1415
Modesto, CA 95354
Addendum No. 1 CSA 43W RAISIN CITY GROUNDWATER WELL
Contract No. 24-14-C Page 5 of 6
10/25/2024
Date Signed
Consulting Engineer:
PROVOST & PRITCHARD CONSULTIN Nicholas Jacobson, PE C84909
455 W. Fir Ave.
Fresno, CA 93611
Addendum No. 1 CSA 43W RAISIN CITY GROUNDWATER WELL
Contract No. 24-14-C Page 6 of 6
ARPA CONTRACT PROVISIONS
The Contract may be funded in part by the federal grant funding received by the COUNTY from
the American Rescue Plan Act ("ARPA"). Therefore, CONTRACTOR must comply with all
federal laws and regulations applicable to the receipt of ARPA grants, including, but not limited
to, the contractual provision set forth in 2 CFR, Part 200, in connection with the
CONTRACTOR's performance of the work or services covered by the Contract (the "Project").
All such federal laws and regulations shall be deemed to be inserted in the Contract and the
Contract shall be read and enforced as though such federal laws and regulations were included
therein. In addition, the CONTRACTOR agrees to the following specific provisions:
Equal Employment Opportunity
During the performance of this contract, the contractor agrees as follows:
(1) The contractor will not discriminate against any employee or applicant for employment
because of race, color, religion, sex, sexual orientation, gender identity, or national origin. The
contractor will take affirmative action to ensure that applicants are employed, and that employees
are treated during employment without regard to their race, color, religion, sex, sexual orientation,
gender identity, or national origin. Such action shall include, but not be limited to the following:
Employment, upgrading, demotion, or transfer; recruitment or recruitment advertising; layoff or
termination; rates of pay or other forms of compensation; and selection for training, including
apprenticeship. The contractor agrees to post in conspicuous places, available to employees and
applicants for employment, notices to be provided setting forth the provisions of this
nondiscrimination clause.
(2) The contractor will, in all solicitations or advertisements for employees placed by or on behalf
of the contractor, state that all qualified applicants will receive consideration for employment
without regard to race, color, religion, sex, sexual orientation, gender identity, or national origin.
(3) The contractor will not discharge or in any other manner discriminate against any employee
or applicant for employment because such employee or applicant has inquired about, discussed,
or disclosed the compensation of the employee or applicant or another employee or applicant.
This provision shall not apply to instances in which an employee who has access to the
compensation information of other employees or applicants as a part of such employee's essential
job functions discloses the compensation of such other employees or applicants to individuals
who do not otherwise have access to such information, unless such disclosure is in response to
a formal complaint or charge, in furtherance of an investigation, proceeding, hearing, or action,
including an investigation conducted by the employer, or is consistent with the contractor's legal
duty to furnish information.
(4) The contractor will send to each labor union or representative of workers with which he has a
collective bargaining agreement or other contract or understanding, a notice to be provided
advising the said labor union or workers' representatives of the contractor's commitments under
this section, and shall post copies of the notice in conspicuous places available to employees and
applicants for employment.
(5) The contractor will comply with all provisions of Executive Order 11246 of September 24,
1965, and of the rules, regulations, and relevant orders of the Secretary of Labor.
(6) The contractor will furnish all information and reports required by Executive Order 11246 of
September 24, 1965, and by rules, regulations, and orders of the Secretary of Labor, or pursuant
thereto, and will permit access to his books, records, and accounts by the administering agency
and the Secretary of Labor for purposes of investigation to ascertain compliance with such rules,
regulations, and orders.
1 of 5
ARPA CONTRACT PROVISIONS
(7) In the event of the contractor's noncompliance with the nondiscrimination clauses of this
contract or with any of the said rules, regulations, or orders, this contract may be canceled,
terminated, or suspended in whole or in part and the contractor may be declared ineligible for
further Government contracts or federally assisted construction contracts in accordance with
procedures authorized in Executive Order 11246 of September 24, 1965, and such other
sanctions may be imposed and remedies invoked as provided in Executive Order 11246 of
September 24, 1965, or by rule, regulation, or order of the Secretary of Labor, or as otherwise
provided by law.
(8) The contractor will include the portion of the sentence immediately preceding paragraph (1)
and the provisions of paragraphs (1) through (8) in every subcontract or purchase order unless
exempted by rules, regulations, or orders of the Secretary of Labor issued pursuant to section
204 of Executive Order 11246 of September 24, 1965, so that such provisions will be binding
upon each subcontractor or vendor. The contractor will take such action with respect to any
subcontract or purchase order as the administering agency may direct as a means of enforcing
such provisions, including sanctions for noncompliance:
Provided, however, that in the event a contractor becomes involved in, or is threatened with,
litigation with a subcontractor or vendor as a result of such direction by the administering agency,
the contractor may request the United States to enter into such litigation to protect the interests
of the United States.
The applicant further agrees that it will be bound by the above equal opportunity clause with
respect to its own employment practices when it participates in federally assisted construction
work: Provided, That if the applicant so participating is a State or local government, the above
equal opportunity clause is not applicable to any agency, instrumentality or subdivision of such
government which does not participate in work on or under the contract.
The applicant agrees that it will assist and cooperate actively with the administering agency and
the Secretary of Labor in obtaining the compliance of contractors and subcontractors with the
equal opportunity clause and the rules, regulations, and relevant orders of the Secretary of Labor,
that it will furnish the administering agency and the Secretary of Labor such information as they
may require for the supervision of such compliance, and that it will otherwise assist the
administering agency in the discharge of the agency's primary responsibility for securing
compliance.
The applicant further agrees that it will refrain from entering into any contract or contract
modification subject to Executive Order 11246 of September 24, 1965, with a contractor debarred
from, or who has not demonstrated eligibility for, Government contracts and federally assisted
construction contracts pursuant to the Executive Order and will carry out such sanctions and
penalties for violation of the equal opportunity clause as may be imposed upon contractors and
subcontractors by the administering agency or the Secretary of Labor pursuant to Part II, Subpart
D of the Executive Order. In addition, the applicant agrees that if it fails or refuses to comply with
these undertakings, the administering agency may take any or all of the following actions: Cancel,
terminate, or suspend in whole or in part this grant (contract, loan, insurance, guarantee); refrain
from extending any further assistance to the applicant under the program with respect to which
the failure or refund occurred until satisfactory assurance of future compliance has been received
from such applicant; and refer the case to the Department of Justice for appropriate legal
proceedings.
Rights and Remedies
(1) The duties and obligations imposed by the Contract Documents and the rights and remedies
available hereunder shall be in addition to, and not a limitation of, any duties, obligations, rights
and remedies otherwise imposed or available by law.
2of5
ARPA CONTRACT PROVISIONS
(2) No action or failure to act by or on behalf of the Owner regarding any deficiency, breach or
default in performance by the Contractor under the Contract Documents, shall be deemed or
construed to constitute acquiescence of the Owner in connection therewith or with regard to any
subsequent deficiency, breach or default in performance by the Contractor; nor shall any such
prior act of failure to act by or on behalf of Owner be deemed or construed as a waiver of any
rights in favor of Owner regarding any such deficiency, breach or default in performance by the
Contractor, regardless of the similarity to the prior incident or circumstance when no action was
taken regarding any alleged deficiency, breach or default in performance by the Contractor.
Termination of Convenience
Under circumstances other than those set forth in Section IV of the Agreement governing
termination of this Contract for cause, this Contract may be terminated by the County, with no
liability to the contractor accruing to the County based solely upon the County's exercise of such
right, upon the giving of thirty (30) days advance written notice of an intention to terminate to the
contractor. In the event of such termination, the contractor shall cease work on such date as is
specified by the County in that notice, and the contractor shall be entitled to payment for all work
performed through and including that date. The County and the contractor shall meet and confer
in an effort to resolve any and all remaining issues relating to completion of the work, payment to
the contractor of any incurred and unpaid costs to which the contractor may claim to be entitled
under the Contract, and any other issues pertaining to final resolution of the contractual
relationship. In the event of any remaining disputes after the parties have met and conferred,
they shall be resolved in accordance with 9-1.23 RESOLUTION OF CONTRACT CLAIMS of the
Special Provisions.
Copeland Anti-Kickback Act
(1) The contractor shall comply with 18 U.S.C. § 874, 40 U.S.C. § 3145, and the requirements of
29 C.F.R. pt. 3 as may be applicable, which are incorporated by reference into this contract. Each
contractor or subrecipient is prohibited from inducing, by any means, any person employed in the
construction, completion, or repair of public work, to give up any part of the compensation to which
he or she is otherwise entitled.
(2) The contractor or subcontractor shall insert in any subcontracts the above clause in any lower
tier subcontracts. The prime contractor shall be responsible for the compliance by any
subcontractor or lower tier subcontractor with all of these contract clauses.
(3) A breach of the contract clauses above may be grounds for termination of the contract, and
for debarment as a contractor or subcontractor as provided in 29 CFR 5.12.
Contract Work Hours and Safety Standards Act
(1) Overtime requirements. No contractor or subcontractor contracting for any part of the contract
work which may require or involve the employment of laborers or mechanics shall require or
permit any such laborer or mechanic in any workweek in which he or she is employed on such
work to work in excess of forty hours in such workweek unless such laborer or mechanic receives
compensation at a rate not less than one and one-half times the basic rate of pay for all hours
worked in excess of forty hours in such workweek.
(2) Violation; liability for unpaid wages; liquidated damages. In the event of any violation of the
clause set forth in paragraph (b)(1) of this section the contractor and any subcontractor
responsible therefor shall be liable for the unpaid wages. In addition, such contractor and
subcontractor shall be liable to the United States (in the case of work done under contract for the
District of Columbia or a territory, to such District or to such territory), for liquidated damages.
3 of 5
ARPA CONTRACT PROVISIONS
Such liquidated damages shall be computed with respect to each individual laborer or mechanic,
including watchmen and guards, employed in violation of the clause set forth in paragraph (b)(1)
of this section, in the sum of$27 for each calendar day on which such individual was required or
permitted to work in excess of the standard workweek of forty hours without payment of the
overtime wages required by the clause set forth in paragraph (b)(1) of this section.
(3) Withholding for unpaid wages and liquidated damages. The County of Fresno shall, upon its
own action or upon written request of an authorized representative of the Department of Labor,
withhold or cause to be withheld from any moneys payable on account of work performed by the
contractor or subcontractor under any such contract or any other Federal contract with the same
prime contractor, or any other federally-assisted contract subject to the Contract Work Hours and
Safety Standards Act, which is held by the same prime contractor, such sums as may be
determined to be necessary to satisfy any liabilities of such contractor or subcontractor for unpaid
wages and liquidated damages as provided in the clause set forth in paragraph (b)(2) of this
section.
(4) Subcontracts. The contractor or subcontractor shall insert in any subcontracts the clauses set
forth in paragraph (b)(1)through (4)of this section and also a clause requiring the subcontractors
to include these clauses in any lower tier subcontracts. The prime contractor shall be responsible
for compliance by any subcontractor or lower tier subcontractor with the clauses set forth in
paragraphs (b)(1) through (4) of this section.
Clean Air Act and the Federal Water Pollution Control Act
The contractor agrees to comply with all applicable standards, orders or regulations issued
pursuant to the Clean Air Act, as amended, 42 U.S.C. § 7401 et seq., and the Federal Water
Pollution Control Act, as amended, 33 U.S.C. 1251 et seq.
(1) The contractor agrees to report each violation to the County and understands and agrees
that the County will, in turn, report each violation as required to assure notification to the Federal
Emergency Management Agency, and the appropriate Environmental Protection Agency
Regional Office.
(2) The contractor agrees to include these requirements in each subcontract exceeding
$150,000 financed in whole or in part with Federal assistance provided by ARPA.
Suspension and Debarment
(1) This contract is a covered transaction for purposes of 2 CFR, part 180 and 2 CFR, part 3000.
As such, the contractor is required to verify that none of the contractor's principals (defined at 2
CFR § 180.995) or its affiliates (defined at 2 CFR § 180.905) are excluded (defined at 2 CFR §
180.940) or disqualified (defined at 2 CFR § 180.935).
(2) The contractor must comply with 2 CFR, part 180, subpart C and 2 CFR, part 3000,
subpart C, and must include a requirement to comply with these regulations in any lower tier
covered transaction it enters into.
(3) This certification is a material representation of fact relied upon by the County. If it is later
determined that the contractor did not comply with 2 CFR, part 180, subpart C and 2 CFR, part
3000, subpart C, in addition to remedies available to the County, the Federal Government may
pursue available remedies, including but not limited to suspension and/or debarment.
(4) The bidder or proposer agrees to comply with the requirements of 2 CFR, part 180, subpart
4of5
ARPA CONTRACT PROVISIONS
C and 2 CFR, part 3000, subpart C while this offer is valid and throughout the period of any
contract that may arise from this offer. The bidder or proposer further agrees to include a
provision requiring such compliance in its lower tier covered transactions.
Byrd Anti-Lobbying Amendment
Contractors who apply or bid for an award of$100,000 or more shall file the required
certification. Each tier certifies to the tier above that it will not and has not used Federal
appropriated funds to pay any person or organization for influencing or attempting to influence
an officer or employee of any agency, a Member of Congress, officer or employee of Congress,
or an employee of a Member of Congress in connection with obtaining any Federal contract,
grant, or any other award covered by 31 U.S.C. § 1352. Each tier shall also disclose any
lobbying with non-Federal funds that takes place in connection with obtaining any Federal
award. Such disclosures are forwarded from tier to tier up to the recipient who in turn will
forward the certification(s) to the awarding agency.
Access to Records
(1) The Contractor agrees to provide the County of Fresno, the US Department of Treasury,
the Comptroller General of the United States, or any of their authorized representatives access
to any books, documents, papers, and records of the Contractor which are directly pertinent to
this contract for the purposes of making audits, examinations, excerpts, and transcriptions.
(2) The Contractor agrees to permit any of the foregoing parties to reproduce by any means
whatsoever or to copy excerpts and transcriptions as reasonably needed.
Buy USA - Domestic Preference for Certain Procurements Using Federal Funds
Contractor should, to the greatest extent practicable under a Federal award, provide a
preference for the purchase, acquisition, or use of goods, products, or materials produced in
the United States (including but not limited to iron, aluminum, steel, cement, and other
manufactured products). The requirements of this section must be included in all subawards
including all contracts and purchase orders for work or products under this award. For purposes
of this section:
(1) "Produced in the United States" means, for iron and steel products, that all manufacturing
processes, from the initial melting stage through the application of coatings, occurred in the
United States.
(2) "Manufactured products" means items and construction materials composed in whole or in
part of non-ferrous metals such as aluminum; plastics and polymerbased products such as
polyvinyl chloride pipe; aggregates such as concrete; glass, including optical fiber; and lumber.
5 of 5
FEDERAL REQUIREMENTS FOR FEDERAL-AID CONSTRUCTION PROJECTS
General
The work will be financed in whole or in part with Federal funds, and therefore all of the Federal statutes,
rules, regulations, and provisions applicable to work financed in whole or in part with Federal funds will
apply.
In addition to the provisions in the Agreement, the Contractor shall comply with the following:
Performance Of Previous Contracts
The bidder shall execute the "Certification with Regard to the Performance of Previous Contracts or
Subcontracts Subject to the Equal Opportunity Clause and the Filing of Required Reports" located in the
proposal. No request for subletting or assigning any portion of the contract in excess of$10,000 will be
considered under the provisions of Section VII of the required contract provisions unless such request is
accompanied by the Certification referred to above, executed by the proposed subcontractor.
Non-Collusion Provision
The provisions in this section are applicable to all contracts except contracts for Federal Aid Secondary
projects. Title 23, United States Code, Section 112, requires as a condition precedent to approval by the
Federal Highway Administrator of the contract for this work that each bidder file a sworn statement
executed by, or on behalf of, the person, firm, association, or corporation to whom such contract is to be
awarded, certifying that such person, firm, association, or corporation has not, either directly or indirectly,
entered into any agreement, participated in any collusion, or otherwise taken any action in restraint of free
competitive bidding in connection with the submitted bid. A form to make the non-collusion affidavit
statement required by Section 112 as a certification under penalty of perjury rather than as a sworn
statement as permitted by 28, USC, Sec. 1746, is included in the proposal.
Contracting with Small and Minority Businesses, Women's Business Enterprises, and Labor
Surplus Area Firms
Conducting the following steps to ensure the use of small and minority businesses, women's business
enterprises, and labor surplus area firms when possible:
• Place such organizations that are qualified on solicitation lists;
• Ensure such organizations are solicited whenever they are potential sources;
• Divide total requirements, when economically feasible, into smaller tasks or quantities;
• Establish delivery schedules, where the requirement permits, which encourage their participation;
• Use the services and assistance, as appropriate, of the Small Business Administration and the
Minority Business Development Agency of the Department of Commerce; and
• Require prime contractor to conduct the above steps if subcontracting.
Prohibition of Certain Telecommunications and Video Surveillance Equipment and Services
In response to significant national security concerns, the agency shall check the prohibited vendor list
before making any telecommunications and video surveillance purchase because recipients and
subrecipients of federal funds are prohibited from obligating or expending loan or grant funds to:
• Procure or obtain;
• Extend or renew a contract to procure or obtain; or
• Enter into a contract(or extend or renew a contract)to procure or obtain equipment, services, or
systems that uses covered telecommunications equipment or services as a substantial or essential
component of any system, or as critical technology as part of any system.
The prohibited vendors (and their subsidiaries or affiliates) are:
• Huawei Technologies Company;
Federal Requirements 1
• ZTE Corporation;
• Hytera Communications Corporation;
• Hangzhou Hikvision Digital Technology Company;
• Dahua Technology Company; and
• Subsidiaries or affiliates of the above-mentioned companies.
In implementing the prohibition, the agency administering loan, grant, or subsidy programs shall prioritize
available funding and technical support to assist affected businesses, institutions and organizations as is
reasonably necessary for those affected entities to transition from covered communications equipment
and services, to procure replacement equipment and services, and to ensure that communications service
to users and customers is sustained.
Federal Requirements 2
INSTRUCTIONS FOR COMPLETING THE BID BOOK FOR FEDERAL AID
PROJECTS
General
Complete forms in the Bid Book.
Submit an electronic bid online at http://www.BidExpress.com (Section 2-1.33D) or submit a hardcopy bid:
1. Under sealed cover addressed to the Department and labeled with the name of the bidder, the name
of the project and the statement'Do Not Open Until The Time Of Bid Opening.'
2. Marked as a bid
3. Identifying the contract number and the bid opening date
Certain bid forms must be submitted with the bid and properly executed.
Certain other forms and information must be submitted either with the bid or within the prescribed period
after bid opening as specified elsewhere in these special provisions.
Failure to submit the forms and information as specified results in a nonresponsive bid.
If an agent other than the authorized corporation officer or a partnership member signs the bid, file a
Power of Attorney with the Department either before opening bids or with the bid. Otherwise, the bid may
be nonresponsive.
Bid Item List and Bid Comparison
Submit a bid based on the bid item quantities the Department shows on the Bid Item List. Bids will be
evaluated and the low bidder determined as indicated in the Notice to Bidders.
Bid Document Completion
Proposal items are identified by title and by the word "Proposal"followed by the number assigned to the
proposal item in question. Proposal items are included in the Bid Book.
Proposal to the Board of Supervisors of Fresno County— Proposal 1
Provided for information.
Bid Proposal Sheet— Proposal 2
One or more sheet(s) or list(s) upon which the bidder completes the bid.
Fill out completely including a unit price and total for each unit price-based item and a total for each lump
sum item.
Do not make any additions such as "plus tax", "plus freight", or conditions such as "less 2% if paid by
15th".
Use ink or typewriter for paper bids.
Evaluation of Bid Proposal Sheet— Proposal 3
Describes how inconsistences and irregularities are evaluated and corrected when Design Services
reviews the Bid Item List.
Bid Security and Signature— Proposal 4
Submit one of the following forms of bidder's security equal to at least 10 percent of the bid:
• Cash
• Cashier's check
• Certified check
• Signed bidder's bond by an admitted surety insurer
Indicate type of bid security provided.
• Cash—Acceptable but not recommended. Cash is deposited in a clearing account and is
returned to bidders by County warrant. This process may take several weeks.
• Cashier's or Certified Checks. This type of security is held until the bid is no longer under
consideration. If submitted by a potential awardee, they will be returned when the contract is fully
executed by the bidder and bonds and insurance have been approved.
• Bid Bonds - Must be signed by the bidder and by the attorney-in-fact for the bonding company.
Provide notarized signature of attorney-in-fact accompanied by bonding company's affidavit
authorizing attorney-in-fact to execute bonds. An unsigned bid bond will be cause for rejection.
Bonding companies may provide their own bid bond forms. The Bid Security and Signature sections must
be completed by the bidder and submitted with their bid.
Acknowledge Addenda
Provide contractor's license information.
State business name and if business is a:
• Corporation - list officers
• Partnership- list partners
• Joint Venture- list members; if members are corporations or partnerships, list their officers or
partners.
• Individual - list Owner's name and firm name style
Signature of Bidder-the following lists types of companies and corresponding authorized signers.
• Corporation - by an officer
• Partnership- by a partner
• Joint Venture- by a member
• Individual - by the Owner
If signature is by a Branch Manager, Estimator, Agent, etc., the bid must be accompanied by a power of
attorney authorizing the individual to sign the bid in question or to sign bids more generally, otherwise the
bid may be rejected.
• Business Address - Firm's Street Address
• Mailing Address - P.O. Box or Street Address
• Complete, sign, and return with bid.
Noncollusion Declaration —Proposal 5
Must be completed, signed, and returned with bid.
Public Contract Code Section 10285.1 Statement— Proposal 6
Select"has"or"has not" in accordance with instructions on form, return with completed for with bid. Note
that signing the bid constitutes signing this statement.
Public Contract Code Section 10162 Questionnaire And Public Contract Code 10232 Statement—
Proposal 7
Select"yes"or"no" accordance with instructions on form, include explanation if"yes" is selected. Return
completed form with bid. Note that signing the bid constitutes signing this questionnaire and statement.
Subcontractors— Proposal 8
Sheet(s) or spaces where upon which bidders list subcontractors. List each subcontractor to perform work
in an amount in excess of 1/2 of 1 percent of the total bid or$10,000, whichever is greater(Pub. Contract
Code §4100 et seq.).
The Subcontractor List submitted with the bid must show the name, location of business, work portions to
be performed, Department of Industrial Relations registration number, and the contractor's license
number for each subcontractor listed.
• Use subcontractor's business name style as registered with the License Board.
• Specify the city in which the subcontractor's business is located and the state if other than
California.
• Description of the work to be performed by the subcontractor. Indicate with bid item numbers
from the bid item list and/or work descriptions similar to those on bid item list.
• List Department of Industrial Relations number and license number for each subcontractor.
Upon request from Design Services, provide the following additional information within 24 hours of bid
opening if not included on the Subcontractor List submitted with the bid:
• Complete physical address for each subcontractor listed.
• Percentage of the total bid or dollar amount associated with each subcontractor listed.
Title 13, California Code of Regulations § 2449(i) General Requirements for In-Use Off-Road
Diesel-Fueled Fleets— Proposal 9
Contractors, if applicable, must submit valid Certificates of Reported Compliance with their bid.
Subcontractor certificates will be due no later than 4:00 PM on the fifth (5th) calendar day after the bid
opening if not submitted with the bid.
Certification With Regard To The Performance Of Previous Contracts Or Subcontracts Subject To
The Equal Opportunity Clause And The Filing Of Required Reports—Proposal 10
For a Federal-aid contract, complete, sign, and return with bid. Certification of proposed subcontractors is
the responsibility of the Bidder and must be provided to the County upon request.
Title 49, Code of Federal Regulations, Part 29 Debarment And Suspension Certification—Proposal
11
For a Federal-aid contract, complete, sign, and return with bid. Certification of proposed subcontractors is
the responsibility of the Bidder and must be provided to the County upon request.
Non-lobbying Certification for Federal-Aid Contracts— Proposal 12
For a Federal-aid contract, complete, sign, and return with bid.
Disclosure of Lobbying Activities— Proposal 13(a) through Proposal 13(b)
For a Federal-aid contract, complete, sign, and return with bid.
Proposal 14— 18— Not Used
Guaranty— Proposal 19
Does not need to be signed with the bid. Part of the contract which must be signed by the contractor
when contract is executed.
CERTIFICATION WITH REGARD TO THE PERFORMANCE OF PREVIOUS
CONTRACTS OR SUBCONTRACTS SUBJECT TO THE EQUAL OPPORTUNITY
CLAUSE AND THE FILING OF REQUIRED REPORTS.
The bidder or proposed subcontractor hereby certifies that they have _, have not
participated in a previous contract or subcontract subject to the equal opportunity clause,
as required by Executive Orders 10925, 11114, or 11246, and that they have _, have
not _, filed with the Joint Reporting Committee, the Director of the Office of Federal
Contract Compliance, a Federal Government contracting or administering agency, or the
former President's Committee on Equal Employment Opportunity, all reports due under
the applicable filing requirements.
(Company)
By:
(Title)
Date:
NOTE: The above certification is required by the Equal Employment Opportunity
Regulations of the Secretary of Labor (41 CFR 60-1 .7(b) (1), and must be submitted by
bidders and proposed subcontractors only in connection with contracts and subcontracts
which are subject to the equal opportunity clause. Contracts and subcontracts which are
exempt from the equal opportunity clause are set forth in 41 CFR 60-1 .5. (Generally only
contracts or subcontracts of$10,000 or under are exempt.)
Currently, Standard Form 100 (EEO-1) is the only report required by the Executive Orders
or their implementing regulations.
Proposed prime contractors and subcontractors who have participated in a previous
contract or subcontract subject to the Executive Orders and have not filed the required
reports should note that 41 CFR 60-1.7(b) (1) prevents the award of contracts and
subcontracts unless such contractor submits a report covering the delinquent period or
such other period specified by the Director, Office of Federal Contract Compliance, U. S.
Department of Labor.
Proposal 10
Contract Number 24-14-C
TITLE 49, CODE OF FEDERAL REGULATIONS, PART 29
DEBARMENT AND SUSPENSION CERTIFICATION
The bidder or proposed subcontractor under penalty of perjury, certifies that, except as
noted below, he/she or any person associated therewith in the capacity of owner, partner,
director, officer, manager:
is not currently under suspension, debarment, voluntary exclusion, or determination
of ineligibility by any federal agency;
has not been suspended, debarred, voluntarily excluded or determined ineligible by
any federal agency within the past 3 years;
does not have a proposed debarment pending; and
has not been indicted, convicted, or had a civil judgment rendered against it by a court
of competent jurisdiction in any matter involving fraud or official misconduct within the
past 3 years.
If there are any exceptions to this certification, insert the exceptions in the following space:
( ) No Exceptions
Exceptions will not necessarily result in denial of award, but will be considered in
determining bidder responsibility. For any exception noted above, indicate below to
whom it applies, initiating agency, and dates of action:
Note: Providing false information may result in criminal prosecution or administrative
sanctions.
The above certification is part of the Proposal. Signing the Proposal on the
signature portion thereof shall also constitute signature of this Certification.
By my signature on this proposal, I certify, under penalty of perjury under the laws of the
State of California and the United States of America, that the Title 23 United States Code,
Section 112 Non-Collusion Declaration and the Title 49 Code of Federal Regulations, Part
29 Debarment and Suspension Certification are true and correct.
Company:
By:
Date:
Title:
Proposal 11
Contract Number 24-14-C
NONLOBBYING CERTIFICATION FOR FEDERAL-AID CONTRACTS
The prospective participant certifies, by signing and submitting this bid or proposal,
to the best of his or her knowledge and belief, that:
(1) No Federal appropriated funds have been paid or will be paid, by or on behalf
of the undersigned, to any person for influencing or attempting to influence an
officer or employee of any Federal agency, a Member of Congress, an officer
or employee of Congress, or an employee of a Member of Congress in
connection with awarding of any cooperative agreement, and the extension,
continuation, renewal, amendment, or modification of any Federal contract,
grant, loan, or cooperative agreement.
(2) If any funds other than Federal appropriated funds have been paid or will be
paid to any person for influencing or attempting to influence an officer of any
Federal agency, a Member of Congress, an officer or employee of Congress,
or an employee of a Member of Congress in connection with this Federal
contract, grant, loan, or cooperative agreement, the undersigned shall
complete and submit Standard Form-LLL, "Disclosure of Lobbying Activities,"
in accordance with its instructions.
This certification is a material representation of fact upon which reliance was placed
when this transaction was made or entered into. Submission of this certification is a
prerequisite for making or entering into this transaction imposed by Section 1352, Title
31, U.S. Code. Any person who fails to file the required certification shall be subject to
a civil penalty of not less than $10,000 and not more than $100,000 for each such
failure.
The prospective participant also agrees by submitting his or her bid or proposal that
he or she shall require that the language of this certification be included in all lower tier
subcontracts, which exceed $100,000 and that all such sub-recipients shall certify and
disclose accordingly.
Bidder:
By:
Date:
Title:
Proposal 12
Contract Number 24-14-C
OMB 0348-0046
DISCLOSURE OF LOBBYING ACTIVITIES
COMPLETE THIS FORM TO DISCLOSE LOBBYING ACTIVITIES PURSUANT TO 31 U.S.C. 1352
1. Type of Federal Action: 2. Status of Federal Action: 3. Report Type:
❑ a. contract ❑ a. bid/offer/application ❑ a. initial
b. grant b. initial award b. material change
c. cooperative agreement c. post-award
d. loan For Material Change Only:
e. loan guarantee year quarter
f. loan insurance date of last report
4. Name and Address of Reporting Entity 5. If Reporting Entity in No.4 is Subawardee,
Enter Name and Address of Prime:
❑ Prime ❑ Subawardee
Tier if known
Congressional District,if known Congressional District,if known
6. Federal Department/Agency: 7. Federal Program Name/Description:
CFDA Number,if applicable
8. Federal Action Number,if known: 9. Award Amount,if known:
10. Name and Address of Lobby Entity 11. Individuals Performing Services
(If individual,last name,first name,MI) (including address if different from No. 10)
(last name,first name,MI)
(attach Continuation Sheet(s)if necessary)
12. Amount of Payment(check all that apply) 14. Type of Payment(check all that apply)
$ ❑ actual ❑ planned a. retainer
b. one-time fee
13. Form of Payment(check all that apply): c. commission
❑ a. cash d. contingent fee
b. in-kind;specify:nature e deferred
Value f. other,specify
15. Brief Description of Services Performed or to be performed and Date(s)of Service,including
officer(s),employee(s),or member(s)contacted,for Payment Indicated in Item 12:
(attach Continuation Sheet(s)if necessary)
16. Continuation Sheet(s)attached: Yes 0 No ❑
17.Information requested through this form is authorized by Title
31 U.S.C.Section 1352. This disclosure of lobbying reliance Signature:
was placed by the tier above when his transaction was made or
entered into. This disclosure is required pursuant to 31 U.S.C. print Name:
1352. This information will be reported to Congress
semiannually and will be available for public inspection. Any
person who fails to file the required disclosure shall be subject Title:
to a civil penalty of not less than$10,000 and not more than
$100,000 for each such failure. Telephone No.: Date:
Authorized for Local Reproduction
Federal Use Only: Standard Form-LLL
Standard Form LLL Rev.04-28-06
Proposal 13(a) May 8, 2013
OMB 0348-0046
INSTRUCTIONS FOR COMPLETING EXHIBIT 10-Q DISCLOSURE OF LOBBYING ACTIVITIES
This disclosure form shall be completed by the reporting entity,whether subawardee or prime federal recipient at the
initiation or receipt of covered federal action or a material change to previous filing pursuant to title 31 U.S.C. Section 1352.
The filing of a form is required for such payment or agreement to make payment to lobbying entity for influencing or
attempting to influence an officer or employee of any agency,a Member of Congress an officer or employee of Congress or
an employee of a Member of Congress in connection with a covered federal action. Attach a continuation sheet for additional
information if the space on the form is inadequate. Complete all items that apply for both the initial filing and material
change report. Refer to the implementing guidance published by the Office of Management and Budget for additional
information.
1. Identify the type of covered federal action for which lobbying activity is or has been secured to influence,the outcome of a
covered federal action.
2. Identify the status of the covered federal action.
3. Identify the appropriate classification of this report. If this is a follow-up report caused by a material change to the information
previously reported,enter the year and quarter in which the change occurred. Enter the date of the last,previously submitted
report by this reporting entity for this covered federal action.
4. Enter the full name,address,city,state,and zip code of the reporting entity. Include Congressional District if known. Check the
appropriate classification of the reporting entity that designates if it is or expects to be a prime or subaward recipient. Identify the
tier of the subawardee,e.g.,the first subawardee of the prime is the first tier. Subawards include but are not limited to:
subcontracts,subgrants,and contract awards under grants.
5. If the organization filing the report in Item 4 checks"Subawardee"then enter the full name,address,city,state,and zip code of
the prime federal recipient. Include Congressional District,if known.
6. Enter the name of the federal agency making the award or loan commitment. Include at least one organization level below
agency name,if known. For example,Department of Transportation,United States Coast Guard.
7. Enter the federal program name or description for the covered federal action(item 1). If known,enter the full Catalog of Federal
Domestic Assistance(CFDA)number for grants,cooperative agreements,loans and loan commitments.
8. Enter the most appropriate federal identifying number available for the federal action identification in item 1 (e.g.,Request for
Proposal(RFP)number,Invitation for Bid(IFB)number,grant announcement number,the contract grant.or loan award number,
the application/proposal control number assigned by the federal agency). Include prefixes,e.g.,"RFP-DE-90-001."
9. For a covered federal action where there has been an award or loan commitment by the Federal agency,enter the federal amount
of the award/loan commitments for the prime entity identified in item 4 or 5.
10. Enter the full name,address,city,state,and zip code of the lobbying entity engaged by the reporting entity identified in Item 4 to
influence the covered federal action.
11. Enter the full names of the individual(s)performing services and include full address if different from 10(a). Enter Last Name,
First Name and Middle Initial(MI).
12. Enter the amount of compensation paid or reasonably expected to be paid by the reporting entity(Item 4)to the lobbying entity
(Item 10). Indicate whether the payment has been made(actual)or will be made(planned). Check all boxes that apply. If this is
a material change report,enter the cumulative amount of payment made or planned to be made.
13. Check all boxes that apply. If payment is made through an in-kind contribution,specify the nature and value of the in-kind
payment.
14. Check all boxes that apply. If other,specify nature.
15. Provide a specific and detailed description of the services that the lobbyist has performed or will be expected to perform and the
date(s)of any services rendered. Include all preparatory and related activity not just time spent in actual contact with federal
officials. Identify the federal officer(s)or employee(s)contacted or the officer(s)employee(s)or Member(s)of Congress that
were contacted.
16. Check whether or not a continuation sheet(s)is attached.
17. The certifying official shall sign and date the form,and print his/her name title and telephone number.
Public reporting burden for this collection of information is estimated to average 30-minutes per response,including time for reviewing
instruction,searching existing data sources,gathering and maintaining the data needed,and completing and reviewing the collection of
information. Send comments regarding the burden estimate or any other aspect of this collection of information,including suggestions for
reducing this burden,to the Office of Management and Budget,Paperwork Reduction Project(0348-0046),Washington,D.C.20503.SF-
LLL-Instructions Rev.06-04
Proposal 13(b) May 8, 2013
TABLE OF CONTENTS
COVER SHEET
COUNTY ADOPTION AND ACKNOWLEDGMENT
Engineer's Signature
Consultant's Signature
NOTICE TO BIDDERS
SPECIAL PROVISIONS
TECHNICAL SPECIFICATIONS
PROJECT DETAILS / DRAWINGS
Project Drawings/Details
Location Map
Construction Funding Sign
County of Fresno Dummy Permit
Self-Dealing Transactions Disclosure Form
BID BOOK
Bidder's Declaration
Bid Form
Abbreviations Used
Bid Security and Signature
Noncollusion Declaration
Public Contract Code
Subcontractor List
General Requirements for In-Use Off-Road Diesel-Fueled Fleets
Certifications
Guaranty
AGREEMENT
Agreement
PLANS
Contract Number 24-14-C
COUNTY ADOPTION AND ACKNOWLEDGEMENT
PROJECT: CSA 43W RAISIN CITY GROUNDWATER WELL
CONTRACT NUMBER: 24-14-C
Nathan Magsig, Chairman 5th District
Ernest Buddy Mendes, Vice Chairman 4th District
Brian Pacheco 1 st District
Steve Brandau 2nd District
Sal Quintero 3rd District
Paul Nerland, County Administrat' fficer
Steven E. White, Di ctor Date
Department of Public Works and Planning
Date Signed:
Q�OFESS/
FN TF
coNo. C76724 '—
Exp.12/31/24
CA
Supervising Engineer:
Sebastian Artal, PE 76724
FRESNO COUNTY
Department of Public Works and Planning
m/a 2220 Tulare Street, Suite 720
Fresno, CA 93721-2106
In responsible charge of the Standard Special Provisions Sections 1-14 and Project Details.
COUNTY ADOPTION AND ACKNOWLEDGEMENT
PROJECT: CSA 43W RAISIN CITY GROUNDWATER WELL
CONTRACT NUMBER: 24-14-C
OQROFESS10
Date Signed: 10/1/zoz4
CO
Z
s o `"
z z �
civil �Q
qTF OF CP'0'F���
DATE SIGNED 10/1/2 0 2 4
Consultant Engineer:
Nicholas Jacobson, PE C84909
PROVOST & PRITCHARD CONSULTING
455 W. Fir Ave.
Fresno, CA 93611
In responsible charge of the Technical Specifications.
COUNTY OF FRESNO STATE OF CALIFORNIA
NOTICE TO BIDDERS
Sealed proposals will be received at:
https://www.bidexpress.com/businesses/36473/home
and at the Fresno County Department of Public Works and Planning (Department), Office of the
Design Engineer, Seventh Floor, Fresno County Plaza Building, 2220 Tulare Street, Fresno, CA
93721 until
2:00 P.M., (1400 hours and 00 seconds)
Thursday, October 31, 2023
If you have any questions about bid submission, please contact us at
DesignServices(a-)fresnocountyca.gov or call (559) 353-4919 or (559) 600-4543.
Promptly following the closing of the bidding all timely submitted bids will be publicly opened and
viewable via a livestream (the link for which will be posted at
http://www.fresnocountVca.gov/planholders) for construction in accordance with the project
specifications therefor, to which special reference is made as follows:
CSA 43W RAISIN CITY GROUNDWATER WELL
6425 W BOWLES AVE, RAISIN CITY, CA 93652
CONTRACT NUMBER 24-14-C
The work to be done consists of, in general, furnishing all labor, materials and equipment necessary
to drill and equip a water well at the location indicated on the plans and connect to the existing water
distribution main in the community of Raisin City, CA, in accordance with the Plans and
Specifications. Electrical work, grading, fence removal and installation and other appurtenant work
as indicated on the plans and specifications is also part of the work.
A pre-bid conference will be held at 1:00 p.m., on October 16, 2024. A discussion of the project will
be held and the project sites will be open for examination. Contractors should meet at 6425 W
Bowles Ave, Raisin City, CA 93652. Attendance at the pre-bid is not mandatory; however, the
scheduled pre-bid will be the only opportunity for prospective bidders to visit the site in the presence
of County staff, and requests for individual site visits with County staff will not be granted.
This project is funded by the American Rescue Plan Act (ARPA).
This project is subject to the contracting requirements and implementing regulations as
amended in Title 13, Section 2449 General Requirements for In-Use Off-Road Diesel-Fueled
Fleets, of the California Code of Regulations (13 CCR § 2449(i)). Bidders must submit a valid
Certificate of Reported Compliance (CRC) issued by the California Air Resources Control
Board at the time of bidding. Bidders are responsible for submitting their listed
subcontractors' CRCs and any supporting documentation within five (5) calendar days of
bid opening. Failure to submit the required CRCs may render a bid non-responsive.
Bidders may fill out a Request to be Added to Planholders list:
https://www.fresnocountyca.gov/Departments/Public-Works-and-Planning/Construction-Bidding-
Opportunities/Request-to-Be-Added-to-the-Planholders-List-Form
Requesters will then be listed as a planholder for the project on the website and receive notifications
and addenda issued for the project.
Prospective bidders may also select the project on www.BidExpress.com. Those that demonstrate
interest in the project will be added to the planholders list, and receive notifications and addenda
issued for the project.
Planholder and exchange/publication names may be obtained from the Fresno County website at
http://www.fresnocountyca.gov/planholders.
Electronic copies, in ".pdf" file format, of the official project plans and specifications, bid books and
proposal sheets and such additional supplemental project information as may be provided, are
available to view, download, and print at http://www.fresnocountyca.gov/planholders.
If a bidder is unable to submit a bid via Bid Express, Bid Books, which contain bid proposal sheets
necessary to submit a bid, may be obtained within the Specifications documents posted on the
Fresno County website.
Electronic bids shall be submitted via the Bid Express website. Hardcopy bids shall be submitted in
a sealed envelope addressed to the Department and labeled with the name of the bidder, contract
number, name of the project, and the statement "Do Not Open Until The Time Of Bid Opening."
Bid security in the amount of ten (10) percent of the amount of the bid, and in the form of a bid bond
issued by an admitted surety insurer licensed by the California Department of Insurance, cash,
cashier's check or certified check shall accompany the bid. You must either attach an electronic bid
bond or provide an original bid bond (or other form of bid security authorized by Public Contract
Code section 20129(a)), prior to the bid opening. Bid security shall be made in favor of the County
of Fresno.
Hardcopy bid bonds shall be submitted in a sealed envelope addressed to the Department and
labeled with the name of the bidder, the name of the project and the statement "Do Not Open Until
The Time Of Bid Opening — BID BOND".
A Summary of Bids and a list of subcontractors for the apparent low bidder will be posted at the
above listed website, generally within 24 hours of the Bid Opening.
All questions regarding this project shall be in writing and shall be received by the Department of
Public Works and Planning, Design Division, no later than 2:00 P.M. on the seventh (7th) calendar
day before bid opening. Any questions received after this deadline will not receive a response
unless the Department of Public Works and Planning elects to issue an addendum to revise the bid
opening date. In the event that the bid opening date is revised, the deadline for questions will be
extended to no later than 2:00 P.M. on the seventh (7th) calendar day before the revised bid opening
date. Questions shall be submitted on the "Request for Clarification Form" provided on our website:
https://www.fresnocountyca.gov/Departments/Public-Works-and-Planning/Construction-Bidding-
Opportunities/24-14-C-CSA-43W-Raisin-City-Groundwater-Well/Request-for-Clarification-Form
Contract Number 24-14-C Notice to Bidders - 2
Any changes to, or clarification of, the project plans and specifications shall be in the form of a
written addendum issued to planholders of record. Questions that prompt a change or clarification
shall be included in the addendum with the subsequent answer.
Any oral explanation or interpretations given to this project are not binding.
No contract will be awarded to a contractor who has not been licensed in accordance with the
provisions of the Contractors State License Law, California Business and Professions Code,
Division 3, Chapter 9, as amended, or whose bid is not on the proposal form included in the contract
document. A valid California Contractor's License, Class A (General Engineering), is required for
this project.
Pursuant to Section 1773 of the Labor Code, the general prevailing wage rates in the county, or
counties, in which the work is to be done have been determined by the Director of the California
Department of Industrial Relations. These wages are set forth in the General Prevailing Wage
Rates for this project, available at County of Fresno, Department of Public Works and Planning,
2220 Tulare Street, Sixth Floor, Fresno CA 93721-2104 and available from the California
Department of Industrial Relations' Internet web site at http://www.dir.ca.gov/DLSR/PWD. Future
effective general prevailing wage rates, which have been predetermined and are on file with the
California Department of Industrial Relations are referenced but not printed in the general prevailing
wage rates.
This project is subject to compliance monitoring and enforcement by the Department of Industrial
Relations.
No contractor or subcontractor may be listed on a bid proposal for a public works project unless
registered with the Department of Industrial Relations pursuant to Labor Code section 1725.5 [with
limited exceptions from this requirement for bid purposes only under Labor Code section 1771.1(a)].
No contractor or subcontractor may be awarded a contract for public work on a public works project
unless registered with the Department of Industrial Relations pursuant to Labor Code section
1725.5.
This contract is subject to state contract nondiscrimination and compliance requirements pursuant
to Government Code section 12990.
Bids are required for the entire work described herein. Bids will be compared on the basis of the
cumulative sum of the bid amounts listed for the individual line items.
The successful bidder shall furnish a faithful performance bond in the amount of 100 percent of the
contract amount and a payment bond in the amount of 100 percent of the contract amount. Each
bond specified in this Notice (bid bond, faithful performance bond and payment bond) shall meet
the requirements of all applicable statutes, including but not limited to those specified in Public
Contract Code section 20129 and Civil Code section 3248.
Each bond specified in this Notice shall be issued by a surety company designated as an admitted
surety insurer in good standing with and authorized to transact business in this state by the
California Department of Insurance, and acceptable to the County of Fresno. Bidders are cautioned
that representations made by surety companies will be verified with the California Department of
Insurance. Additionally, the County of Fresno, in its discretion, when determining the sufficiency of
a proposed surety company, may require the surety company to provide additional information
supported by documentation. The County generally requires such information and documentation
whenever the proposed surety company has either a Best's Key Rating Guide of less than A and a
financial size designation of less than Vill. Provided, however, that the County expressly reserves
its right to require all information and documentation to which the County is legally entitled from any
proposed surety company.
Contract Number 24-14-C Notice to Bidders - 3
Pursuant to Public Contract Code section 22300, substitution of securities for any moneys withheld
by the County of Fresno to ensure performance under the contract shall be permitted.
The Board of Supervisors reserves the right to reject any or all bids.
Board of Supervisors, County of Fresno
Paul Nerland, County Administrative Officer
Bernice E. Seidel, Clerk of the Board
Issue Date: October 1, 2024
Contract Number 24-14-C Notice to Bidders - 4
Special Provisions
Contract Number 24-14-C
DIVISION I GENERAL PROVISIONS
1 GENERAL
1-1.01 GENERAL
Add to the beginning of Section 1:
The work is done in accordance with the 2023 Standard Specifications, 2023 Standard Plans and the
following special provisions.
Where these special provisions indicate to replace, add to, delete, delete from, or otherwise modify a
"section,"or a portion thereof, the section or portion thereof to which such modification is to be applied is
the section or portion thereof with the corresponding numbering in the 2023 Standard Specifications.
Revised standard plans apply if listed on the "List of Revised Standard Plans," if any, in these special
provisions; or if shown or referenced on the project plans or in the project details section of the book
entitled "Specifications."
In case of conflict between the Standard Specifications and these special provisions, the special
provisions shall take precedence over and be used in lieu of such conflicting portions.
Add to the end of section 1-1.01:
Bid Items and Applicable Sections
Refer to Section 01 22 00 "EXPLANATION OF BID ITEMS" of the Technical Specifications
Add to the 1st table of section 1-1.06:
SJVAPCD San Joaquin Valley air pollution control district
METS Caltrans Material Engineering and Testing Services
Add to section 1-1.06:
Abbreviations in the Bid Items and Applicable Sections are also used in the Bid Item List- Proposal 2.
Add or Replace items in Section 1-1.07 with:
Authorized Facility Audit List: Caltrans-developed list of facilities. For the Authorized Facility Audit List,
go the METS website.
Authorized Material List: Caltrans-developed list of authorized materials. For the Authorized Material
List go to the METS website.
Authorized Material Source List: Caltrans-developed list of authorized source materials. For the
Authorized Material Source List go to the METS website.
Bid Item List: List of bid items, units of measure, and the associated quantities. The verified Bid Item List
is the Bid Item List with verified prices. The Contract Proposal (Proposal 2)of Low Bidder at the
Department's website is the verified Bid Item List. After contract award, interpret a reference to the
Bid Item List as a reference to the verified Bid Item List.
Caltrans: State of California Department of Transportation
County: The County of Fresno
Department: The Fresno County Board of Supervisors and its authorized representatives.
District Office: County of Fresno Department of Public Works and Planning
Director: Department's Chairman
2
Engineer: The County's Director of Public Works and Planning, acting through their authorized
designees.
federal-aid contract: Contract that has a federal-aid project number on the cover of the Specifications.
holiday: Holiday shown in the following table:
Holidays
Holiday Date observed
Every Sunday Every Sunda
New Year's Day January 1st
Birthday of Martin Luther King, Jr. 3rd Monday in January
Presidents' Day 3rd Monday in February
Cesar Chavez Day March 31 st
Memorial Day Last Monday in May
Juneteenth June 19th
Independence Day July 4th
Labor Day 1st Monday in September
Veterans Day November 11th
Thanksgiving Day 4th Thursday in November
Day after Thanksgiving Day Day after Thanksgiving Da
Christmas Day December 25th
If January 1st, March 31st, June 19th, July 4th, November 11th, or December 25th fall on a Sunday, the
Monday following is a holiday. If January 1st, March 31st, July 4th, November 11th, or December 25th fall
on a Saturday, the preceding Friday is a holiday.
Office engineer: The Director of Public Works and Planning for the County of Fresno
permanent erosion control establishment period: Number of working days shown in Section 8-1.04 for
permanent erosion control establishment work.
plans: Standard plans, revised standard plans, and project plans.
1. standard plans: Drawings standard to Department construction projects. These plans are in a
book titled Standard Plans.
2. revised standard plans: New or revised standard plans. These plans are listed in the List of
Revised Standard Plans in a book titled Specifications.
3. project plans: Drawings specific to the project, including authorized shop drawings. These plans
also include a section titled Project Details of a book titled Specifications.
specifications: Standard specifications, revised standard specifications, and special provisions.
1. standard specifications: Specifications standard to Department construction projects. These
specifications are in a book titled Standard Specifications.
2. special provisions: Specifications specific to the project. These specifications are in a section
titled Special Provisions of a book titled Specifications.
Replace Section 1-1.08 with:
1-1.08 DISTRICTS
Not Used
Add to the end of Section 1-1.09
This project is not in a freeze-thaw area.
3
Replace Section 1-1.10 with:
1-1.10 PAVEMENT CLIMATE REGIONS
To help account for the effects of various climatic conditions on pavement performance, the State has
been divided into 9 climate regions. The project's pavement climate region is Inland Valley.
Replace Section 1-1.11 with:
1-1.11 WEBSITES,ADDRESSES, AND TELEPHONE NUMBERS
4
Websites, Addresses, and Telephone Numbers
Reference or
agency or
department unit Website Address Telephone no.
Authorized https://dot.ca.gov/program
Material Lists s/engineering=
Authorized services/authorized-
Material Source materials-lists
Lists
CA Unified
Certification https:Hcaliforniaucp.dbesy
Program's list of stem.com/
certified DBEs
California https:Hdot.ca.gov/program
MUTCD s/safety- -- --
ro rams/camutcd
https://www.fresnocountyc 2220 Tulare Street
Department a gov/ Design Division —Seventh Floor (559)600-9908
Fresno, CA 93721
Department of
Conservation, http://www.conservation.c
Office of Mine a.gov/dmr/
Reclamation
Department of 455 Golden Gate Ave
Industrial http://www.dir.ca.gov San Francisco CA 94102 --
Relations
Design Tel: (559) 353-
Services- 4919
Contract https: 2220 Tulare Street Fax:(559)455-
Administration, a.gov/planholders ountyc Design Division —Seventh Floor 4609 Email:
Planholders, a.gov/planholders Fresno, CA 93721 DesignServices(a)
Bid Results fresnocountyca.g
ov
Division of Major Construction Payment and
Accounting, Information Unit
Office of https://dot.ca.gov/program Office of External Accounts Payable
External s/accounting Division of Accounting (916)227-9013
Accounts Department of Transportation
Payable P.O. Box 168043
Sacramento, CA 95816-8043
Division of http://www.dot.ca.gov/hq/c
Construction onstruc/
Geotechnical Services
Geotechnical https:Hdot.ca.gov/program Department of Transportation (g16)227-7000
Services s/engineering-services 5900 Folsom Blvd
Sacramento, CA 95819-4612
Materials Engineering and Testing
https:Hdot.ca.gov/program Services
METS s/engineering-services Department of Transportation (916)227-7000
5900 Folsom Blvd
Sacramento, CA 95819-4612
https://dot.ca.gov/program
MPQP s/construction/material- -- --
lant- ualit - ro ram
5
Director of Public Works & Planning
Office Engineer __ Fresno County cn (559) 600-4078
2220 Tulare St, 8 Floor
Fresno, CA 93721
Office of
Electrical Office of Electrical Systems Regional
Systems Transportation Management Center
Regional -- 3165 Gold Valley Dr
Transportation Rancho Cordova, CA 95742
Management
Center
MSC 9-4/41
Offices of Documents Unit Offices of Structure
Structure Design (916)227-0716
Design, Department of Transportation
Documents Unit 1801 30th St
Sacramento, CA 95816-7006
Publication Unit
Publication Department of Transportation
Distribution Unit 1900 Royal Oaks Dr
Sacramento, CA 95815-3800
Replace Section 1-1.12 with:
1-1.12 MISCELLANY
Make checks and bonds payable to the County of Fresno.
2 BIDDING
2-1.01 GENERAL
Section 2 includes specifications related to bid eligibility and the bidding process.
2-1.02 BID INELIGIBILITY
A firm that has provided architectural or engineering services to the Department for this contract before
bid submittal for this contract is prohibited from any of the following:
1. Submitting a bid
2. Subcontracting for a part of the work
3. Supplying materials
2-1.03 CONTRACTOR REGISTRATION
No contractor or subcontractor may be listed on a bid proposal for a public works project unless
registered with the Department of Industrial Relations pursuant to Labor Code section 1725.5 [with limited
exceptions from this requirement for bid purposes only under Labor Code section 1771.1(a)].
Replace Section 2-1.04 with:
2-1.04 PREBID OUTREACH MEETING
Section 2-1.04 applies if a mandatory prebid meeting is shown on the Notice to Bidders.
The Department may conduct a meeting to provide access to the site and/or discuss the project in the
presence of County staff.
6
Each bidder must attend the meeting. The bidder's representative must be a company officer, project
superintendent, or project estimator. For a joint venture, one of the parties must attend the mandatory
prebid meeting.
The Department does not accept a bid from a bidder who did not attend the meeting.
A sign-in will be used to identify the attendees. Each bidder must include the name and title of the
company representative attending the meeting.
The Department may hold a single prebid meeting for more than one contract. Sign in for the contract you
intend to bid on. If you are bidding on multiple contracts, sign-in for each contract you intend to bid on.
The sign-in lists, with the names of all companies in attendance at each prebid meeting, will be made
available at the website shown on the Notice to Bidders for bidder inquiries.
Replace Section 2-1.06 with:
2-1.06 BID DOCUMENTS
2-1.06A General
The Bid book includes bid forms and certifications and may be requested from Design Services and are
available online at http://www.BidExpress.com.
The Specifications includes the Notice to Bidders, project details, and special provisions.
The Specifications, project plans, and any addenda to these documents may be accessed at the
planholders website at https://www.fresnocountyca.gov/planholders.
The Standard Specifications and Standard Plans may be accessed online at 2015 Caltrans Standard
Specifications and 2023 Caltrans Standard Specifications
2-1.06B Supplemental Project Information
The Department makes the following supplemental project information available:
Supplemental Project Information
Where Available Description
Included in Project Details 0 Location Map
• Construction Funding Sign
• County of Fresno Dummy Permit
If as-built drawings are available, they may not show existing dimensions and conditions. Where new
construction dimensions are dependent on existing bridge dimensions, verify the field dimensions and
adjust the dimensions of the work to fit the existing conditions.
7
Replace Section 2-1.12 with:
2-1.12 RESERVED
Replace Section 2-1.15 with:
2-1.15 RESERVED
Replace Section 2-1.18 with:
2-1.18 RESERVED
Replace Section 2-1.27 with:
2-1.27 RESERVED
Replace Section 2-1.33 with:
2-1.33 BID DOCUMENT COMPLETION AND SUBMITTAL
2-1.33A General
Complete forms in the Bid book.
Certain bid forms must be submitted with the bid and properly executed.
Certain other forms and information must be submitted either with the bid or within the prescribed period
after bid opening as specified elsewhere in these special provisions.
Failure to submit the forms and information as specified results in a nonresponsive bid.
If an agent other than the authorized corporation officer or a partnership member signs the bid, file a
Power of Attorney with the Department either before opening bids or with the bid. Otherwise, the bid may
be nonresponsive.
Electronic Bids: Complete and submit the bid online at http://www.BidExpress.com (Section 2-1.33). Your
electronic signature is your confirmation of and agreement to all certifications and statements contained in
the Bid book. On forms and certifications that you submit through the electronic bidding service, you
agree that each form and certification where a signature is required is deemed as having your signature.
Hardcopy Bid: Submit a hardcopy bid:
1. Under sealed cover
2. Marked as a bid
3. Identifying the contract number and the bid opening date
4. Use ink or typewriter
2-1.33B Bid Item List and Bid Comparison
Submit a bid based on the bid item quantities the Department shows on the Bid Item List (Proposal 2).
Bids will be evaluated and the low bidder determined as indicated in the Notice to Bidders.
Do not submit an unbalanced bid. An unbalanced is a bid is one in which one or more bid items is/are
considered by the Department to have been bid at an amount that is unreasonably high or unreasonably
low. A bid may be considered to be non-responsive and may be rejected if it is considered by the
Department to be unbalanced.
2-1.33C Bid Document Completion
Proposal items are identified by title and by the word "Proposal'followed by the number assigned to the
proposal item in question. Proposal items are included in the Bid Book.
8
2-1.33C(1) Proposal 1 - Proposal to the Board of Supervisors of Fresno County
2-1.33C(2) Proposal 2 - Bid Item List
One or more sheet(s) or list(s) upon which the bidder completes the bid.
Fill out completely including a unit price and total for each unit price-based item and a total for each lump
sum item.
Do not make any additions such as "plus tax", "plus freight", or conditions such as "less 2% if paid by
15th".
Use ink or typewriter for paper bids.
2-1.33C(3) Proposal 3 - Evaluation of Bid Item List
Describes how inconsistences and irregularities are evaluated and corrected when Design Services
reviews the Bid Item List.
2-1.33C(4) Proposal 4 - Bid Security and Signature
Submit one of the following forms of bidder's security equal to at least 10 percent of the bid:
• Cash
• Cashier's check
• Certified check
• Signed bidder's bond by an admitted surety insurer
Indicate type of bid security provided.
• Cash—Acceptable but not recommended. Cash is deposited in a clearing account and is
returned to bidders by County warrant. This process may take several weeks.
• Cashier's or Certified Checks. This type of security is held until the bid is no longer under
consideration. If submitted by a potential awardee, they will be returned when the contract is fully
executed by the bidder and bonds and insurance have been approved.
• Bid Bonds - Must be signed by the bidder and by the attorney-in-fact for the bonding company.
Provide notarized signature of attorney-in-fact accompanied by bonding company's affidavit
authorizing attorney-in-fact to execute bonds. An unsigned bid bond will be cause for rejection.
Bonding companies may provide their own bid bond forms. Bid Security and Signature sections must be
completed by the bidder and submitted with their bid.
Provide contractor's license information.
State business name and if business is a:
• Corporation - list officers
• Partnership- list partners
• Joint Venture- list members; if members are corporations or partnerships, list their officers or
partners.
• Individual - list Owner's name and firm name style
Signature of Bidder-the following lists types of companies and corresponding authorized signers.
• Corporation - by an officer
• Partnership- by a partner
• Joint Venture- by a member
• Individual - by the Owner
9
If signature is by a Branch Manager, Estimator, Agent, etc., the bid must be accompanied by a power of
attorney authorizing the individual to sign the bid in question or to sign bids more generally, otherwise the
bid may be rejected.
Business Address - Firm's Street Address
Mailing Address - P.O. Box or Street Address
Complete, sign, and return with bid.
2-1.33C(5) Proposal 5 - Noncollusion Declaration
Must be completed, signed, and returned with bid.
2-1.33C(6) Proposal 6 - Public Contract Code Section 10285.1 Statement
Select"has"or"has not" in accordance with instructions on form, return with completed for with bid. Note
that signing the bid constitutes signing this statement.
2-1.33C(7) Proposal 7 - Public Contract Code Section 10162 Questionnaire And Public Contract
Code 10232 Statement
Select: "yes" or"no" accordance with instructions on form, include explanation if"yes" is selected. Return
completed form with bid. Note that signing the bid constitutes signing this questionnaire and statement.
2-1.33C(8) Proposal 8 -Subcontractors
Sheet(s) or spaces where bidders list subcontractors. List each subcontractor to perform work in an
amount in excess of 1/2 of 1 percent of the total bid (Pub Cont Code §4100 et seq.).
The Subcontractor List submitted with the bid must show the name, location of business, work portions to
be performed, and the contractor's license number for each subcontractor listed.
• Use subcontractor's business name style as registered with the License Board.
• Specify the city in which the subcontractor's business is located and the state if other than
California.
• Description of the work to be performed by the subcontractor. Indicate with bid item numbers
from the bid item list and/or work descriptions similar to those on bid item list.
• List license number and Department of Industrial Relations registration number for each
subcontractor.
Upon request from Design Services, provide the following additional information within 24 hours of bid
opening if not included on the Subcontractor List submitted with the bid:
• Complete physical address for each subcontractor listed.
• Percentage of the total bid or dollar amount associated with each subcontractor listed.
2-1.33C(9) Proposal 9 -Title 13, California Code of Regulations § 2449(i) General Requirements for
In-Use Off-Road Diesel-Fueled Fleets
Contractors, if applicable, must submit valid Certificates of Reported Compliance with their bid.
Subcontractor certificates will be due no later than 4:00 p.m. on the fifth (51h) calendar day after the bid
opening if not submitted with the bid.
2-1.33C(18) Proposal 10 -2-1.33C(17) Proposal 18
Not used
2-1.33C(19) Proposal 19 - Guaranty
10
Does not need to be signed with the bid. Part of the contract which must be signed by the contractor
when contract is executed.
2-1.33D Electronic Bid Document Completion
Electronic versions of the bid book documents are available online at http://www.BidExpress.com, and
may be submitted through that website.
You must either attach an electronic bid bond or provide an original bid bond (or other form of bid security
authorized by Public Contract Code Section 20129(a)), prior to the bid opening.
Bidders submitting online may use one of the accepted electronic sureties (SurePath or Tinubu)to submit
their bid bond; or may submit cash, cashier's check, certified check, or a bidder bond to Design Services
at 2220 Tulare St., Seventh Floor, Fresno, CA 93721. Those submitting bid bonds directly to Design
Services must submit their bid bond:
1. Under sealed cover
2. Marked as a bid-bond
3. Identifying the contract number and the bid opening date on the cover
Replace Section 2-1.34 with:
2-1.34 BIDDER'S SECURITY
Submit one of the following forms of bidder's security equal to at least 10 percent of the bid:
1. Cash
2. Cashier's check
3. Certified check
4. Signed bidder's bond by an admitted surety insurer
Submit cash, cashier's check, certified check, or bidder's bond with your bid.
Replace Section 2-1.40 with:
2-1.40 BID WITHDRAWAL
1. An authorized agent may withdraw a bid before the bid opening date and time by submitting a written
bid withdrawal request at the location where the bid was submitted. Withdrawing a bid does not
prevent you from submitting a new bid. An authorized agent is an individual authorized to submit a
bid.
2. After the bid opening time, you cannot withdraw a bid.
2-1.41-2-1.42 RESERVED
2-1.43 BID OPENING
The Department publicly opens and reads bids at the time and place shown on the Notice to Bidders.
2-1.44-2-1.45 RESERVED
2-1.46 DEPARTMENT'S DECISION ON BID
The Department's decision on the bid amount is final.
The Department may reject:
1. All bids
2. A nonresponsive bid
11
Replace Section 2-1.47 with:
2-1.47 BID RELIEF
The Department may grant bid relief under Pub Cont Code § 5100 et seq. Submit any request for bid
relief via email to Design Services at the address listed in the table in Section 1-1.11.
Add Section 2-1.51:
2-1.51 DISCLOSURE OF SELF-DEALING TRANSACTIONS
This provision is only applicable if the contractor is operating as a corporation (a for-profit or non-profit
corporation)or if during the term of this agreement, the contractor changes its status to operate as a
corporation.
Members of the contractor's Board of Directors shall disclose any self-dealing transactions that they are a
party to while contractor is providing goods or performing services under this agreement. A self-dealing
transaction shall mean a transaction to which the contractor is a party and in which one or more of its
directors has a material financial interest. Members of the Board of Directors shall disclose any self-
dealing transactions that they are a party to by completing and signing a Self-Dealing Transaction
Disclosure Form which is included in Project Details of these special provisions.
In the event that the Contractor(to whom the project is awarded) is operating as a corporation or
incorporates during the course of the construction contract, and any member of its board of directors is
engaged or intends to become engaged in self-dealing transaction(s), each member of its board of
directors who is engaged or intends to become engaged in a self-dealing transaction or transactions must
complete and submit to the County a completed Self-Dealing Transaction Disclosure Form (in Project
Details)for each such transaction prior to engaging therein or immediately thereafter.
3 CONTRACT AWARD AND EXECUTION
Replace Section 3 with:
3-1.01 GENERAL
Section 3 includes specifications related to contract award and execution.
3-1.02 CONSIDERATION OF BIDS
3-1.02A General
Bids will be compared on the basis listed in the Notice to Bidders.
3-1.02B Tied Bids
The Department breaks a tied bid with a coin toss.
3-1.03 CONTRACTOR REGISTRATION
No contractor or subcontractor may be awarded a contract for public work on a public works project
(awarded on or after April 1, 2015) unless registered with the Department of Industrial Relations pursuant
to Labor Code section 1725.5.
3-1.04 CONTRACT AWARD
3-1.04A BID PROTEST PROCEDURES
Any bid protest must be submitted in writing and delivered by the Bidder by either of the following means:
(1)via e-mail to Des ianServices(@fresnocountyca.aov; or(2)via certified mail, return receipt requested to
the following address: Design Division, Department of Public Works and Planning, 2220 Tulare Street,
Sixth Floor, Fresno, CA 93721.
The bid protest must be received no later than 5:00 p.m. of the seventh (711) calendar day following
the bid opening for any issues found within the bid itself, or 5:00 p.m. of the third (3'd) calendar day
following the deadline for submittal of the specific bid document(s) placed at issue by the protest.
Any Bidder filing a protest is encouraged to submit the bid protest via e-mail, because the deadline is
12
based on the Department's receipt of the bid protest. A bid protest accordingly may be rejected as
untimely if it is not received by the deadline, regardless of the date on which it was postmarked. The
Bidder's compliance with the following additional procedures also is mandatory:
a. The initial protest document shall contain a complete statement of the grounds for the protest,
including a detailed statement of the factual basis and any supporting legal authority.
b. The protest shall identify and address the specific portion of the document(s)forming the basis for
the protest.
c. The protest shall include the name, address and telephone number of the person representing
the protesting party.
d. The Department will provide a copy of the initial protest document and any attached
documentation to all other Bidders or proposers who appear to have a reasonable prospect of
receiving an award depending upon the outcome of the protest.
e. The Board of Supervisors will issue a decision on the protest. If the Board of Supervisors
determines that a protest is frivolous, the party originating the protest may be determined to be
irresponsible and that party may be determined to be ineligible for future contract awards.
f. The procedure and time limits set forth herein are mandatory and are the Bidder's sole and
exclusive remedy in the event of a bid protest. Failure by the Bidder to comply with these
procedures shall constitute a waiver of any right to further pursue the bid protest, including the
subsequent filing of a Government Code Claim or legal proceedings.
3-1.04B AWARD PERIOD
If the Department awards the contract, the award is made to the lowest responsible bidder within 54
calendar days after bid opening.
The Department may extend the specified award period if the bidder agrees.
You may request to extend the award period by faxing a request to Design Services before 4:00 p.m. on
or before the last day of the award period. If you do not make this request, after the specified award
period:
1. Your bid becomes invalid
2. You are not eligible for the award of the contract
3-1.05 CONTRACT BONDS (PUB CONT CODE §§ 10221 AND 10222)
The successful bidder must furnish 2 bonds conforming to the requirements in the Agreement of these
special provisions.
3-1.06 CONTRACTOR LICENSE
For a federal-aid contract, the Contractor must be properly licensed as a contractor from contract award
through Contract acceptance (Pub Cont Code § 10164).
For a non-federal-aid contract:
1. Contractor must be properly licensed as a contractor from bid opening through Contract acceptance
(Bus & Prof Code § 7028.15)
2. Joint venture bidders must obtain a joint venture license before contract award (Bus & Prof Code §
7029.1)
13
3-1.07 INSURANCE POLICIES
The successful bidder must submit copies of its insurance policies conforming to the requirements in the
Agreement of these special provisions.
3-1.08—3-1.10 RESERVED
3-1.11 PAYEE DATA RECORD
Complete and deliver to the Engineer a Payee Data Record form when requested by the Engineer.
3-1.12 RESERVED
3-1.14-3-1.17 RESERVED
3-1.18 CONTRACT EXECUTION
The successful bidder must sign the Agreement.
Deliver to Design Services:
1. Signed Agreement
2. Contract bonds
3. Documents identified in section 3-1.07
4. For a federal-aid contract, Local Agency Bidder-DBE Information form
Design Services must receive these documents before the 10th business day after the bidder receives
the contract.
The bidder's security may be forfeited for failure to execute the contract within the time specified (Pub
Cont Code §§ 10181, 10182, and 10183).
3-1.19 BIDDERS' SECURITIES
The Department keeps the securities of the 1 st, 2nd, and 3rd low bidders until the contract has been
executed. The other bidders' securities, other than bidders' bonds, are returned upon determination of the
1st, 2nd, and 3rd low bidders, and their bidders' bonds are of no further effect (Pub Cont Code § 10184).
4 SCOPE OF WORK
Replace Section 4-1.02 with:
4-1.02 INTENT
The Contract intent is to provide for work completion using the best general practices.
Nothing in the specifications, special provisions, Standard Specifications, or in any other Contract
document voids the Contractor's public safety responsibilities.
Replace Section 4-1.07D with:
4-1.07D Reserved
Replace the last paragraph of Section 4-1.13 with:
Remove warning, regulatory, and guide signs when directed by the Engineer.
14
5 CONTROL OF WORK
Delete the last paragraph of Section 5-1.01
Add the following before the last sentence in Section 5-1.02:
Caltrans Standard Plans, County of Fresno Standard Drawings, and any other other-agency Standard
Drawings included in the "Project Details" section of the book entitled "Specifications" have the same
ranking as Standard Plans."
All other drawings in the "Project Details" section of the book entitled "Specifications" have the same
ranking as Project Plans.
Tables and other documents in the "Project Details" section of the book entitled "Specifications" have the
same ranking as Special Provisions. If a portion of a document in the Project Details section conflicts with
the Special Provisions, the Special Provisions shall prevail.
Replace Section 5-1.09 with:
5-1.09 RESERVED
Replace Section 5-1.12 with:
5-1.12 ASSIGNMENT
The performance of the Contractor or any Contract part may be assigned only with prior written consent
from the Department. To request consent, submit a Contractor Action Request—Assignment of Contract
Performance form. The Department does not consent to any requested assignment that would relieve you
of your surety of the responsibility to complete the work or any part of the work. No third-party agreement
relieves you or your surety of the responsibility to complete the work. Do not sell, transfer, or otherwise
dispose of any Contract part without prior written consent from the Department.
If you assign the right to receive Contract payments, the Engineer accepts the assignment upon the
Engineer's receipt of a Contractor Action Request—Assignment of Contract Monies, Assignee Change of
Name/Address form. Assigned payments remain subject to deductions and withholds described in the
Contract. The Department may use withheld payments for work completion whether payments are
assigned or not.
A pending or disapproved request for assignment does not relieve you of the responsibility to commence
and pursue work timely and in strict accordance with contract documents.
Replace Section 5-1.13C with:
5-1.13C RESERVED
Replace Section 5-1.13D with:
5-1.13D RESERVED
Add the following paragraph to the end of section 5-1.16:
Submit Daily Log records to the Engineer weekly for the entire course of work unless the Engineer
requests another interval.
Replace Section 5-1.20B(4)with:
5-1.20B(4) Contractor—Property Owner Agreement
The County contacted the owner of the property APN 03518044, immediately south of the school
property.
The property owner is willing to cooperate with the contractor to use their site as an area for proper
disposing of mud, cutting and development water during the construction of the well. The contractor is
responsible for coordinating and obtaining authorization per this section. Any potential fees that may be
15
requested by the owner shall be included in the carious items of work and no further compensation will be
allowed therefor.
Private property contact information: Liz Clark, phone number(559) 284-5110.
Before procuring material from or disposing or stockpiling of material, or development water, or staging
materials and equipment on non-highway property:
1. Provide proof that the property where materials are to be disposed of or equipment
parked/stored is appropriately zoned and/or permitted for the use proposed by the Contractor.
2. Obtain written authorization from each and every owner of the property where materials are to
be dispose of, stockpiled or equipment parked/stored.
3. Provide proof that the signor(s)of the authorization are the owners of the property or
authorized person.
4. Provide an executed release from the property owner(s) absolving the Department from any
and all responsibility in connection with the disposing of materials or parking/storage of equipment on said
property.
5. Obtain written permission from the Engineer to dispose of materials or park/store equipment at
the location designated in said authorization.
Before Contract acceptance, submit a document signed by the owner of the material source or disposal
site stating that the Contractor has complied with the Contractor-owner agreement.
Failure by the Contractor to provide written authorization shall result in the withholding of all funds due to
the Contractor until said authorization is received by the County.
Replace Section 5-1.20C with:
5-1.20C Permits with County of Fresno Building Department and Health Department
Contractor is required to obtain the necessary permits from the County of Fresno Health Department and
Building Department.
A dummy permit with the Building Department required permits and fees are incorporated in the Project
Details sections of these Specifications
Replace Section 5-1.23A with:
5-1.23A General
Section 5-1.23 includes specifications for action and informational submittals. Attention is directed to
Section 01 33 00 Submittal Procedures of the Technical specifications
Any submittal not specified as an informational submittal is an action submittal.
Submit action and informational submittals to the Engineer. Unless otherwise specified in these
Specifications, submittals shall be provided via email in .pdf format.
Each submittal must have a cover sheet that must include:
1. Contract number
2. Project Name
3. Date
4. Submittals (and resubmittals if applicable) must be numbered sequentially
16
5. Structure number if applicable
6. Contractor
7. Person responsible for submitting the submittal
8. Signature of Contractor's representative sending submittal
9. Section number and/or item submittal is referencing
10. Pages of submittal, excluding cover sheet
The Department rejects a submittal if it has any error or omission.
If the last day for submitting a document falls on a Saturday or holiday, it may be submitted on the next
business day with the same effect as if it had been submitted on the day specified.
Documents must be submitted in the English language.
Convert documents to US customary units.
Replace the first paragraph of Section 5-1.23B(2)(b) with:
If specified, email electronic shop drawing and calculation sheet submittals to the Engineer.
Replace Section 5-1.24 with:
5-1.24 CONSTRUCTION SURVEYS
The Engineer places stakes and/or marks as the Engineer determines to be necessary to establish the
lines and grades required for the work.
Submit your request for Engineer-furnished stakes:
1 Once staking area is ready for stakes
2. On a Request for Construction Stakes form
After your submittal, the Engineer starts staking within 2 working days.
Preserve stakes and marks placed by the Engineer. If the stakes or marks are destroyed, the Engineer
replaces them at the Engineer's earliest convenience and deducts the cost.
Replace Section 5-1.27E with:
5-1.27E CHANGE ORDER BILLS
Maintain separate records for change order work costs.
Replace Section 5-1.32 with:
5-1.32 AREAS FOR USE
Occupy the highway only for purposes necessary to perform the work.
Defend, indemnify, and hold the Department harmless to the same extent as under section 7-1.05.
The Department does not allow temporary residences within the County right-of-way.
Replace Section 5-1.43A with:
5-1.43A General
Minimize and mitigate the impacts of work or events for which you will make a potential claim.
For each potential claim assign an identification number determined by chronological sequencing and the
1st date of the potential claim.
Use the identification number for each potential claim on the:
1. Initial Potential Claim Record form
17
2. Supplemental Potential Claim Record form
3. Full and Final Potential Claim Record form
Failure to comply with this procedure is:
1. Waiver of the potential claim and a waiver of the right to a corresponding claim for the disputed work
in the administrative claim procedure
2. Bar to arbitration (Pub Cont Code § 10240.2)
Replace the word "State" with "Department" in the 3rd paragraph of Section 5-1.43D.
Replace the word "Department's" with "Caltrans" in the 6t" paragraph of Section 5-1.43E(1)(a).
Replace the word "Department" with "Caltrans" where it appears in Section 5-1.43E(2)(a).
Replace the word "Department" with "Caltrans" where it appears in Section 5-1.43E(3)(a).
6 CONTROL OF MATERIALS
Replace section 6-1.05 with:
6-1.05 SPECIFIC BRAND OR TRADE NAME AND SUBSTITUTION
Unless substitution is expressly precluded in the special provisions, a reference to a specific brand or
trade name establishes a quality standard and is not intended to limit competition. Unless the Department
has made a public interest finding expressly authorizing sole source procurement of a particular item, you
may use a product that is equal to or better than the specified brand or trade name if authorized.
Submit a substitution request with a time period that:
1. Follows Contract award
2. Allows 30 days for review
3. Causes no delay
Include substantiating data with the substitution request that proves that substitution:
1. Causes no delay
2. Is of equal or better quality and suitability
If the special provisions disallow substitution of a particular item, provide the specified item and do not
propose substitution.
Replace Section 6-1.06 with%
6-1.06 RESERVED
7 LEGAL RELATIONS AND RESPONSIBILITY TO THE PUBLIC
Add after the last paragraph of Section 7-1.02C:
The following information is provided for the Contractor's information, and nothing herein or elsewhere
within these special provisions shall be construed as limiting the Contractor's responsibility for complying
with all applicable rules and regulations. In conformance with Title 13 § 2449(i), between March 1 and
June 1 of each year, new valid Certificates of Reported Compliance for the current compliance year, as
defined in section 2449(n)for the Contractor and all applicable subcontractors must be submitted. Submit
18
new valid Certificates of Reported Compliance to the Engineer at least one week prior to the expiration
date of the current certificate.
Replace the 2"d Paragraph of Section 7-1.02K(2) with:
The general prevailing wage rates and any applicable changes to these wage rates are available:
1. From Design Services
2. From the Department of Industrial Relations'Web site
Add to the list in the second paragraph of Section 7-1.02K(3)with:
1.10. Fringe Benefits
Replace section 7-1.02K(4)(a) with:
7-1.02K(4)(a) Apprenticeship Requirements for non-Federal Projects
A. Pursuant to Sections 1770-1780 of the Labor Code of the State of California, the Director of
the Department of Industrial Relations has determined the general prevailing rate of wages in
the locality for each craft or type of worker needed to execute the work. Said wage rates
pursuant to Section 1773.2 of the Labor Code are on file with the Clerk to the Fresno County
Board of Supervisors, and will be made available to any interested person on request. A
copy of this wage scale may also be obtained at the following Web Site: www.dir.ca.gov/dlsr.
B. Pursuant to Section 1775 of the Labor Code of the State of California, nothing in this Article
shall prevent the employment of properly registered apprentices upon public works. Every
such apprentice shall be paid the standard wage paid to apprentices under the regulations of
the craft or trade at which he/she is employed, and shall be employed only at the work of the
craft or trade to which he/she is registered.
C. Only apprentices, as defined in Section 3077, who are in training under apprenticeship standards
and written apprentice agreements under Chapter 4 (commencing at Section 3070), Division
3, of the Labor Code, are eligible to be employed on public works. The employment and
training of each apprentice shall be in accordance with the provisions of the apprenticeship
standards and apprentice agreements under which he/she is training.
Replace the 4th paragraph of section 7-1.02K(6)(j)(ii)with:
Submit the lead compliance plan as an informational submittal.
Add to the end of Section 7-1.02M(2):
Except for motor trucks, truck tractors, buses, and passenger vehicles, equip all hydrocarbon-fueled
engines, both stationary and mobile including motorcycles, with spark arresters that meet USFS
standards as specified in the Forest Service Spark Arrester Guide. Maintain the spark arresters in good
operating condition. Spark arresters are not required by Cal Fire, the BLM, or the USFS on equipment
powered by properly maintained exhaust-driven turbo-charged engines or equipped with scrubbers with
properly maintained water levels. The Forest Service Spark Arrester Guide is available at the district
offices.
Each toilet must have a metal ashtray at least 6 inches in diameter by 8 inches deep half-filled with sand
and within easy reach of anyone using the facility.
Locate flammable materials at least 50 feet away from equipment service, parking, and gas and oil
storage areas. Each small mobile or stationary engine site must be cleared of flammable material for a
radius of at least 15 feet from the engine.
19
Each area to be cleared and grubbed must be cleared and kept clear of flammable material such as dry
grass, weeds, brush, downed trees, oily rags and waste, paper, cartons, and plastic waste. Before
clearing and grubbing, clear a fire break at the outer limits of the areas to be cleared and grubbed. Other
fire breaks may be ordered and are change order work.
Furnish the following fire tools:
1. 1 shovel and 1 fully charged fire extinguisher UL rated at 4 B:C or more on each truck, personnel
vehicle, tractor, grader, or other heavy equipment.
The pickup truck and operator must patrol the area of construction for at least 1/2 hour after job site
activities have ended.
Cal Fire, USFS, and BLM have established the following adjective class ratings for 5 levels of fire danger
for use in public information releases and fire protection signing: low, moderate, high, very high, extreme.
Obtain the fire danger rating daily for the project area from the nearest Cal Fire unit headquarters, USFS
ranger district office, or BLM field office.
Arrangements have been made with Cal Fire, USFS, and BLM to notify the Department when the fire
danger rating is very high or extreme. This information will be furnished to the Engineer who will notify
you for dissemination and action in the area affected. If a discrepancy between this notice and the fire
danger rating obtained from the nearest office of either Cal Fire or USFS exists, you must conduct
operations according to the higher of the two fire danger ratings.
If the fire danger rating reaches very high:
1. Falling of dead trees or snags must be discontinued.
2. No open burning is permitted and fires must be extinguished.
3. Welding must be discontinued except in an enclosed building or within an area cleared of flammable
material for a radius of 15 feet.
4. Blasting must be discontinued.
5. Smoking is allowed only in automobiles and cabs of trucks equipped with an ashtray or in cleared
areas immediately surrounded by a fire break unless prohibited by other authority.
6. Vehicular travel is restricted to cleared areas except in case of emergency.
If the fire danger rating reaches extreme, take the precautions specified for a very high fire danger rating
except smoking is not allowed in an area immediately surrounded by a firebreak and work of a nature that
could start a fire requires that properly equipped fire guards be assigned to such operation for the
duration of the work.
The Engineer may suspend work wholly or in part due to hazardous fire conditions. The days during this
suspension are non—working days.
If field and weather conditions become such that the determination of the fire danger rating is suspended,
section 7-1.02M(2)will not be enforced for the period of the suspension of the determination of the fire
danger rating. The Engineer will notify you of the dates of the suspension and resumption of the
determination of the fire danger rating.
Place the contents of Section 7-1.04 under the heading:
7-1.04 PUBLIC SAFETY
7-1.04A General
Replace the 7t" paragraph in Section 7-1.04A with:
Provide flaggers whenever necessary to ensure that the public is given safe guidance through the work
zone.
20
Replace the 111" paragraph in Section 7-1.04A with:
Cover signs that direct traffic to a closed area.
Add to the end of Section 7-1.04A:
Where 2 or more lanes in the same direction are adjacent to the area where the work is being performed,
including shoulders, the adjacent lane must be closed under any of the following conditions:
1. Work is off the traveled way but within 6 feet of the edge of the traveled way, and the approach speed
is greater than 45 miles per hour
2. Work is off the traveled way but within 3 feet of the edge of the traveled way, and the approach speed
is less than 45 miles per hour
Closure of the adjacent traffic lane is not required when performing any of the following:
1. Working behind a barrier
2. Paving, grinding, or grooving
3. Installing, maintaining, or removing traffic control devices except Type K temporary railing
Do not reduce an open traffic lane width to less than 10 feet. When traffic cones or delineators are used
for temporary edge delineation, the side of the base of the cones or delineators nearest to traffic is
considered the edge of the traveled way.
Add the following to the end of Section 7-1.04:
7-1.04B WORK ZONE SAFETY AND MOBILITY
7-1.04B(1) POLICY
In order to ensure safe and efficient flow of traffic through work zones, the County of Fresno, via its
General Plan, Transportation and Circulation Element, Policy TRA-1, has adopted the use of AASHTO
Standards as supplemented by Caltrans and County Department of Public Works and Planning
Standards.
7-1.04B(2)TRAFFIC MANAGEMENT PLAN
Perform traffic management shall be in accordance with Section 12, "TEMPORARY TRAFFIC
CONTROL,"of these special provisions.
7-1.04B(3)TEMPORARY TRAFFIC CONTROL PLAN
Prepare traffic control plan(s) in accordance with Section 12, "TEMPORARY TRAFFIC CONTROL," of
these special provisions.
7-1.04B(4)PUBLIC INFORMATION
Provide notice to public agencies and others to the extent required, if any, elsewhere in these special
provisions. The Engineer provides other noticing not identified to be performed by the Contractor.
Replace the word "State" with "County" where it occurs in Section 7-1.05C.
Replace the word "State" with "Department" in the 15t paragraph of Section 7-1.06B.
Replace the word "State" with "County" in the 51h paragraph of Section 7-1.06C.
Replace the word "State" with "the Department" in Section 7-1.061)(1).
Replace Section 7-1.061)(2)with:
21
7-1.06D(2) Liability Limits/Additional Insureds
Refer to the Agreement of these special provisions
Additional insured coverage must be provided by a policy provision or by an endorsement providing
coverage at least as broad as Additional Insured(Form B) endorsement form CG 2010 and CG 2037 (for
completed operations), as published by the Insurance Services Office (ISO), or equivalent form as
approved by the Department.
Replace the word "State" with "County" in Section 7-1.06D(3).
Replace the word "State" with "County" in Section 7-1.06D(4).
Replace Section 7-1.06E with:
7-1.06E Automobile Liability Insurance
Comply with requirements in the Agreement of these special provisions.
Replace Section 7-1.06G with:
7-1.06G NOT USED
Replace Section 7-1.06H with:
7-1.06H Enforcement
The Department may assure your compliance with your insurance obligations. 30 days before an
insurance policy lapses, expires, or is canceled during the Contract period you must submit to the
Department evidence of renewal or replacement of the policy.
If you fail to maintain any required insurance coverage, the Department may maintain this coverage and
withhold or charge the expense to you or terminate your control of the work.
Any failure to comply with the reporting provisions of your policy shall not affect coverage provided to the
Department, including its officers, directors, agents (excluding agents who are design professionals), and
employees.
You are not relieved of your duties and responsibilities to indemnify, defend, and hold harmless the
County, its officers, agents, and employees by the Department's acceptance of insurance policies and
certificates.
Minimum insurance coverage amounts do not relieve you for liability in excess of such coverage, nor do
they preclude the County from taking other actions available to it, including the withholding of funds under
this Contract.
Replace Section 7-1.061 with:
7-1.061 Self-Insurance
Comply with the Agreement of these special provisions.
Add to the beginning of Section 7-1.0713:
This section applies to seal coat projects.
Add Section 7-1.07C:
7-1.07C Claims
This section applies to non-seal coat projects which involve asphalt concrete paving. Pay for claims for
personal property damage caused by your work. Claims are limited to:
1. 10 percent of the total bid
Within 30 days of the last working day placement of hot mix asphalt, do the following:
22
1. Process and resolve all claims reported or submitted to you by the public as follows:
1.1. Within 3 business days of receipt of a claim, submit to the Department a copy of the claim, a
written analysis of the claim, and a statement indicating whether or not you will pay the claim. If
you reject a claim, provide the reasons for rejection in writing.
1.2. If the claimant becomes dissatisfied with your handling of the claim, immediately refer the
claimant to the local district claims office for assistance in resolving the claim.
2. Submit to the Department evidence of your paid claims.
All claims presented to the Department, (Govt Code § 900 et seq.) are processed and resolved by the
Department as follows:
1. The claims are processed as formal government claims subject to all laws and policies and are
resolved as the Department determines including referring the claim to you for handling.
2. If the Department approves settlement of a claim or is ordered to pay pursuant to a court order, the
claim is paid from funds withheld from you.
3. Within 3 business days of the Department's determination that you are responsible for resolving the
claim, the Department sends a copy of the claim to you for resolution or notifies you of the
Department's decision to resolve the claim.
The Department withholds an amount not to exceed 5 percent of the total bid to resolve all claims. The
amount is held no longer than 60 days following the last working day so that the Department has ample
time to resolve any pending claims. After 60 days, any remaining amount withheld is returned to you.
If no withheld funds remain or have been returned, the Department may pay any claims and seek
reimbursement from you through an offset or any other legal means. Any reimbursement or offset to be
recovered from you, including all other paid claims, is limited to 10 percent of the total bid.
Section 7-1.07C does not limit your obligation to defend and indemnify the Department.
8 PROSECUTION AND PROGRESS
Replace Section 8-1.01 with:
8-1.01 GENERAL
Section 8 includes specifications related to prosecuting the Contract and work progress.
8-1.01A Work Hours
Perform all work on working days during daytime except drilling operations that may proceed 24 hrs a
day.
You may request approval to work on a holiday or on a non-working day. If, pursuant to such request, the
Engineer authorizes you to work on a holiday or on a non-working day, you pay the actual cost incurred
by the Department to perform all inspection, surveying, testing, and all other project-related work by the
Department on such holiday or non-working day. Such payment will be deducted from monies due or
which may become due to the Contractor.
Plan work so that all construction operations performed each day, including cleanup of the project site,
establishment of appropriate traffic control and any other work necessary for the safety of the public shall
be completed within the daytime hours.
Do not perform work during nighttime unless approved by the Engineer, except drilling operations that
may proceed 24 hrs a day.
For work other than drilling operations, request approval to work during nighttime in writing and include
the appropriate traffic control plan(s) and work plan(s)which clearly identify all provisions for illuminating
all portions of the work site, including any flagging operations.
For work other than drilling operations, if you fail to complete work during the daytime hours, the Engineer
may stop all work upon the onset of nighttime and order you to perform any and all work the Engineer
deems necessary to ensure the safety of the public during the nighttime hours.
23
You are not entitled to any additional compensation or extension of the contract time as a result of the
Engineer stopping the work due to the onset of nighttime.
Replace the 111 paragraph of Section 8-1.02B(1) with:
No pay item is provided for Level 1 Critical Path Project Schedule. Payment is considered to be included
in the various items of work including revisions and time analysis.
Add to the end of the list in the 4t" paragraph of Section 8-1.02B(3)with:
3. Time Impact Analysis (Refer to Section 8-1.02C(8)(b)for description)
Replace Section 8-1.02C with:
8-1.02C Reserved except for 8-1.02C(8)(b)
Replace Section 8-1.04 with:
8-1.04 START OF JOB SITE ACTIVITIES
8-1.04A General
Provide signed contracts, bonds, and evidence of insurance timely as required.
This section, 8-1.04, "Start of Job Activities," does not modify remedies available to the Department
should you fail to provide signed contracts bonds and insurance timely.
Submit a notice 72 hours before starting job site activities. If the project has more than 1 location of work,
submit a separate notice for each location.
You may start job site activities before receiving notice of Contract approval if you:
1. Deliver the signed Contract, bonds, and evidence of insurance to the Department
2. Submit 72-hour notice
3. Are authorized by the Department to start
4. Perform work at your own risk
5. Perform work under the Contract
If the Contract is approved, work already performed that complies with the Contract is authorized.
If the Contract is not approved, leave the job site in a neat condition. If a facility has been changed,
restore it to its former condition or an equivalent condition. The Department does not pay for the
restoration.
8-1.04B Reserved
Replace Section 8-1.04C with:
8-1.04C Long Lead Time Equipment Start
Section 8-1.04B, Standard Start, does not apply to this project.
This project includes two, non-concurrent phases.
The first order of work (submittals) involves potholing, submittals and equipment procurement.
The second order of work involves physical construction upon the project site.
8-1.04C(1) First Order of Work, Submittals
Be prepared to begin the first order of work no later than the 20th business day after award of the
Contract by the Department.
The Engineer may issue a notice to proceed with the first order of work as soon as the Contracts,
including bonds and insurance certificates, have been approved.
24
Start the first order of work on the day shown in the notice to proceed, unless an early start has been
approved.
The Engineer may issue a notice of commencement of contract time for the first order of work if you fail to
provide Contracts, including bonds and insurance certificates or other required documents timely.
The Engineer shall have a maximum of ten (10)working days in which to review and approve or reject
each submittal from the Contractor. In the event that the Engineer rejects any of the Contractor's initial
submittals, the Engineer shall have a maximum of ten (10)working days in which to review and approve
or reject each re-submittal from the Contractor. The ten (10)working day time period for the Engineer's
review shall commence on the day upon which the Engineer receives the submittal or re-submittal in
question.
In the event that the Engineer's review of a submittal or re-submittal requires in excess of ten (10)
working days, the Engineer shall extend the number of working days allowed for the completion of the
first order of work by one working day for each working day of delay in the Engineer's completion of the
review.
The first order of work is complete when you:
• have received approval for all submittals required for the project.
• have furnished a statement from the vendors that the orders for required equipment and
materials has been received and accepted by said vendor
• have furnished a statement from vendors which indicates that the anticipated delivery date for the
equipment and materials ordered is in conformance with contract requirements.
• Receive a written statement that the first order of work is complete.
Complete the first order of work before the expiration of
FIFTY(50) WORKING DAYS
from the date shown in said Notice to Proceed, or in the Notice of Commencement of Contract Time,
whichever was issued first.
Pay to the County of Fresno the sum of
FIVE HUNDRED DOLLARS ($500)
per day for each and every calendar day's delay in finishing the first order of work in excess of the
number of working days prescribed above.
8-1.04C(2) Second Order of Work
The Engineer, in their sole discretion, may issue the Notice to Proceed —Second Order of Work
immediately upon delivery to the Contractor of the materials and equipment necessary to construct the
project. Alternatively, the Engineer may defer issuance of the Notice to Proceed —Second Order of Work
to the extent the Engineer, in their sole discretion, deems appropriate.
Begin work at the site on the date shown on the Notice to Proceed —Second Order of Work. Do not
begin site work prior to the date shown on the Notice to Proceed —Second Order of Work. The date
shown on the Notice to Proceed —Second Order of Work will be the first working day charged against the
allotted number of working days for the second order of work.
Complete the second order of work before the expiration of
ONE HUNDRED (100) WORKING DAYS
from the date shown in said Notice to Proceed —Second Order of Work.
25
Complete all work, including corrective work and punch list work, prior to the expiration of the allotted
working days. Working days continue to accrue until corrective work and punch list work is completed
and accepted.
Pay to the County of Fresno the sum of
THREE THOUSAND DOLLARS ($3,000)
per day for each and every calendar day's delay in finishing the second order of work, including corrective
work and punch list work, in excess of the number of working days prescribed above.
Such payment is in addition to payment, if any, for failure to complete the first order of work as specified.
Replace the 111 paragraph in Section 8-1.05 with:
Contract time starts on the day specified in the notice to proceed or in the notice of commencement of
contract time as described in section 8-1.04 or on the day you start job site activities, whichever occurs
first.
Replace the 3rd and 4tn paragraph including the table in Section 8-1.10A with:
Liquidated damages are specified in section 8-1.04.
Replace the word "State's" with "County's" in Section 8-1.14A.
9 PAYMENT
Add Section 9-1.01A:
9-1.01A COMPENSATION
The bid items shown in the bid item list represent full compensation for performing all work. Full
compensation for any work for which there is no bid item shall be considered to be included in the various
items of work.
Delete paragraphs 11-14 of Section 9-1.03.
Add after the 61" paragraph of Section 9-1.03:
Notwithstanding anything to the contrary in these special provisions, full compensation for
performing all work as shown, as specified, and as directed by the Engineer is considered to be
included in the various bid items, and no additional payment will be made, except pursuant to a
contract change order to perform work not shown and/or specified.
If one or more bid item(s) is/are not included, perform the work as shown and as specified and
payment therefor is considered to be included in the various items of work.
Replace the last paragraph of Section 9-1.03 with:
Pay your subcontractors within 10 days of receipt of each progress payment under Pub Cont Code §§
10262 and 10262.5.
Replace the word "Department's" with "Caltrans" in the 5tn paragraph of Section 9-1.07A.
Replace Section 9-1.16F with:
9-1.16F Retentions
The Department, once in each month, shall cause an estimate in writing to be made by the Engineer.
The estimate shall include the total amount of work done and acceptable materials furnished, provided
the acceptable materials are listed as eligible for partial payment as materials in the special provisions
and are furnished and delivered by the Contractor on the ground and not used or are furnished and
26
stored for use on the contract, if the storage is within the State of California and the Contractor furnishes
evidence satisfactory to the Engineer that the materials are stored subject to or under the control of the
Department, to the time of the estimate, and the value thereof. The estimate shall also include any
amounts payable for mobilization. Daily extra work reports furnished by the Contractor less than 5
calendar days, not including Saturdays, Sundays and legal holidays, before the preparation of the
monthly progress estimate shall not be eligible for payment until the following month's estimate.
The amount of any material to be considered in making an estimate will in no case exceed the amount
thereof which has been reported by the Contractor to the Engineer on State-furnished forms properly
filled out and executed, including accompanying documentation as therein required, less the amount of
the material incorporated in the work to the time of the estimate. Only materials to be incorporated in the
work will be considered. The estimated value of the material established by the Engineer will in no case
exceed the contract price for the item of work for which the material is furnished.
The Department shall retain 5 percent of the estimated value of the work done and 5 percent of the value
of materials so estimated to have been furnished and delivered and unused or furnished and stored as
aforesaid as part security for the fulfillment of the contract by the Contractor. The Department will not
hold retention for mobilization or demobilization.
The Department shall pay monthly to the Contractor, while carrying on the work, the balance not retained,
as aforesaid, after deducting therefrom all previous payments and all sums to be kept or retained under
the provisions of the contract. No monthly estimate or payment shall be required to be made when, in the
judgment of the Engineer, the work is not proceeding in accordance with the provisions of the contract.
No monthly estimate or payment shall be construed to be an acceptance of any defective work or
improper materials.
Attention is directed to the prohibitions and penalties pertaining to unlicensed contractors as provided in
Business and Professions Code Sections 7028.15(a) and 7031.
Add Section 9-1.23:
9-1.23 RESOLUTION OF CONTRACT CLAIMS
Public works contract claims of three hundred seventy-five thousand dollars ($375,000)or less which arise
between a Contractor and a local public agency shall be resolved in accordance with the provisions of
California Public Contract Code Sections 20104-20104.6, inclusive. In addition, California Public Contract
Code Section 9204 requires that the procedure established therein shall apply to all claims (as therein
defined)filed by a contractor in connection with a public works project. Accordingly, this contract expressly
incorporates all of the terms and conditions of those statutory provisions, which are as follows:
California Public Contract Code Section 9204
(a) The Legislature finds and declares that it is in the best interests of the state and its citizens to ensure
that all construction business performed on a public works project in the state that is complete and not in
dispute is paid in full and in a timely manner.
(b) Notwithstanding any other law, including, but not limited to, Article 7.1 (commencing with Section
10240)of Chapter 1 of Part 2, Chapter 10 (commencing with Section 19100)of Part 2, and Article 1.5
(commencing with Section 20104)of Chapter 1 of Part 3, this section shall apply to any claim by a
contractor in connection with a public works project.
(c) For purposes of this section:
(1) "Claim" means a separate demand by a contractor sent by registered mail or certified mail
with return receipt requested, for one or more of the following:
(A)A time extension, including, without limitation, for relief from damages or penalties for
delay assessed by a public entity under a contract for a public works project.
27
(B) Payment by the public entity of money or damages arising from work done by, or on
behalf of, the contractor pursuant to the contract for a public works project and payment
for which is not otherwise expressly provided or to which the claimant is not otherwise
entitled.
(C) Payment of an amount that is disputed by the public entity.
(2) "Contractor" means any type of contractor within the meaning of Chapter 9 (commencing with
Section 7000)of Division 3 of the Business and Professions Code who has entered into a direct
contract with a public entity for a public works project.
(3)(A) "Public entity" means, without limitation, except as provided in subparagraph (B), a state
agency, department, office, division, bureau, board, or commission, the California State
University, the University of California, a city, including a charter city, county, including a charter
county, city and county, including a charter city and county, district, special district, public
authority, political subdivision, public corporation, or nonprofit transit corporation wholly owned by
a public agency and formed to carry out the purposes of the public agency.
(B) "Public entity" shall not include the following:
(i)The Department of Water Resources as to any project under the jurisdiction of
that department.
(ii)The Department of Transportation as to any project under the jurisdiction of
that department.
(iii)The Department of Parks and Recreation as to any project under the
jurisdiction of that department.
(iv)The Department of Corrections and Rehabilitation with respect to any project
under its jurisdiction pursuant to Chapter 11 (commencing with Section 7000) of
Title 7 of Part 3 of the Penal Code.
(v)The Military Department as to any project under the jurisdiction of that
department.
(vi)The Department of General Services as to all other projects.
(vii)The High-Speed Rail Authority.
(4) "Public works project' means the erection, construction, alteration, repair, or improvement of
any public structure, building, road, or other public improvement of any kind.
(5) "Subcontractor" means any type of contractor within the meaning of Chapter 9 (commencing
with Section 7000) of Division 3 of the Business and Professions Code who either is in direct
contract with a contractor or is a lower tier subcontractor.
(d) (1) (A) Upon receipt of a claim pursuant to this section, the public entity to which the claim applies
shall conduct a reasonable review of the claim and, within a period not to exceed 45 days, shall provide
the claimant a written statement identifying what portion of the claim is disputed and what portion is
undisputed. Upon receipt of a claim, a public entity and a contractor may, by mutual agreement, extend
the time period provided in this subdivision.
(B) The claimant shall furnish reasonable documentation to support the claim.
(C) If the public entity needs approval from its governing body to provide the claimant a
written statement identifying the disputed portion and the undisputed portion of the claim,
and the governing body does not meet within the 45 days or within the mutually agreed to
extension of time following receipt of a claim sent by registered mail or certified mail,
return receipt requested, the public entity shall have up to three days following the next
duly publicly noticed meeting of the governing body after the 45-day period, or extension,
expires to provide the claimant a written statement identifying the disputed portion and
the undisputed portion.
(D)Any payment due on an undisputed portion of the claim shall be processed and made
within 60 days after the public entity issues its written statement. If the public entity fails
to issue a written statement, paragraph (3) shall apply.
28
(2) (A) If the claimant disputes the public entity's written response, or if the public entity fails to
respond to a claim issued pursuant to this section within the time prescribed, the claimant may
demand in writing an informal conference to meet and confer for settlement of the issues in
dispute. Upon receipt of a demand in writing sent by registered mail or certified mail, return
receipt requested, the public entity shall schedule a meet and confer conference within 30 days
for settlement of the dispute.
(B)Within 10 business days following the conclusion of the meet and confer conference,
if the claim or any portion of the claim remains in dispute, the public entity shall provide
the claimant a written statement identifying the portion of the claim that remains in
dispute and the portion that is undisputed. Any payment due on an undisputed portion of
the claim shall be processed and made within 60 days after the public entity issues its
written statement. Any disputed portion of the claim, as identified by the contractor in
writing, shall be submitted to nonbinding mediation, with the public entity and the claimant
sharing the associated costs equally. The public entity and claimant shall mutually agree
to a mediator within 10 business days after the disputed portion of the claim has been
identified in writing. If the parties cannot agree upon a mediator, each party shall select a
mediator and those mediators shall select a qualified neutral third party to mediate with
regard to the disputed portion of the claim. Each party shall bear the fees and costs
charged by its respective mediator in connection with the selection of the neutral
mediator. If mediation is unsuccessful, the parts of the claim remaining in dispute shall be
subject to applicable procedures outside this section.
(C) For purposes of this section, mediation includes any nonbinding process, including,
but not limited to, neutral evaluation or a dispute review board, in which an independent
third party or board assists the parties in dispute resolution through negotiation or by
issuance of an evaluation. Any mediation utilized shall conform to the timeframes in this
section.
(D) Unless otherwise agreed to by the public entity and the contractor in writing, the
mediation conducted pursuant to this section shall excuse any further obligation under
Section 20104.4 to mediate after litigation has been commenced.
(E) This section does not preclude a public entity from requiring arbitration of disputes
under private arbitration or the Public Works Contract Arbitration Program, if mediation
under this section does not resolve the parties' dispute.
(3) Failure by the public entity to respond to a claim from a contractor within the time periods
described in this subdivision or to otherwise meet the time requirements of this section shall result
in the claim being deemed rejected in its entirety. A claim that is denied by reason of the public
entity's failure to have responded to a claim, or its failure to otherwise meet the time requirements
of this section, shall not constitute an adverse finding with regard to the merits of the claim or the
responsibility or qualifications of the claimant.
(4)Amounts not paid in a timely manner as required by this section shall bear interest at 7
percent per annum.
(5) If a subcontractor or a lower tier subcontractor lacks legal standing to assert a claim against a
public entity because privity of contract does not exist, the contractor may present to the public
entity a claim on behalf of a subcontractor or lower tier subcontractor. A subcontractor may
request in writing, either on his or her own behalf or on behalf of a lower tier subcontractor, that
the contractor present a claim for work which was performed by the subcontractor or by a lower
tier subcontractor on behalf of the subcontractor. The subcontractor requesting that the claim be
presented to the public entity shall furnish reasonable documentation to support the claim. Within
45 days of receipt of this written request, the contractor shall notify the subcontractor in writing as
to whether the contractor presented the claim to the public entity and, if the original contractor did
not present the claim, provide the subcontractor with a statement of the reasons for not having
done so.
29
(e) The text of this section or a summary of it shall be set forth in the plans or specifications for any
public works project that may give rise to a claim under this section.
(f) A waiver of the rights granted by this section is void and contrary to public policy, provided, however,
that (1) upon receipt of a claim, the parties may mutually agree to waive, in writing, mediation and
proceed directly to the commencement of a civil action or binding arbitration, as applicable; and (2) a
public entity may prescribe reasonable change order, claim, and dispute resolution procedures and
requirements in addition to the provisions of this section, so long as the contractual provisions do not
conflict with or otherwise impair the timeframes and procedures set forth in this section.
(g) This section applies to contracts entered into on or after January 1, 2017.
(h) Nothing in this section shall impose liability upon a public entity that makes loans or grants available
through a competitive application process, for the failure of an awardee to meet its contractual
obligations.
(i) This section shall remain in effect only until January 1, 2027, and as of that date is repealed, unless a
later enacted statute, that is enacted before January 1, 2027, deletes or extends that date.
California Public Contract Code Sections 20104—20104.6
Section 20104
(a)(1) This article applies to all public works claims of three hundred seventy-five thousand dollars
($375,000) or less which arise between a contractor and a local agency.
(2) This article shall not apply to any claims resulting from a contract between a contractor and a
public agency when the public agency has elected to resolve any disputes pursuant to Article 7.1
(commencing with Section 10240)of Chapter 1 of Part 2.
(b)(1) "Public work" means "public works contract' as defined in Section 1101 but does not include any
work or improvement contracted for by the state or the Regents of the University of California.
(2) "Claim" means a separate demand by the contractor for(A)a time extension, (B) payment of
money or damages arising from work done by, or on behalf of, the contractor pursuant to the
contract for a public work and payment of which is not otherwise expressly provided for or the
claimant is not otherwise entitled to, or(C) an amount the payment of which is disputed by the
local agency.
(c) The provisions of this article or a summary thereof shall be set forth in the plans or specifications for
any work which may give rise to a claim under this article.
(d) This article applies only to contracts entered into on or after January 1, 1991.
Section 20104.2
For any claim subject to this article, the following requirements apply:
(a) The claim shall be in writing and include the documents necessary to substantiate the claim. Claims
must be filed on or before the date of final payment. Nothing in this subdivision is intended to extend the
time limit or supersede notice requirements otherwise provided by contract for the filing of claims.
30
(b) (1) For claims of less than fifty thousand dollars ($50,000), the local agency shall respond in writing to
any written claim within 45 days of receipt of the claim, or may request, in writing, within 30 days of
receipt of the claim, any additional documentation supporting the claim or relating to defenses to the claim
the local agency may have against the claimant.
(2) If additional information is thereafter required, it shall be requested and provided pursuant to
this subdivision, upon mutual agreement of the local agency and the claimant.
(3) The local agency's written response to the claim, as further documented, shall be submitted
to the claimant within 15 days after receipt of the further documentation or within a period of time
no greater than that taken by the claimant in producing the additional information, whichever is
greater.
(c) (1) For claims of over fifty thousand dollars ($50,000) and less than or equal to three hundred
seventy-five thousand dollars ($375,000), the local agency shall respond in writing to all written claims
within 60 days of receipt of the claim, or may request, in writing, within 30 days of receipt of the claim, any
additional documentation supporting the claim or relating to defenses to the claim the local agency may
have against the claimant.
(2) If additional information is thereafter required, it shall be requested and provided pursuant to
this subdivision, upon mutual agreement of the local agency and the claimant.
(3) The local agency's written response to the claim, as further documented, shall be submitted
to the claimant within 30 days after receipt of the further documentation, or within a period of time
no greater than that taken by the claimant in producing the additional information or requested
documentation, whichever is greater.
(d) If the claimant disputes the local agency's written response, or the local agency fails to respond within
the time prescribed, the claimant may so notify the local agency, in writing, either within 15 days of receipt
of the local agency's response or within 15 days of the local agency's failure to respond within the time
prescribed, respectively, and demand an informal conference to meet and confer for settlement of the
issues in dispute. Upon a demand, the local agency shall schedule a meet and confer conference within
30 days for settlement of the dispute.
(e) Following the meet and confer conference, if the claim or any portion remains in dispute, the claimant
may file a claim as provided in Chapter 1 (commencing with Section 900) and Chapter 2 (commencing
with Section 910) of Part 3 of Division 3.6 of Title 1 of the Government Code. For purposes of those
provisions, the running of the period of time within which a claim must be filed shall be tolled from the time
the claimant submits his or her written claim pursuant to subdivision (a) until the time that claim is denied
as a result of the meet and confer process, including any period of time utilized by the meet and confer
process.
(f) This article does not apply to tort claims and nothing in this article is intended nor shall be construed
to change the time periods for filing tort claims or actions specified by Chapter 1 (commencing with
Section 900) and Chapter 2 (commencing with Section 910)of Part 3 of Division 3.6 of Title 1 of the
Government Code.
Section 20104.4
The following procedures are established for all civil actions filed to resolve claims subject to this article:
(a) Within 60 days, but no earlier than 30 days, following the filing or responsive pleadings, the court
shall submit the matter to nonbinding mediation unless waived by mutual stipulation of both parties. The
31
mediation process shall provide for the selection within 15 days by both parties of a disinterested third
person as mediator, shall be commenced within 30 days of the submittal, and shall be concluded within
15 days from the commencement of the mediation unless a time requirement is extended upon a good
cause showing to the court or by stipulation of both parties. If the parties fail to select a mediator within
the 15-day period, any party may petition the court to appoint the mediator.
(b) (1) If the matter remains in dispute, the case shall be submitted to judicial arbitration pursuant to
Chapter 2.5 (commencing with Section 1141.10)of Title 3 of Part 3 of the Code of Civil Procedure,
notwithstanding Section 1141.11 of that code. The Civil Discovery Act(Title 4 (commencing with Section
2016.010) of Part 4 of the Code of Civil Procedure)shall apply to any proceeding brought under this
subdivision consistent with the rules pertaining to judicial arbitration.
(2) Notwithstanding any other provision of law, upon stipulation of the parties, arbitrators
appointed for purposes of this article shall be experienced in construction law, and, upon
stipulation of the parties, mediators and arbitrators shall be paid necessary and reasonable hourly
rates of pay not to exceed their customary rate, and such fees and expenses shall be paid
equally by the parties, except in the case of arbitration where the arbitrator, for good cause,
determines a different division. In no event shall these fees or expenses be paid by state or
county funds.
(3) In addition to Chapter 2.5 (commencing with Section 1141.10)of Title 3 of Part 3 of the Code
of Civil Procedure, any party who after receiving an arbitration award requests a trial de novo but
does not obtain a more favorable judgment shall, in addition to payment of costs and fees under
that chapter, pay the attorney's fees of the other party arising out of the trial de novo.
(c) The court may, upon request by any party, order any witnesses to participate in the mediation or
arbitration process.
Section 20104.6
(a) No local agency shall fail to pay money as to any portion of a claim which is undisputed except as
otherwise provided in the contract.
(b) In any suit filed under Section 20104.4, the local agency shall pay interest at the legal rate on any
arbitration award or judgment. The interest shall begin to accrue on the date the suit is filed in a court of
law.
DIVISION II GENERAL CONSTRUCTION
10 GENERAL
Add to the end of Section 10-1.02C(2):
Protect any irrigation component to be relocated before performing any other construction activity in the
area.
Replace Reserved in Section 10-1.02C(3)with:
Transplant any plant to be transplanted before performing any other construction activity in the area.
32
12 TEMPORARY TRAFFIC CONTROL
Replace section 12-2 with:
12-2 CONSTRUCTION PROJECT FUNDING INFORMATION SIGNS
12-2.01 GENERAL
Details for construction project information signs are in Project Details.
Keep construction project information signs clean and in good repair at all times.
12-2.02 MATERIALS
Provide Construction project information signs, posts, and mounting hardware.
Construction project information signs must be wood post signs complying with section 82-3 of the
Standard Specifications. Each sign shall be supported by two 16-feet tall 4x4 smooth wood posts, painted
white.
Sign panels for construction project information signs must be 4 feet tall by 6 feet wide and made of 3/4
inch thick exterior grade plywood.
The background on construction project information signs must be painted white.
Text shall be black on a white background.
The size of the text and logos on construction project information signs must be as described in the
Project Details. Do not add any additional information unless authorized.
12-2.03 CONSTRUCTION
Provide and Install a total of 1 construction project information signs at the location designated by the
Engineer before starting major work activities visible to highway users.
The Contractor shall construct and maintain signage meeting the guidelines specified in the Project
Details insert. The sign shall be prominently displayed in a location visible to the public.
Upon completion and acceptance of the work, the signs shall be removed and become the property of the
Contractor.
Replace the 3rd paragraph of Section 12-3.01C with:
If ordered, furnish and place additional temporary traffic control devices. This work is not change order
work if:
1. Required to conform with your traffic control plan
2. Required to conform with the MUTCD
3. Necessary for public safety or convenience as determined by the Engineer
4. Required to perform staged construction shown on the plans
Replace the last paragraph of Section 12-3.03C with:
Moving plastic traffic drums from location to location if ordered after initial placement is not change order
work if:
1. Required to conform with your traffic control plan
2. Required to conform with the MUTCD
33
3. Necessary for public safety or convenience as determined by the Engineer
4. Required to perform staged construction shown on the plans
Replace the last paragraph of Section 12-3.10C with:
Moving a barricade from location to location is change order work if ordered after initial placement of the
barricade unless.
1. Required to conform with your traffic control plan
2. Required to conform with the MUTCD
3. Necessary for public safety or convenience as determined by the Engineer
4. Required to perform staged construction shown on the plans
Replace Section 12-3.11 B(5)(b)with:
12-3.11 13(5)(b) Construction Project Funding Identification Signs
Reserved
Replace the word "Department's" with the word "Caltrans" in the 11t paragraph of Section 12-
3.20A(4)(a).
Replace the last paragraph of Section 12-3.20C(1) with:
If the Engineer orders a lateral move of temporary barrier system and repositioning is not shown, the
lateral move is change order work unless:
1. Required to conform with your traffic control plan
2. Required to conform with the MUTCD
3. Necessary for public safety or convenience as determined by the Engineer
4. Required to perform staged construction shown on the plans
Replace the 2"d paragraph of Section 12-3.20C(2)(c) with:
Install K rail as shown in the project plans.
Replace the last paragraph of Section 12-3.31 C with:
Moving portable flashing beacons from location to location if ordered after initial placement is change
order work unless:
1. Required to conform with your traffic control plan
2. Required to conform with the MUTCD
3. Necessary for public safety or convenience as determined by the Engineer
4. Required to perform staged construction shown on the plans
Replace the 2"d paragraph of Section 12-3.35B(6)with:
Provide any software on a CD or other Engineer-authorized data-storage device to the Engineer.
Add before the 1st paragraph of Section 12-3.41A(1):
Section 12-3.41 is used when shown in the Bid Item List.
Replace Section 12-4.02A(3)(a) with:
12-4.02A(3)(a) General
The Contractor shall prepare and submit to the County Construction Engineer for approval, a traffic
control system plan indicating the means and methods he will employ to institute and maintain traffic
control for all phases of the work within the project. The traffic control system plan shall be submitted to
the County Construction Engineer as early as possible, preferably five (5) working days prior to pre-
34
construction meeting. The Engineer will require five (5)working days to review the initial submittal of the
traffic control system plan and an additional five (5)working days for each successive review.
No work at the project site whatsoever, including preparatory work such as the installation of
construction project funding signs, shall commence until the traffic control system plan has been
approved in writing by the Engineer. In the event that the traffic control system plan is not
submitted timely, the Engineer may issue a notice of commencement of contract time prior to
approval of the traffic control system plan, and working days will begin to accrue against the
allotted contract time.
Late submittal of the traffic control plan or revisions thereafter required, due to the inadequacy of the plan,
shall not be accepted as justification for the delay in the start of the working days for the project.
It shall be the Contractor's responsibility to provide, install, maintain, and remove any and all detour
signage and traffic control devices and to obtain all permits, including permits from Caltrans, as may be
necessary to establish detours as part of the contractor's traffic control plan.
Traffic will not be allowed to be limited to one direction when construction activities are not actively in
progress. Providing, installing, maintaining, and removing all traffic control, including portable changeable
message signs if required, obtaining and complying with all permits, and providing all traffic control
operations shall be the responsibility of the contractor, and no additional compensation will be allowed
therefor.
Replace Section 12-4.02A(3)(b)with:
12-4.02A(3)(b) Closure Schedules
One-way traffic shall be controlled through the project in accordance with the California Manual MUTCD
and Caltrans Standard Plans T-11 and T-13 entitled "Traffic Control System for Lane Closure on Multilane
Conventional Highways" and "Traffic Control System for Lane Closure on Two Lane Conventional
Highways," and these special provisions. Night closure will not be permitted.
When traffic is under one way control on unpaved areas, the cones shown along the centerline on the
plan need not be placed.
Every Monday by noon, submit a closure schedule request for planned closures for the next week.
The next week is defined as Sunday at noon through the following Sunday at noon.
Submit a closure schedule request 5 days before the anticipated start of any job site activity that reduces:
1. Horizontal clearances of traveled ways, including shoulders, to 2 lanes or fewer due to activities such
as temporary barrier placement and paving
2. Vertical clearances of traveled ways, including shoulders, due to activities such as pavement
overlays, overhead sign installation, or falsework girder erection
Submit closure schedule changes, including additional closures, by noon at least 3 business days before
a planned closure.
Cancel closure requests at least 48 hours before the start time of the closure.
The Department notifies you of unauthorized closures or closures that require coordination with other
parties as a condition for authorization.
35
Replace Section 12-4.02A(3)(d)with:
12-4.02A(3)(d) Traffic Break Schedule
Not Used.
Replace Section 12-4.02C(1)with:
12-4.02C(1) General
Work that interferes with traffic is limited to the hours when closures are allowed.
Do not reduce an open traffic lane width to less than 10 feet. If traffic cones or delineators are used for
temporary edge delineation, the side of the base of the cones or delineators nearest to traffic is
considered the edge of the traveled way.
Discuss the contingency plan for any activity that could affect the closure schedule with the Engineer at
least 5 business days before starting the activity requiring the plan.
The Engineer may reschedule a closure that was canceled due to unsuitable weather.
Traffic will be controlled by flagmen by eyesight, radio (walkie talkie) or baton. In the event these
methods do not work satisfactorily, as determined by the Engineer, a pilot car will be required.
The Engineer may require a pilot car to be used during earthwork operations in preparation of the grading
plane or other operations when the Contractor's operations cover an area beyond the line of sight, or
beyond the range of radios or when the baton method does not function satisfactorily.
You may use automated flagger assistance devices to enhance the traffic control system for a lane
closure on a two-lane convention highway, except if a bid item for automated flagger assistance devices
is shown in the Bid Item List, the use of AFADs is required.
Do not use automated flagger assistance devices:
1. On multi-lane highways
2. As a substitute or a replacement for a temporary traffic control signal
3. If the devices impair access for pedestrians and bicycles, unless alternate access is provided
4. If the usable shoulder area is not wide enough to place a trailer mounted device
5. If the distance between the devices is more than 800 feet, except when each device is controlled by a
separate operator and radio communication is available between the AFAD operators
Replace Section 12-4.02C(2)with:
12-4.02C(2) Not Used
Replace Section 12-4.02C(3)with:
12-4.02C(3) Closure Requirements and Charts
12-4.02C(3)(a) General
Where 2 or more lanes in the same direction, including the shoulders, are adjacent to the area where the
work is being performed, close the adjacent lane under any of the following conditions:
1. Work is off the traveled way but within 6 feet of the edge of the traveled way, and the approach
speed is greater than 45 mph
2. Work is off the traveled way but within 3 feet of the edge of the traveled way, and the approach
speed is less than 45 mph
Closure of the adjacent traffic lane is not required during any of the following activities:
1. Work behind a barrier
2. Paving, grinding, or grooving
3. Installation, maintenance, or removal of traffic control devices except for temporary railing
36
12-4.02C(3)(b) - 12-4.02C(3)(n)
Reserved
12-4.02C(3)(o) Closure of Conventional County Roads
The type and location of signs, lights, flags, flagmen, and other traffic control and safety devices shall be
in accordance with the current edition of the California Manual on Uniform Traffic Control Devices
(MUTCD) issued by the State of California, Department of Transportation (Caltrans).
Allow public traffic to pass through construction at all times unless otherwise specified herein.
Provide access to properties abutting the project site at all times.
When directed by the Engineer, traffic shall be routed through the work under one-way control.
Under one-way reversing traffic control operations, public traffic may be stopped in one direction for periods
not to exceed 10 minutes.
Lane closure is defined as the closure of a traffic lane or lanes within a single traffic control system.
No work that would require a lane closure shall be performed.
Keep driveways and access roads accessible at all times.
Maintain vehicular access to the channel bank access roads at all times.
Personal vehicles of the Contractor's employees shall not be parked on the traveled way or shoulders
including sections closed to public traffic.
12-4.02C(3)(p)-12-4.02C(3)(s) Reserved
Replace Section 12-4.02C(7)(d)with:
12-4.02C(7)(d) Reserved
Replace the word "Department's" with "Caltrans" in Section 12-4.02C(9)(a)(iv).
Replace section 12-4.02C(9)(d) with:
12-4.02C(9)(d) Payment
You pay the cost of furnishing all flaggers, including transporting flaggers and furnishing stands and
towers for flaggers to provide for the passage of traffic through the work as specified in sections 7-1.03
and 7-1.04.
Add before the 1st paragraph of Section 12-4.02C(10):
Section 12-4.02C(10) is used when Pickup Truck Mounted Changeable Message Sign is shown in the Bid
Item List.
Replace item 3.6.1 in the list in Section 12-4.02C(11)(a)(iii)(B) with:
Not Used
Replace item 5 in the list in Section 12-4.02C(11)(a)(iv)(C)with:
Not Used
Replace Section 12-4.02C(11)(d)with:
12-4.02C(11)(d) Payment
Full payment for conforming to the requirements of this section shall be considered to be included in the
Traffic Control Plan item on the Bid Items List.
Replace Section 12-4.02C(14) with:
12-4.02C(14) Failure to Provide Traffic Control.
If you do not provide the traffic control and it becomes necessary for the Engineer to notify you of your
duties according to the Standard Specifications and these special provisions, you will pay$200 per 15-
37
minute period or portion thereof to the County for all the time required to acquire the traffic control,
including pilot car.
Such payment shall commence at the time notice of the improper traffic control condition is given to you
or your authorized representative by the Engineer and shall terminate when the condition is corrected.
Such payment will be deducted from your payment.
In addition, when it is necessary for the Engineer to perform the work, you will pay the actual cost for the
performance thereof. Such amount will be deducted from your payment. This will be in addition to any
penalties imposed in these special provisions.
The provisions in this section will not relieve you from your responsibility to provide such additional
devices or take such measures as may be necessary to comply with the provisions in Section 7-1.04,
"Public Safety," of the Standard Specifications.
Replace Section 12-4.02D with:
12-4.02D Payment
The Department pays for change order work for a traffic control system by force account for increased
traffic control and uses a force account analysis for decreased traffic control.
Traffic control system for lane closure is paid for as traffic control system. Flagging costs are paid for as
specified in section 12-1.04.
The requirements in section 4-1.05 for payment adjustment do not apply to traffic control system.
Adjustments in compensation for traffic control system will be made for an increase or decrease in traffic
control work if ordered.
A traffic control system required by change order work is paid for as a part of the change order work.
Full compensation for furnishing and operating the pilot car, (including driver, radios, and any other
equipment and labor required) shall be considered as included in the contract lump sum price paid for
traffic control system and no further payment will be made.
13 WATER POLLUTION CONTROL
Replace the word "Department" with "Caltrans" where it occurs in Section 13-1.01A.
Replace the 111 paragraph of Section 13-1.01D(2)with:
13-1.01 D(2) Regulatory Requirements
Comply with the discharge requirements in the NPDES General Permit for Storm Water Discharges
Associated with Construction and Land Disturbance Activities; Order No. 2009-000 9-DWQ, CAS000002
(Construction General Permit)and any amendments thereto issued by the SWRCB. The Construction
General Permit may be found at:
http://www.waterboards.ca.gov/water issues/prog ra ms/stormwater/constperm its.s html
Add to the end of Section 13-1.01 D(2):
This Project disturbs 0.6 acres of soil. A WPCP is required for this project.
Replace Section 13-1.01 D(4)(b)with:
13-1.01 D(4)(b) Qualifications
The WPC manager must:
1. Comply with the requirements provided in the Construction General Permit for:
38
1.1. QSP if the project requires a WPCP
1.2. QSD if the project requires a SWPPP
2. Complete the stormwater management training described at the Stormwater and Water Pollution
Control Information link at the Caltrans Division of Construction website
Replace Section 13-2.04:
13-2.04 PAYMENT
The Department pays for prepare water pollution control program as follows:
1. Total of 50 percent of the item total upon authorization of the WPCP
2. Total of 90 percent of the item total upon work completion
3. Total of 100 percent of the item total upon Contract acceptance
Add Section 13-3.01 C(5):
13-3.01C(5) Annual Certification
Submit an annual certification of compliance as described in the Caltrans Stormwater Pollution
Prevention Plan (SWPPP) and Water Pollution Control Program (WPCP) Preparation Manual before July
15th of each year.
Replace Section 13-4.03G with:
13-4.03G Dewatering
Dewatering consists of discharging accumulated stormwater, groundwater, or surface water from
excavations or temporary containment facilities.
If dewatering is required, perform dewatering work as specified for the work items involved, such as a
temporary ATS or dewatering and discharge.
If dewatering and discharging activities are not specified for a work item and you perform dewatering
activities:
1. Conduct dewatering activities under the Caltrans Field Guide for Construction Site Dewatering.
2. Ensure any dewatering discharge does not cause erosion, scour, or sedimentary deposits that could
impact natural bedding materials.
3. Discharge the water within the project limits. Dispose of the water if it cannot be discharged within
project limits due to site constraints or contamination.
4. Do not discharge stormwater or non-stormwater that has an odor, discoloration other than sediment,
an oily sheen, or foam on the surface. Immediately notify the Engineer upon discovering any such
condition.
Replace the 2nd paragraph of Section 13-5.04 with:
If there is no bid item for temporary soil stabilization measures, payment therefor is considered to be
included in the bid item for prepare and implement water pollution control program or in the bid item for
prepare and implement stormwater pollution prevention plan, as applicable.
Replace Section 13-6.04 with:
13-6.04 PAYMENT
The payment quantity for temporary sediment control bid items paid for by the length is the length
measured along the centerline of the installed material.
39
The payment quantity, if any, for temporary fiber roll does not include the additional quantity used for
overlaps.
The Department does not pay for the relocation of temporary drainage inlet protection during work
progress.
If there are no bid items for installing or maintaining temporary sediment control measures, payment
therefor is considered to be included in the bid item for prepare and implement water pollution control
program or in the bid item for prepare and implement stormwater pollution prevention plan, as applicable.
Replace Section 13-7.03D with:
13-7.03D Payment
The Department does not pay for the relocation of temporary construction entrances or roadways during
work progress.
If there are no bid items for installing or maintaining temporary construction entrances or roadways,
payment therefor is considered to be included in the bid item for prepare and implement water pollution
control program or in the bid item for prepare and implement stormwater pollution prevention plan, as
applicable.
Replace the 1st paragraph and the 1st line of the 2"d paragraph of Section 13-8.01C(2)with:
Within 20 days of Contract approval, submit 3 copies of the ATS plan if an ATS plan is required for the
project.
The plan, if required, must include:
Replace the word "Department's" with "Caltrans" in items 3 and 4 of the list in Section 13-
8.01 C(2).
14 ENVIRONMENTAL STEWARDSHIP
Add after the 3rd paragraph of section 14-10.01:
Food scraps, paper wrappers, food containers, cans, bottles and all food related trash and litter must be
removed from the project site at the end of each working day.
Replace the 8th paragraph of section 14-10.01 with:
Furnish and use closed-lid trash containers in the job-site yard, field trailers, and locations where workers
gather for lunch and breaks.
Replace Section 14-11.08 with:
14-12.04 RELATIONS WITH SAN JOAQUIN VALLEY AIR POLLUTION CONTROL DISTRICT
(SJVAPCD)
You are responsible for compliance with all applicable SJVAPCD regulations and requirements. This
section is provided for your information, and nothing herein or elsewhere within these special provisions
shall be construed as limiting your responsibility for complying with all applicable rules and regulations.
In accordance with SJVAPCD Regulation VIII — Fugitive PM10 Prohibitions: Rule 8021, implementation of
an SJVAPCD-approved dust control plan is not required prior to commencement of any dust generating
activities. You must file Construction Notification with SJVAPCD 48 hours prior to starting work.
Pursuant to section 6.4 of District Rule 8021 —Construction, Demolition, Excavation, Extraction, and
Other Earthmoving Activities, the owner or operator of a construction project of at least 1.0 acre in size
40
shall provide written notification to the District at least 48 hours prior to his/her intent to commence any
earthmoving activities. Use the first two pages of this form to submit a written Construction
Notification. There are no fees for filing a construction notification.
It is your responsibility to be fully informed of the requirements of all rules, regulations, plans and
conditions that may govern your operations and to conduct the work accordingly.
Replace Section 14-12.05-14.12.08 With:
14-12.05-14.12.08 RESERVED
41
Technical Specifications
Contract Number 24-14-C
County of Fresno
CONTRACT DOCUMENTS
AND
SPECIFICATIONS
FOR THE
CSA 43W Raisin City Groundwater Well Project
September 2024
Prepared for:
County of Fresno
Department of Public Works and Planning, Design Division
2220 Tulare St, 6t" Floor
Fresno, California 93721
Prepared by:
PROVOST& PRITC HARD
CONSULTING GROUP QROFESS10
pAVI �F.j,
G'
� m
LU Z '64,909 O 1;101
Z yy
T
Ciw �Q
qTF OF CP,0F
455 W FIR AVE DATESIGNED 9/30/2024
CLOVIS, CALIFORNIA 93611-0242
559/449-2700 FAX 559/449-2715
This Page is Intentionally Left Blank
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 00 01 10
TABLE OF CONTENTS
DIVISION 00— BIDDING AND CONTRACT DOCUMENTS
0001 01 Project Title Page
0001 10 Table of Contents
DIVISION 01 - GENERAL REQUIREMENTS
01 0005 Specifications
01 1100 Description of the Work and Schedule
01 2000 Measurement& Payment
01 2200 Explanation of Bid Items
01 3300 Submittal Procedures
01 4213 Definitions &Abbreviations
01 4300 Quality Control and Testing
01 5000 Temporary Facilities and Control
01 51 36 Watering
01 5713 Temporary Erosion and Sedimentation Control
01 5723 Storm Water Pollution Prevention Plan
01 5727 Dust Control
01 5750 Construction Staking
01 7419 Construction Waste Management and Disposal
01 7700 Contract Closeout
DIVISION 02 - EXISTING CONDITIONS
0201 20 Protecting Existing Underground Utilities
0241 00 Demolition
DIVISION 03 - CONCRETE
03 30 01 Cast-in-Place Concrete
DIVISION 05- METALS
05 05 20 Bolts, Washers, Anchors and Eyebolts
DIVISION 09 - FINISHES
09 90 00 Painting and Coating (Site)
09 97 57 Polyethylene Tape Pipe Coating
TABLE OF CONTENTS
0001 10-1
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/dfbec 15f-9ba 9-4bOa-8c83-
4fc1dbe11ee8/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/00 01 10 Table of Contents.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
DIVISION 26 - ELECTRICAL
26 05 19 Conductors and Cables
26 05 26 Grounding and Bonding for Electrical Systems
26 05 33 Raceways and Boxes
26 05 53 Electrical Identification
26 18 11 Overcurrent Protection Devices
26 27 26 Wiring Devices
26 28 16 Safety Switches and Individual Mounted Circuit Breakers
26 29 33 Solid State Reduced Voltage Controller
DIVISION 31 - EARTHWORK
31 11 00 Clearing and Grubbing
31 2317 Trenching Backfilling and Compacting
31 2335 Disposal of Materials
DIVISION 32 - EXTERIOR IMPROVEMENTS
3231 00 Fencing
DIVISION 33 - UTILITIES
33 05 26 Utility Line Markings
33 13 00 Disinfection of Water Distribution System
3321 13 Water Well Drilling
DIVISION 40 - Process Integration
40 05 00 Pipe & Fittings
40 05 23 Valves &Appurtenances
40 20 10 Pipe Supports
40 50 00 Instrumentation and Controls—General Provisions
40 90 00 Instrumentation
4091 25 Magnetic Flow Meter
40 96 31 SCADA Control Loop Descriptions
40 97 15 Pressure Gages
DIVISION 43 - Process Gas and Liquid Handling, Purification and Storage
4321 52 Well Pumping Facilities
END SECTION
TABLE OF CONTENTS
0001 10-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/dfbec 15f-9ba 9-4bOa-8c83-
4fc1dbe11ee8/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/00 01 10 Table of Contents.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 01 00 05
SPECIFICATIONS
PART 1 GENERAL
1.1 GENERAL
A. The Contractor shall keep on the job a copy of the Plans and Specifications and
shall at all times give the Owner and Engineer access thereto.
B. Anything mentioned in the Specifications and not shown on the Plans or shown on
the Plans and not mentioned in the Specifications shall be of like effect as if shown
or mentioned in both.
C. The Contractor shall not take advantage of any errors, discrepancies or omissions
which may exist in the Plans and Specifications but shall immediately call them to
the attention of the Engineer whose interpretation or correction thereof shall be
conclusive.
D. In case of conflict between portions of the Contract Documents, the order of
precedence of Contract Documents shall be:
First: Permits from other agencies as may be required by law.
Second: Addenda
Third: Bid Documents, Division 0
Fourth: Technical Specifications, Division 2 through Division 43
Fifth: Plans
Sixth: General Requirements, Division 1
Seventh: State Standard Specifications
Eighth: Reference Documents
E. Change Orders, supplemental agreements and approved revisions to Plans and
Specifications will take precedence over documents listed above. Detailed Plans
shall have precedence over general Plans.
F. Whenever any conflict appears in any portions of the Contract Documents, it shall
be resolved by application of the order of precedence.
1.2 GENERAL REQUIREMENTS AND TECHNICAL SPECIFICATIONS
A. For definitions of the Specifications categorized as General Requirements (Division
1) and Technical Specifications (Division 2 through Division 43) refer to Section 01
42 13 — Definitions and Abbreviations.
1.3 REFERENCE DOCUMENTS
A. For a definition of Reference Documents and State Standard Specifications refer to
Section 01 42 13 — Definitions and Abbreviations.
SPECIFICATIONS
01 00 05-1
https://u s-pa rtn er-i nteg rations.egnyte.cc m/msoffice/wopi/files/ac8a0008-5ff7-4916-a03a-
eefOd3907819/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 00 05 Specifications.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
B. Throughout the following Specification sections, references are made to various
widely published, standard and commercial specifications, manuals, or codes of
technical societies, organizations, or associations. These specifications are
intended to amplify the descriptions of materials, equipment, and construction
systems. The Contractor shall caution each of his Subcontractors to become familiar
with the contents of the pertinent portions of these Reference Documents. The
following Reference Documents are the most widely used, and are cited or referred
to in each of the following sections of these Specifications:
1. American Society of Testing Materials (ASTM)
2. American National Standards Institute (ANSI)
3. American Standards Associations (ASA)
4. American Concrete Institute (ACI)
5. Federal Specifications, as applicable.
6. California Building Code
7. California Plumbing Code
8. Caltrans State Standard Specifications
9. National Electric Code
10. Construction Safety Orders of the Division of Industrial Relations latest
edition.
C. Each citation of a Reference Document shall be construed to refer to the latest
published revision of such specification as of the date of the invitation for bids and
to such portions of it that relate and apply directly to the material or installation called
for on this job. The Engineer will give no consideration to any claimed ignorance as
to what a cited Reference Document contains, since such Subcontractor on a project
of this scope is deemed to be experienced and familiar with his own trade to be
experienced and familiar with his own trade's generally accepted, published
standards of quality.
D. Whenever references are made to any of the above-mentioned Reference
Documents or testing methods in the governing Building Codes, the requirements
of those Reference Documents shall govern, insofar as they are not in contravention
with maxima or minima prescribed by documents designated in the Building Code.
SPECIFICATIONS
01 00 05-2
https://u s-pa rtn er-i nteg rations.egnyte.cc m/msoffice/wopi/files/ac8a0008-5ff7-4916-a03a-
eefOd3907819/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 00 05 Specifications.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1.4 LIST OF DRAWINGS
A. The Work shall conform to the following Drawings:
SHEET
TITLE NUMBERS
GENERAL
COVER SHEET G1
SHEET INDEX & GENERAL NOTES G2
CIVIL LEGEND G3
HYDRAULIC PROFILE G4
CIVIL
PROCESS FLOW DIAGRAM Cl
DEMOLITION PLAN C2
SITE & PIPING PLAN C3
CONTROL PLAN C4
WELL PUMP FOUNDATION & CASING C5
WELL EQUIPMENT C6
DETAILS
FENCE DETAILS D1
CONSTRUCTION DETAILS D2
CONSTRUCTION DETAILS D3
ELECTRICAL
COVER SHEET Ell
ENLARGED PLAN — POWER E21
DETAILS E31
CONTROL DIAGRAM E41
1.5 OCCUPATIONAL SAFETY AND HEALTH ACT
A. The applicable standards of the American National Standards Institute and the
National Fire Protection Association that have been adopted are hereby made a part
of these Specifications as a whole and as mentioned in the various sections.
B. Any errors, ambiguities, or inconsistencies of these standards with either the local
codes, the Specifications, or the Drawings shall be brought to the attention of the
Engineer.
1.6 COMPLIANCE WITH ALL LAWS AND CODES
A. Contractor shall conform to and abide by all local city, county, state and federal laws,
rules, regulations, including industrial safety laws. Such laws shall be considered
as essential parts of these Specifications and, in the absence of definite
requirements herein, the provisions of such rules and regulations shall be observed
by the Contractor. If the Drawings and/or Specifications are at variance therewith,
Contractor shall so notify Engineer promptly. Should the Contractor perform any
work contrary to such laws, ordinances, rules and regulations he shall bear all costs
arising therefrom.
B. Where these Specifications, however, call for or describe materials workmanship or
construction of a better quality, higher standard, or larger size than is required by
SPECIFICATIONS
01 00 05-3
https://us-partner-i ntegrations.eg nyte.com/msoffice/wopi/files/ac8a0008-5ff7-4916-aO3a-
eefOd3907819/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 00 05 Specifications.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
said rules and regulations, the provisions of these Specifications shall take
precedence over said rules and regulations. Contractor shall furnish, without any
extra charge, all additional labor or materials, or both, when required for compliance
with these rules and regulations.
END SECTION
SPECIFICATIONS
01 00 05-4
https://u s-pa rtn er-i nteg rations.egnyte.cc m/msoffice/wopi/files/ac8a0008-5ff7-4916-a03a-
eefOd3907819/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 00 05 Specifications.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 01 11 00
DESCRIPTION OF WORK AND SCHEDULE CONSTRAINTS
PART 1 GENERAL
1.1 WORK INCLUDED
A. The Work consists of furnishing all labor, materials and equipment necessary to drill
and equip a second water well at the location indicated on the conformed plans and
connect to the existing water distribution main in the community of Raisin City, CA,
in accordance with the Plans and the Specifications.
B. The construction site is located in Fresno County south of Fresno, California.
C. The primary components are generally described as follows:
1. Drilling a new well
2. Equipping new well
3. Connecting new well to existing water distribution system
4. Electrical work as indicated on the plans
1.2 BEGINNING OF WORK
A. The Contractor shall begin work as stated in Section 8-1.04A Start of Job Site
Activities.
1. Depending on lead times for materials and equipment, the project may be
split into 2 phases:
a. First Order of Work: Submittals Phase
b. Second Order of Work: Construction Phase
1.3 TIME OF COMPLETION
A. The Contractor shall substantially complete all work as stated in Section 8-1.04A
Start of Job Site Activities.
1.4 TIME CONSTRAINTS
A. Contractor shall supervise, inspect, and direct the Work competently and apply such
skills and expertise as may be necessary to perform the Work in accordance with
the Contract Documents. Contractor shall be solely responsible for the specific
means, methods, techniques, sequence, or procedure of construction required to
complete the project as specified by the Contract Documents. Contractor shall be
responsible to see that the completed Work complies accurately with the Contract
Documents.
DESCRIPTION OF WORK AND SCHEDULE CONSTRAINTS
01 11 00-1
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/a693a486-e3ea-438f-b952-
fc6286205e3a/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 11 00 Description of Work and Schedule Constraints.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1.5 ORDER OF WORK
A. Drilling of the pilot hole and zone sampling shall be the Contractor's first order of
business.
END SECTION
DESCRIPTION OF WORK AND SCHEDULE CONSTRAINTS
01 11 00-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/a693a486-e3ea-438f-b952-
fc6286205e3a/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 11 00 Description of Work and Schedule Constraints.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 01 20 00
MEASUREMENT & PAYMENT
PART 1 GENERAL
1.1 MEASUREMENT
A. Unless otherwise specified in the Contract Documents, quantities of work shall be
determined from measurements or dimensions in a horizontal plane. All
measurements shall be made in accordance with United States Standard Measures
and shall be measured on the basis of"in-place" quantities.
B. After the work has been completed, the Engineer will make field measurements of
unit price items in order to determine the quantities of the various items as a basis
for payment. On all unit price items, the contractor will be paid for the actual amount
of the work performed in accordance with the contract documents, as computed
from field measurements.
C. Work or quantities not listed in the description of bid items are considered incidental
to other construction and will not be measured. Compensation for such incidental
work is considered to be included in the various items of work bid.
1.2 PARTIAL PAYMENT
A. Attention is directed to Section 9-1.16 of the State Standard Specifications which,
except as modified herein, shall apply in its entirety.
1. The department shall withhold not less than 5 percent of the contract price
until final completion and acceptance of the project.
2. Partial payments for materials on hand shall not exceed one hundred percent
(100%) of the value of material delivered on site, properly stored in a secured
fenced area subject to, or under the control of, the owner and local agency,
and unused. Contractor shall submit copies of invoices of materials to support
values. Materials stored shall be installed within 60 days of delivery for
payment eligibility.
B. Payment shall not relieve the Contractor from its obligations under the Contact; nor
shall such payment be construed as acceptance of any of the Work. Payment shall
not be construed as transfer of ownership of any equipment or materials to the
Owner. Responsibility of ownership shall remain with the Contractor who shall
obligated to protect any fully or partially completed work or structure for which
payment has been made; or replace any materials or equipment to be provided
under the Contract which may be damaged, lost, stolen or otherwise degraded in
any way prior to acceptance of the Work.
MEASUREMENT& PAYMENT
01 20 00-1
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/af3780ed-9 bff-40e3-baa6-
e0774351b1e8/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 20 00 Measurement&Payment With Escrow.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1.3 FINAL PAYMENT
A. Refer to State Standard Specifications Section 9-1.17.
MEASUREMENT& PAYMENT
01 20 00-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/af3780ed-9 bff-40e3-baa6-
e0774351b1e8/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 20 00 Measurement&Payment With Escrow.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
ESCROW AGREEMENT FOR SECURITY DEPOSITS IN LIEU OF RETENTION
This Escrow Agreement is made and entered into by and between
whose address is
herein after called "Owner,"
whose address is
hereinafter called "Contractor" and
whose address is
hereinafter called "Escrow Agent."
For the consideration hereinafter set forth, the Owner, Contractor, and Escrow Agent agree as
follows:
(1) Pursuant to Section 22300 of the Public Contract Code of the State of California, Contractor has
the option to deposit securities with Escrow Agent as a substitute for retention earnings required to
be withheld by Owner pursuant to the Construction Contract entered into between the Owner and
Contractor for in the amount of
dated (hereinafter referred to as the "Contract"). Alternatively, on written
request of the Contractor, the Owner shall make payments of the retention earnings directly to the
escrow agent. When the Contractor deposits the securities as a substitute for Contract earnings,
the Escrow Agent shall notify the Owner within 10 days of the deposit. The market value of the
securities at the time of the substitution shall be at least equal to the cash amount then required to
be withheld as retention under the terms of the Contract between the Owner and Contractor.
Securities shall be held in the name of
and shall designate the Contractor as the beneficial owner.
(2) The Owner shall make progress payments to the Contractor for those funds which otherwise
would be withheld from progress payments pursuant to the Contract provisions, provided that the
Escrow Agent holds securities in the form and amount specified above.
(3)When the Owner makes payment of retentions earned directly to the Escrow Agent, the Escrow
Agent shall hold them for the benefit of the Contractor until the time that the escrow created under
this contract is terminated. The Contractor may direct the investment of the payments into
securities. All terms and conditions of this agreement and the rights and responsibilities of the
parties shall be equally applicable and binding when the Owner pays the Escrow Agent directly.
(4) Contractor shall be responsible for paying all fees for the expenses incurred by Escrow Agent in
administering the Escrow Account and all expenses of the Owner. These expenses and payment
terms shall be determined by the Owner, Contractor, and Escrow Agent.
(5) The interest earned on the securities or the money market accounts held in escrow and all
interest earned on that interest shall be for the sole account of Contractor and shall be subject to
withdrawal by Contractor at any time and from time to time without notice to the Owner.
(6) Contractor shall have the right to withdraw all or any part of the principal in the Escrow Account
only by written notice to Escrow Agent accompanied by written authorization from the Owner to the
Escrow Agent that Owner consents to the withdrawal of the amount sought to be withdrawn by
Contractor.
MEASUREMENT& PAYMENT
01 20 00-3
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/af3780ed-9 bff-40e3-baa6-
e0774351b1e8/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 20 00 Measurement&Payment With Escrow.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
(7)The Owner shall have a right to draw upon the securities in the event of default by the Contractor.
Upon seven days' written notice to the Escrow Agent from the owner of the default, the Escrow
Agent shall immediately convert the securities to cash and shall distribute the cash as instructed by
the Owner.
(8) Upon receipt of written notification from the Owner certifying that the Contract is final and
complete, and that the Contractor has complied with all requirements and procedures applicable to
the Contract, Escrow Agent shall release to Contractor all securities and interest on deposit less
escrow fees and charges of the Escrow Account. The escrow shall be closed immediately upon
disbursement of all moneys and securities on deposit and payments of fees and charges.
(9) Escrow Agent shall rely on the written notifications from the Owner and the Contractor pursuant
to Sections (5) to (8), inclusive, of this agreement and the Owner and Contractor shall hold Escrow
Agent harmless from Escrow Agent's release and disbursement of the securities and interest as set
forth above.
(10)The names of the persons who are authorized to give written notice or to receive written notice
on behalf of the Owner and on behalf of Contractor in connection with the foregoing, and exemplars
of their respective signatures are as follows:
On behalf of Owner: On behalf of Contractor: On behalf of Escrow Agent:
Title Title Title
Name Name Name
Signature Signature Signature
Address Address Address
At the time the Escrow Account is opened, the Owner and Contractor shall deliver to the Escrow
Agent a fully executed counterpart of this Agreement.
IN WITNESS WHEREOF, the parties have executed this Agreement by their proper officers on the
date first set forth above.
MEASUREMENT& PAYMENT
01 20 00-4
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/af3780ed-9 bff-40e3-baa6-
e0774351b1e8/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 20 00 Measurement&Payment With Escrow.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
Owner Contractor
Title Title
Name Name
Signature Signature
END SECTION
MEASUREMENT& PAYMENT
01 20 00-5
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/af3780ed-9 bff-40e3-baa6-
e0774351b1e8/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 20 00 Measurement&Payment With Escrow.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
This Page is Intentionally Left Blank
MEASUREMENT& PAYMENT
01 20 00-6
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/af3780ed-9 bff-40e3-baa6-
e0774351b1e8/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 20 00 Measurement&Payment With Escrow.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 01 22 00
EXPLANATION OF BID ITEMS
PART 1 GENERAL
The Contract payment for the specified items of work as set forth in the Bid Schedule shall be full
compensation for furnishing all labor, materials, methods or processes, implements, tools,
equipment and incidentals and for doing all work involved as required by the provisions of the
Contract Documents for a complete in place and operational system.
A. Unless otherwise specified in the Specifications, quantities of work shall be
determined per each, or from measurements or dimensions in a horizontal plane.
All materials shall be measured on the basis of "in place" quantities and paid for
using the units listed in the bid schedule.
B. Except as noted, the Engineer will make field measurements of unit price items in
order to determine the quantities of the various items as a basis for payment. On
all unit price items, the contractor will be paid for the actual amount of the work
performed in accordance with the contract documents, as computed from field
measurements.
1. Work or quantities not listed in the description of bid items are considered
incidental to other construction and will not be separately measured or paid
for. Compensation for such work and/or material shall be included in the
prices paid for other items of work.
1.2 BID ITEMS
Bid Item 1 — Mobilization, Demobilization, Insurance, and Bonds:
This item is a lump sum bid for mobilization, all necessary bonds, insurance,
permits, licenses, fees required during the performance of the work, necessary
potholing, and demobilization and shall conform to the provisions of these
Specifications.
This item shall consist of covering the Contractors cost for Contract Documents
and for the moving of personnel, equipment, supplies and incidentals to the
project site. This item shall include obtaining all permits required for the project;
except any permits specifically included under a separate bid item. Permit fees
and all other permit preparation costs shall be included in this bid item. All costs
for furnishing and installing the required construction funding sign shall be
included in this bid item. This item also includes demobilization, including
removal of all equipment supplies, personnel, and incidentals from the project
site at the end of construction.
All costs associated with this item shall be included in the lump sum price and no
additional payment will be made. This bid item shall be paid as specified in
EXPLANATION OF BID ITEMS
01 22 00-1
https:Hu s-partner-integrations.eg n yte.co m/msoffi ce/wo p i/fi I es/5e7bd d 29-efc8-4d 2d-99c5-
b34eb49c8765/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/01 22 00 Explanation of Bid Items.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
Section 9 Payment and Sub-Section 9-1.16D Mobilization of the State Standard
Specifications.
Bid Item 2 — Prepare and Implement WPCP:
This bid item is a lump sum bid for all materials, labor and appurtenances required
to prepare and implement a Water Pollution Control Program ("WPCP"), including
preparing the WPCP, testing, monitoring and all other work associated with
implementing the WPCP and complying with State and Federal permit
requirements. This bid item shall be paid at the lump sum price bid. Payment will
be prorated based on the percentage of contract work completed.
Bid Item 3 — Dust Control:
This bid item is a lump sum bid for all materials, labor and appurtenances required
to perform dust control measures for the project limits in accordance with
conditions of these Specifications. This bid item shall be paid at the lump sum price
bid. Payment will be prorated based on the percentage of contract work
completed.
Bid Item 4— Job Site Management
This bid item is a lump sum bid item for the cost of all work involved with CSA 43W
job site management and includes full compensation for furnishing all labor,
materials, tools, equipment, and incidentals and for doing all the work involved in
spill prevention and control, material management, waste management, non-
stormwater management, and dewatering and identifying, sampling, testing,
handling, and disposing of hazardous waste resulting from your activities, as
specified in the Standard Specifications and these Special Provisions, and as
ordered by the Engineer.
Bid Item No. 4 is intended to cover all of the base "Job Site Management' costs
for CSA 43W.
The contractor shall abide by all federal and state regulations regarding removal
and disposal of hazardous waste materials including, but not limited to asbestos
cement pipe.
This item also includes providing worker protection from trench failures and other
hazards that may occur during construction. The Contractor shall comply with the
provisions of the Construction Safety Orders, Tunnel Safety Orders, and General
Safety Orders issued by the State of California Division of Industrial Safety, as well
as all other applicable laws, ordinances and regulations, as they pertain to the
protection of workers from the hazard of caving ground.
The Contractor shall obtain a permit from the Division of Industrial Safety of the
State of California prior to commencement of construction. This bid item shall be
paid at the lump sum price bid. Payment will be prorated based on the percentage
of CSA 43W contract work completed.
EXPLANATION OF BID ITEMS
01 22 00-2
https:Hu s-partner-integrations.eg n yte.co m/msoffi ce/wo p i/fi I es/5e7bd d 29-efc8-4d 2d-99c5-
b34eb49c8765/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/01 22 00 Explanation of Bid Items.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
Bid Item 5— Traffic Control:
This bid item is a lump sum bid for all materials, labor and appurtenances required
to maintain traffic control measures within the CSA 43W project limits in
accordance with Section 12 of the Standard Specifications, special provisions and
as directed by the Engineer and County inspector. The Contractor shall submit a
traffic control plan for review and approval by the County. The County will require
only one traffic control plan for the entire project. Traffic control provisions shall
conform to the following requirements:
1. The California Manual on Uniform Traffic Control Devices (MUTCD) and
Section 12 of the Special Provisions and Standard Specifications, latest
edition, is hereby referred to and incorporated herein as though set forth in
full. The Contractor shall be responsible for providing all necessary traffic
control facilities, 24 hours per day, 7 days per week for the entire duration
of the project.
Full compensation for furnishing all labor, materials, tools, equipment and
incidentals, and for doing all work involved for the sole convenience, direction and
safety of public traffic and pedestrians shall be included in this bid item. This bid
item shall be paid at the lump sum price bid. Payment will be prorated based on
the percentage of contract work completed.
Bid Item 6 — Clearinq and Grubbinq:
Payment for this item shall include full compensation for all labor, materials, tools,
equipment and incidentals making up the cost of all work involved in clearing and
grubbing within project site, all as described in the Specifications. This bid item will
be paid as a lump sum, prorated based on the percentage of this item completed.
Bid Item 7 — Site Demolition:
Payment for this item shall include full compensation for all labor, materials, tools,
equipment and incidentals making up the cost of all work involved in demolition of
indicated components within the work site, including sawcutting and removal of
concrete, concrete curb, fence mow strips, removal and disposal of fence, tree
removal, and other facilities as described in the Specifications and shown on the
Plans. This bid item will be paid for by Lump Sum, prorated, based on percentage
of work completed.
Bid Item 8 — Furnish and Install 30" Diameter Conductor Casing:
This bid item is a unit price bid for furnishing and installing 30-inch diameter
conductor casing and shall be per lineal foot complete in place, and shall be full
compensation for furnishing all labor, equipment and materials to complete the
installation, including cement seals outside of casing, as described herein. The
quantities may be increased, decreased, or deleted entirely by Owner, with no
change in unit price.
EXPLANATION OF BID ITEMS
01 22 00-3
https:Hu s-partner-integrations.eg n yte.co m/msoffi ce/wo p i/fi I es/5e7bd d 29-efc8-4d 2d-99c5-
b34eb49c8765/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/01 22 00 Explanation of Bid Items.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
Bid Item 9 — Drill Pilot Hole (to 700-ft Total Depth):
This bid item is a unit price bid for drilling the pilot hole from the bottom of the
conductor casing and shall be per lineal foot completed, and shall be full
compensation for furnishing all labor, equipment and materials to complete the
installation as described herein. The quantities may be increased, decreased, or
deleted entirely by Owner, with no change in unit price.
Bid Item 10 — Perform Electric Log and Deviation Log:
Payment for this item shall include full compensation for furnishing all labor,
equipment, materials, and incidentals to complete the work as described herein,
and no additional compensation will be made therefore. This bid item will be paid
for by Lump Sum, prorated, based on percentage of work completed.
Bid Item 11 — Collect Depth Zone Samples:
This bid item is a unit price bid for collection of individual depth zone samples and
shall be per zone sampled, and shall be full compensation for furnishing all labor,
equipment and materials to complete the sample collection as described herein.
The quantities may be increased, decreased, or deleted entirely by Owner, with no
change in unit price.
Bid Item 12 — Open Pilot Hole to 24" Diameter (to 700-ft Total Depth):
This bid item is a unit price bid for opening the pilot hole to 24-inch diameter well
bore hole from the bottom of the conductor casing the total depth and shall be per
lineal foot completed, and shall be full compensation for furnishing all labor,
equipment, and materials to complete the installation as described herein,
including drillers log and report. The quantities may be increased, decreased, or
deleted entirely by Owner, with no change in unit price.
Bid Item 13— Furnish and Install 12" Diameter Blank Casing:
This bid item is a unit bid price for furnishing and installing 12-inch diameter blank
casing and shall be per lineal foot complete in place, and shall be full compensation
for furnishing all labor, equipment and materials to complete the installation as
described herein. The quantities may be increased, decreased, or deleted entirely
by Owner, with no change in unit price.
Bid Item 14— Furnish and Install 12" Diameter Perforated Casing:
This bid item is a unit bid price for furnishing and installing 12-inch diameter mill
slot perforated casing and shall be per lineal foot complete in place, and shall be
full compensation for furnishing all labor, equipment and materials to complete the
installation as described herein. The quantities may be increased, decreased, or
deleted entirely by Owner, with no change in unit price.
Bid Item 15 — Furnish and Install 20-foot Compression Section:
This bid item is for furnishing and installing 20-foot lengths of compression section,
complete in place, and shall be full compensation for furnishing all labor,
EXPLANATION OF BID ITEMS
01 22 00-4
https:Hu s-partner-integrations.eg n yte.co m/msoffi ce/wo p i/fi I es/5e7bd d 29-efc8-4d 2d-99c5-
b34eb49c8765/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/01 22 00 Explanation of Bid Items.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
equipment and materials to complete the installation as described herein. This bid
item will be paid for by Lump Sum.
Bid Item 16 — Furnish and Install 3" Diameter Gravel Fill Pipe:
This bid item is a unit bid price for furnishing and installing 3-inch diameter
schedule 40 steel gravel fill pipe in accordance with the Technical Specifications
and shall be per lineal foot complete in place, and shall be full compensation for
furnishing all labor, equipment and materials complete the installation described
herein. The quantities may be increased, decreased, or deleted entirely by Owner,
with no change in unit price.
Bid Item 17 — Furnish and Install Gravel Pack:
This bid item is a unit bid price for furnishing and installing gravel pack and shall
be per lineal foot complete in place, and shall be full compensation for furnishing
all labor, equipment, and other materials to complete the installation as described
herein. The quantities may be increased, decreased, or deleted entirely by Owner,
with no change in unit price.
Bid Item 18 — Furnish and Install Annular Seal:
This bid item is a unit bid price for furnishing and installing cement-grout and
bentonite annular seals and shall be per lineal foot complete in place, and shall be
full compensation for furnishing all labor, equipment and materials to complete the
installation as described herein and shown on the bid documents. The quantities
may be increased, decreased, or deleted entirely by Owner, with no change in unit
price.
Bid Item 19— Perform Preliminary Well Development:
This bid item is a unit bid price for preliminary well development. Payment will be
on a per hour basis, and shall be full compensation for furnishing all labor,
equipment and materials to complete the work as described herein. The quantities
may be increased, decreased, or deleted entirely by Owner, with no change in unit
price.
Bid Item 20— Perform Pump Development and Pump Test (Mob/Demob pump and
pump up to 40 hours):
This bid item is a lump sum bid price for pump development and pump tests.
Payment for this bid item shall include full compensation for furnishing all labor,
equipment and materials and incidentals to complete the work as described herein,
and no additional compensation will be made therefore.
Bid Item 21 — Additional Pump Development and Pump Testing Time:
This is a unit price bid item for pump development and pump testing and shall be
on a per hour basis, and shall be full compensation for furnishing all labor,
equipment, materials, and incidentals to complete the well development as
EXPLANATION OF BID ITEMS
01 22 00-5
https:Hu s-partner-integrations.eg n yte.co m/msoffi ce/wo p i/fi I es/5e7bd d 29-efc8-4d 2d-99c5-
b34eb49c8765/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/01 22 00 Explanation of Bid Items.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
described herein. The quantities may be increased, decreased, or deleted entirely
by Owner, with no change in unit price.
Bid Item 22 — Perform Video Log:
This bid item includes performing the video log and plumbness and alignment
testing, and shall be full compensation for furnishing all labor, equipment and
materials to complete the work as described herein. The item will be paid for by
Lump Sum.
Bid Item 23 — Construct Well Pump Foundation:
This bid item includes constructing a well pump foundation and shall be full
compensation for furnishing all labor, equipment and materials to complete the
work as described herein. The item will be paid for by Lump Sum.
Bid Item 24— Furnish and Install Submersible Well Pump and Motor:
This bid item includes furnishing and installing the pump, motor,well head facilities,
and sounding tube and shall be full compensation for furnishing all labor,
equipment and materials to complete the work as described herein. The item will
be paid for by Lump Sum.
Bid Item 25— Furnish and Install 4" Diameter Column Pipe:
This bid item includes furnishing and installing the column pipe and shall be per
lineal foot complete in place, and shall be full compensation for furnishing all labor,
equipment and materials to complete the installation as described herein. The
quantities may be increased, decreased, or deleted entirely by Owner, with no
change in unit price.
Bid Item 26— Site Grading:
This bid item includes rough and finish grading, import material and all labor and
equipment required to complete the grading of the site including over excavation
under all concrete slabs and compaction of fill material, fill areas and spreading
unsuitable material at the end of the job at the direction of the Owner. This bid item
will be paid for by Lump Sum.
Bid Item 27— Well Discharge, Site Piping, Valves, and Appurtenances:
This bid item is a lump sum bid for installing all well discharge piping and valves,
onsite and offsite piping and fittings, valves and all appurtenances as detailed on
the Plans and Specifications. This item shall include trenching, bedding, backfill
and compaction, well supply pipe, well discharge valves and fittings, meter, air
release valve, sample taps, injection taps, pipe supports, polyethylene
encasement, tracer wire, caution tap, fittings, valves and valve boxes, restoring
surface to original condition, and testing, as shown on the Plans. Completed item
shall provide a complete and fully operational system.
EXPLANATION OF BID ITEMS
01 22 00-6
https:Hu s-partner-integrations.eg n yte.co m/msoffi ce/wo p i/fi I es/5e7bd d 29-efc8-4d 2d-99c5-
b34eb49c8765/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/01 22 00 Explanation of Bid Items.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
The bid item price shall include full compensation for furnishing all labor, tools
,equipment and materials, along with all associated appurtenances required to
complete the work under this bid item, in conformance with the plans and
specifications, and as directed by the Engineer. This bid item will be paid for by
Lump Sum on a prorated basis based on the percentage of work completed.
Bid Item 28 — Temporary Chain Link Fence:
This bid item includes furnishing for all labor, materials, tools, and equipment
necessary for furnishing and installing a temporary 6-foot chain link fence.
Temporary fence installation includes, but is not limited to, furnishing of the 6-foot-
tall, free-standing chain link fence, and installation of all appurtenances required
as indicated on the Plans. This bid item will be paid for by Lump Sum on a prorated
basis based on the percentage of work completed under this bid item.
Bid Item 29 — Permanent Chain Link Fence:
This bid item includes furnishing for all labor, materials, tools, and equipment
necessary for furnishing and installing a permanent 6-foot chain link fence with 25-
year privacy slats as indicated in the Plans. Permanent fence installation includes,
but is not limited to, forming and pouring concrete mow strip and installation of all
appurtenances required to enclose the site and connect the new fence to the
existing site perimeter fencing. This bid item will be paid for by Lump Sum on a
prorated basis based on the percentage of work completed under this bid item.
Bid Item 30 — Electrical, Controls, & Lighting:
This bid item is a lump sum bid for all work associated with all electrical equipment
required for the CSA 43W site, including, but not limited to modification at the
existing electrical facilities, pump starter, site lighting, site electrical, conduit and
conductors for all work, and all electrical connections.
The bid item price shall include full compensation for furnishing all labor, tools,
equipment and materials, coordination with Building Department inspector , along
with all associated appurtenances required to complete electrical, controls and
lighting in conformance with the Plans and Specifications and as directed by the
Engineer. This bid item shall be paid at the lump sum price bid. Payment will be
prorated based on the percentage of work completed under this bid item.
Bid Item 31 — Connection to Existing Water System:
Payment under this item shall be considered full compensation for all labor,
materials, tools, equipment and incidentals necessary for removal, installation, and
fitment of all Water Connection pipe, fittings, and all appurtenances necessary for
connection of proposed well piping to existing well piping; excavation, bedding,
connections, abandoning and restoring existing services, backfilling, thrust block,
compaction and watering; disinfection, testing; and doing all work involved in
installing Water Connection as detailed in the Plans and Specifications.
EXPLANATION OF BID ITEMS
01 22 00-7
https:Hu s-partner-integrations.eg n yte.co m/msoffi ce/wo p i/fi I es/5e7bd d 29-efc8-4d 2d-99c5-
b34eb49c8765/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/01 22 00 Explanation of Bid Items.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
Bid Item 32 — Start-up and Testing
This bid item is a lump sum bid and includes furnishing services associated with startup
and testing. Completed bid item shall provide a complete and fully operational facility with
complete integration between well, tank, hydropneumatic tank, and booster pumps.
The bid item price shall include full compensation for furnishing all labor, tools, equipment
and materials, along with all associated appurtenances required to complete the work
under this bid item, in conformance with the Plans and Specifications, and as directed by
the Engineer. This bid item will be paid for by Lump Sum on a prorated basis based on
the percentage of work completed under this bid item.
Bid Item 33— Operations and Maintenance Manuals
This bid item is a lump sum bid and includes preparing and furnishing an operations and
maintenance manuals for all equipment.
The bid item price shall include full compensation for furnishing all labor, tools, equipment
and materials, along with all associated appurtenances required to complete the work
under this bid item, in conformance with the Plans and Specifications, and as directed by
the Engineer. This bid item will be paid for by Lump Sum on a prorated basis based on
the percentage of work completed under this bid item.
Bid Item 34— Record Drawings
This bid item is a lump sum bid and includes preparing and furnishing record drawings
for Raisin City (CSA 43W) improvements.
The bid item price shall include full compensation for furnishing all labor, tools, equipment
and materials, along with all associated appurtenances required to complete the work
under this bid item, in conformance with the Plans and Specifications, and as directed by
the Engineer. This bid item will be paid for by Lump Sum on a prorated basis based on
the percentage of work completed under this bid item.
Bid Item 35 — Supplemental Work Allowance
This item is provided to account for supplemental work which may be required due to
differing job site conditions not provided for on the Plans or in these Specifications and
other unforeseen work which the Engineer determines is necessary to allow for the work
required by the Contract Documents to proceed as intended without interruption.
This item will be used only for this purpose. The dollar amount listed on the Bid Proposal
Form is an estimated allowance set aside by the Owner and shall be included on each
Bidder's Bid Proposal sheets.
Supplemental work shall be performed only upon direct written authorization from the
Engineer and daily extra work reports shall be submitted to and approved by the
Engineer. The Contractor shall maintain separate records for extra work performed in
accordance with the provisions of Section 5-1.27, "Records," of the Standard
Specifications and the special provisions.
EXPLANATION OF BID ITEMS
01 22 00-8
https:Hu s-partner-integrations.eg n yte.co m/msoffi ce/wo p i/fi I es/5e7bd d 29-efc8-4d 2d-99c5-
b34eb49c8765/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/01 22 00 Explanation of Bid Items.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
The Contractor will be paid only for the value of completed supplemental work which has
been authorized in writing by the Engineer.
The value of work, which the Owner may authorize under this item, may be less than the
amount shown on the Bid Proposal sheet, and it could be that no supplemental work will
be authorized at all. Accordingly, payments to the Contractor for supplemental work will
likely differ substantially from the estimated Allowance which is included in the Bid
Proposal. If no supplemental work is authorized or if no authorized supplemental work is
performed, then no payments will be made to the Contractor under this Bid item and the
Contract Price will be reduced by the full amount of the item included in the Bid Proposal
for supplemental work. The provisions in Section 9-1.06, "Changed Quantity Pay
Adjustments" of the Standard Specifications shall not apply to the item "Supplemental
Work Allowance."
The value of supplemental work cannot exceed the amount shown on the bid proposal
sheet. Additional work that requires compensation exceeding this allowance shall be
subject to approval by the contract change order procedures of this Contract.
The Contractor shall have no claim for anticipated overhead or profit should the County
fail to authorize any supplemental work or should the value of authorized supplemental
work be less than anticipated by the Contractor.
END SECTION
EXPLANATION OF BID ITEMS
01 22 00-9
https:Hu s-partner-integrations.eg n yte.co m/msoffi ce/wo p i/fi I es/5e7bd d 29-efc8-4d 2d-99c5-
b34eb49c8765/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/01 22 00 Explanation of Bid Items.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
This Page is Intentionally Left Blank
EXPLANATION OF BID ITEMS
01 22 00-10
https:Hu s-partner-integrations.eg n yte.co m/msoffi ce/wo p i/fi I es/5e7bd d 29-efc8-4d 2d-99c5-
b34eb49c8765/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/01 22 00 Explanation of Bid Items.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 01 33 00
SUBMITTAL PROCEDURES
PART 1 GENERAL
1.1 WORK INCLUDED
A. The work described in this section includes general requirements and procedures
related to the preparation and transmission of submittals to include Shop Drawings,
Product Information, Calculations, Test Reports, Certificates, Samples, Manuals,
and Record Drawings.
1.2 RELATED WORK
A. General Conditions
B. Section 01 77 00 — Contract Closeout
C. Individual equipment specifications
1.3 GENERAL
A. Contractor shall have completed the following work tasks before a submittal:
1. Reviewed and coordinated the Shop Drawing or Sample with other Shop
Drawings and Samples and with the requirements of the Work and the
Contract Documents;
2. Determined and verified all field measurements, quantities, dimensions,
specified performance and design criteria, installation requirements,
materials, catalog numbers, and similar information with respect thereto;
3. Determined and verified the suitability of all materials and equipment offered
with respect to the indicated application, fabrication, shipping, handling,
storage, assembly, and installation pertaining to the performance of the Work;
and
4. Determined and verified all information relative to Contractor's responsibilities
for means, methods, techniques, sequences, and procedures of construction,
and safety precautions and programs incident thereto.
1.4 TRANSMITTAL INFORMATION
A. Each submittal document shall have a separate cover or transmittal. Transmittals
shall include the following identification data, as applicable:
1. Submittal number
2. Contract number
SUBMITTAL PROCEDURES
01 33 00-1
https:Hus-partner-integrations.egnyte.com/msoffice/wapi/files/ddf7el 81-8e28-4b3a-a5c4-
fb270b094c67/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/01 33 00 Submittal Procedures.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3. Project name and location
4. Product identification
5. Applicable contract drawing number, specification section, and paragraph
number
6. Stamp Space: Blank space of approximately 2-1/2 inches high by 4 inches
wide adjacent to the identification data to receive Engineer's status stamp.
7. Contractor's certification statement as described below:
a. "Certification Statement: By this submittal, we hereby represent that
we have determined and verified all field measurements, field
construction criteria, materials, dimensions, catalog numbers and
pertinent data and we have checked and coordinated each item with
other applicable approved drawings and all Contract requirements."
B. With each submittal, Contractor shall give Engineer specific written notice of any
variations that the Shop Drawing or Sample may have from the requirements of the
Contract Documents. This notice shall be set forth in a written communication
separate from the Shop Drawings or Sample submittal; and, in addition, in the case
of Shop Drawings by a specific notation made on each Shop Drawing submitted to
Engineer for review of each such variation.
C. Furnish neat, legible, and sufficiently explicit detail to enable proper review for
Contract compliance.
D. Contractor assumes all risks of error and omission.
E. Work performed before acceptance, or not conforming to accepted submittals, shall
be at Contractor's risk.
F. Submittal requirements contained in this specification are in addition to specific
submittal requirements contained in individual equipment specification sections.
1.5 LIMITATIONS OF ENGINEER'S REVIEW
A. Engineer's review is only for the purposes of determining if the items covered by the
submittals will conform to the requirements in the Contract Documents.
B. Engineer's review will not extend to means, methods, techniques, sequences, or
procedures of construction or to safety precautions or programs incident thereto.
C. Engineer's review of a separate item will not indicate acceptance of the assembly in
which the item functions.
D. Engineer's review of a Submittal shall not relieve Contractor from responsibility for
any deviation from the requirements of the Contract Documents unless Contractor
has given Engineer specific written notice of any deviation per the requirements of
this Section. Engineer will document any such accepted variation from the
requirements of the Contract Documents in a Field Order.
SUBMITTAL PROCEDURES
01 33 00-2
https:Hus-partner-integrations.egnyte.com/msoffice/wapi/files/ddf7el 81-8e28-4b3a-a5c4-
fb270b094c67/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/01 33 00 Submittal Procedures.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
E. Engineer's review of a Submittal, or of a variation from the requirements of the
Contract Documents, shall not, under any circumstances, change the Contract
Times or Contract Price, unless such changes are included in a Change Order.
1.6 SUBMITTAL PROCESS
A. Submittals shall be sent to the Engineer electronically through email or a file transfer
system agreed upon by the Owner, Engineer, and Contractor during the
Preconstruction Conference.
B. Engineer will provide timely review of Submittals in accordance with the Schedule
of Submittals agreed upon by the Owner, Engineer, and Contractor during the
Preconstruction Conference.
C. Submittals will be returned, marked with one of the following classifications:
1. NO EXCEPTION TAKEN: Requires no corrections, no marks.
2. MAKE CORRETIONS NOTED: Requires minor corrections. Items may be
fabricated as marked without further resubmission. Resubmit 2 corrected
copies to the Engineer.
3. REVISE AND RESUBMIT: Requires corrections. Resubmit entire submittal
following original submission with corrections noted. Allow time for checking
and Engineer's appropriate action.
4. REJECTED: Submitted information does not comply with the Contract
Documents. No items shall be fabricated. Resubmit entire submittal following
original submission with corrections noted.
5. INFORMATION ONLY: Items in the submittal are saved in the project file for
information only but were not reviewed by the Engineer.
PART 2 SUBMITTAL DOCUMENTS
2.1 SHOP DRAWINGS
A. When requested submit, submit two (2) sets of shop drawings.
2.2 SAMPLES
A. When requested or required by individual specification sections, submit one (1)
sample of each item.
B. Samples shall be representative of the actual material proposed for use in the
project and of sufficient size to demonstrate design, color, texture, and finish.
C. Permanently attach to each sample
1. The submittal number
SUBMITTAL PROCEDURES
01 33 00-3
https:Hus-partner-integrations.egnyte.com/msoffice/wapi/files/ddf7el 81-8e28-4b3a-a5c4-
fb270b094c67/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/01 33 00 Submittal Procedures.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2. The contract number
3. Project name and location
4. Product identification
5. Applicable contract drawing and specification section number
6. Subcontractor's, vendor's and/or manufacturer's name, address, and
telephone number.
D. Certain samples may be tested for specific requirements by the Owner and/or
Engineer prior to acceptance. Failure of sample to pass tests will be sufficient cause
for refusal to consider further samples of the same brand and make.
E. Rejected samples will be returned upon request, and resubmittals shall consist of
new samples.
2.3 RECORD DRAWINGS
A. Maintain 1 record copy of Contract Documents at site in good order and annotated
to show revisions made during construction. Keep annotations current for possible
inspection.
1. Make record drawings available to Engineer at all times during life of Contract.
2. Drawings: Made part of record drawings and to include:
a. Contract Drawings: Annotate or redraft, as required, to show revisions,
substitutions, variations, omissions, and discrepancies made or
discovered during construction concerning location and depth of
utilities, piping, ductbanks, conduits, manholes, pumps, valves, vaults,
and other equipment. Make revisions and show on all drawing views
with actual dimensions established to permanent points.
b. Working/Layout Drawings: When required as submittals, record actual
layouts of conduit runs between various items of electrical equipment
for power, control, and instrumentation; wire sizes, numbers, and
functions; configuration of conduits; piping layouts; and duct layouts.
3. Before preliminary inspection, furnish reproducible of record drawings. At
completion of Contract and before final payment is made, furnish Engineer 1
set of reproducibles of finally accepted record drawings reflecting revisions
herein described.
2.4 OPERATION AND MAINTENANCE MANUALS
A. Furnish Operation and Maintenance Manuals for various types of equipment and
systems, as required by Contract Documents. Operation and Maintenance Manuals
shall be provided for all mechanical and electrical equipment. Unless otherwise
indicated, furnish separate manual for each piece of equipment and system. If
manual contains other items or equipment, indicate where specified items are
SUBMITTAL PROCEDURES
01 33 00-4
https:Hus-partner-integrations.egnyte.com/msoffice/wapi/files/ddf7el 81-8e28-4b3a-a5c4-
fb270b094c67/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/01 33 00 Submittal Procedures.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
located in manual. Include in manual complete information necessary to operate,
maintain, and repair specific equipment and system furnished under this Contract,
and include the following specific requirements;
1. Contents.
a. Table of Contents and Index.
b. Brief description of equipment/system and principal components.
C. Starting and stopping procedures, both normal and emergency.
d. Installation, maintenance, and overhaul instructions including detailed
assembly drawings with parts list and numbers, and recommended
spare parts list with recommended quantity, manufacturer's price,
supplier's address, and telephone number.
e. Recommended schedule for servicing, including technical data sheets
that indicate weights and types of oil, grease, or other lubricants
recommended for use and their application procedures.
f. One copy of each component wiring diagram and system wiring
diagram showing wire size and identification.
g. One accepted copy of each submittal with changes made during
construction properly noted, including test certificates, characteristic
curves, factory and field test results.
h. For electrical systems, include dimensioned installation drawings,
single line diagrams, control diagrams, wiring and connection
diagrams, list of material for contactors, relays and controls, outline
drawings showing relays, meters, controls and indication equipment
mounted on equipment or inside cubicles, control and protective
schematics, and recommended relay settings.
2. Material:
a. Preliminary
1) Submit one (1) electronic copy of the preliminary O&M manuals
in searchable PDF format.
b. Final
1) Submit one (1) electronic copy of the final O&M manuals in
searchable PDF format.
2) Submit two (2) hard copies of the final O&M Manual as
described below:
a) Covers: Oil, moisture, and wear resistant 9 inches by 11-
1/2 inches size.
SUBMITTAL PROCEDURES
01 33 00-5
https:Hus-partner-integrations.egnyte.com/msoffice/wapi/files/ddf7el 81-8e28-4b3a-a5c4-
fb270b094c67/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/01 33 00 Submittal Procedures.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
b) Pages: 60 pound paper 8-1/2 inches by 11 inches size
with minimum of 2 punched holes 8-1/2 inches apart
reinforced with plastic, cloth, or metal.
c) Fasteners: Metal screw post or Acco metal strap type.
d) Diagrams and Illustrations: Attach foldouts, as required.
PART 3 EXECUTION
NOT USED
END SECTION
SUBMITTAL PROCEDURES
01 33 00-6
https:Hus-partner-integrations.egnyte.com/msoffice/wapi/files/ddf7el 81-8e28-4b3a-a5c4-
fb270b094c67/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/01 33 00 Submittal Procedures.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 01 42 13
DEFINITIONS AND ABBREVIATIONS
PART 1 GENERAL
1.1 DEFINITIONS AND TERMS
A. Whenever in these Specifications, or in other Contract Documents, the following
terms are used, the intent and meaning shall be interpreted as follows:
1. Board: Fresno County Board of Supervisors.
2. Calendar Day: Every day shown on the calendar.
3. Contractor: The word "Contractor" means the person, firm or corporation to
whom the award is made. Subcontractors as such will not be recognized.
a. Where pronouns "he", "his", or "him" are used in reference to the
Contractor, it shall be inferred to be inclusive of all genders.
4. Contract Price: The total amount of money for which the Contract is awarded.
5. Contract Unit Price: The Contractor's original bid for a single unit of an item
of work in the Proposal.
6. Contract Time: The number of calendar days for completion of the Work,
including authorized time extensions. In the event a calendar date is
specified for Project completion in lieu of a number of calendar days,the Work
shall be completed by that calendar date. The Contract Time shall be
computed by excluding the first and including the last day; and if the last day
be Sunday or a legal holiday, that shall be excluded.
7. Design Engineer: Provost & Pritchard Consulting Group.
8. Engineer: County of Fresno Director of Public Works and Planning, and/or
his designee.
9. Equipment: (Construction) - All machinery and equipment, together with the
necessary supplies for upkeep and maintenance, and also tools and
apparatus necessary for the proper construction and acceptable completion
of work. (Installed) - All material or articles used in equipping a facility as
furnishings or apparatus to fulfill a functional design.
10. General Conditions: As specified in Section 00 72 00 — General Conditions.
11. General Requirements: All specifications contained in Division 1.
12. Notice: Any notice allowed or required to be given by the Owner may be given
by the Engineer.
DEFINITIONS AND ABBREVIATIONS
01 42 13-1
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/ea822 bat-bef7-482 b-935f-
b38d07baf840/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 42 13 Definitions&Abbreviations.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
13. Owner: Fresno County.
14. Person: Any individual, association, partnership, corporation, trust, joint
venture or other legal entity.
15. Plans: The drawings, profiles, cross-sections, working drawings and
supplemental drawings, or reproduction thereof, approved by the Engineer,
which show the location, character, dimensions or details of the work.
16. Proposal: The offer of a Bidder when submitted on the Proposal form;
properly signed and guaranteed.
17. Reference Documents: Bulletins, Rules, Methods of Analysis or Test, Codes,
Standards, and Specifications of public or private agencies, Engineer
Societies, or Industrial Associations. Reference shall be to the latest edition
thereof, including Amendments, which are in effect and published at the time
the Request for Bids is issued, unless a specific edition is identified, in which
case reference shall be to such specific edition. Reference Documents are
intended to amplify the descriptions of materials, equipment, and construction
systems and are to be considered a part of the Contract Documents insofar
as the various sections thereof are referred to hereinafter. Examples of
Reference Documents are Federal Specifications, State Standard
Specifications, and those of American Society of Testing Materials (ASTM),
American National Standards Institute (ANSI), American Standards
Associations (ASA), and American Concrete Institute (ACI).
18. Salvage: The protection storage, and/or removal of specified existing
equipment, parts or materials during the work for retention and later use by
the Owner.
19. Sanitary Sewer: Any conduit and appurtenances intended for the reception
and transfer of sewage.
20. State: The State of California.
21. State Standard Plans: State of California, Business and Transportation
Agency, Department of Transportation, Caltrans, Standard Plans, latest
revision.
22. State Standard Specifications: Standard Specifications for the project are
those entitled "Standard Specifications, State of California, Business and
Transportation Agency, Department of Transportation", current version,
hereinafter referred to as the State Standard Specifications. These
Specifications are to be considered a part of the Contract Documents insofar
as they are not superseded by other provisions contained in Divisions 0
through 43 of these Specifications.
23. Storm Sewer: Any conduit and appurtenances intended for the reception and
transfer of storm water.
DEFINITIONS AND ABBREVIATIONS
01 42 13-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/ea822 bat-bef7-482 b-935f-
b38d07baf840/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 42 13 Definitions&Abbreviations.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
24. Street: Any public road, highway, parkway, freeway, alley, walk or
right-of-way.
25. Surety: Any individual, firm or corporation bound with and for the Contractor
for the acceptable performance, execution and completion of the Work, and
for the satisfaction of all obligations incurred.
26. Utility: Tracks, overhead of underground wires, pipelines, conduits, ducts or
structures, sewers of storm drains owned, operated or maintained in or
across a public right-of-way or private easement.
27. Water Main: Any conduit and appurtenances intended for the distribution of
water.
1.2 REFERENCED STANDARDS
A. The standards referred to, except as modified, shall have full force and effect as
though printed in this Specification, and shall be the latest edition or revision thereof
in effect on the bid opening date, unless a particular edition or issue is indicated.
Copies of these standards are not available from the Owner. The Engineer will
furnish, upon request, information as to how copies may be obtained.
1.3 LIST OF ABBREVIATIONS
A. Abbreviations and terms, or pronouns in place of them, shall be interpreted as
follows:
AA Aluminum Association
AABC Associated Air Balance Council
AAMA Architectural Aluminum Manufacturers Association
AASHTO American Association of State Highway and Transportation Officials
ABMA American Boiler Manufacturers Association
ACI American Concrete Institute
ACPA American Concrete Pipe Association
ADC Air Diffusion Council
AEIC Association of Edison Illuminating Companies
AFBMA Antifriction Bearing Manufacturers Association
AGA American Gas Association
AGMA American Gear Manufacturers Association
AHA American Hardboard Association
Al Asphalt Institute
AIA American Institute of Architects
AISC American Institute of Steel Construction
AISI American Iron and Steel Institute
AITC American Institute of Timber Construction
AMCA Air Moving and Conditioning Association
ANSI American National Standards Institute
APA American Plywood Association
API American Petroleum Institute
APWA American Public Works Association
ARI American Refrigeration Institute
ASA (now U.S.A.S.I., USA Standards Institute) Association & its Standard
Specifications
ASAHC American Society of Architectural Hardware Consultants
DEFINITIONS AND ABBREVIATIONS
01 42 13-3
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/ea822 bat-bef7-482 b-935f-
b38d07baf840/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 42 13 Definitions&Abbreviations.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
ASCE American Society of Civil Engineers
ASHRAE American Society of Heating, Refrigerating, and Air-Conditioning Engineers
ASME American Society of Mechanical Engineers
ASSE American Society of Sanitary Engineers
ASTM American Society for Testing and Materials
AWG American Wire Gage
AWI Architectural Woodwork Institute
AWPA American Wood-Preservers'Association
AWS American Welding Society
AWWA American Water Works Association
BHMA Builders Hardware Manufacturers Association
BIA Brick Institute of America (formerly SCPI)
CAL/OSHA California Occupational Safety and Health Administration
CALTRANS California Department of Transportation
CBC California Building Code
CCR California Codes of Regulations
CDA Copper Development Association
CEC California Electrical Code
CEQA California Environmental Quality Act
CFR Code of Federal Regulations
CISPI Cast Iron Soil Pipe Institute
CMAA Crane Manufacturers Association of America
CMC California Mechanical Code
CPC California Plumbing Code
CRA California Redwood Association
CRSI Concrete Reinforcing Steel Institute
CS Commercial Standard (U.S. Department of Commerce)
DHI Door and Hardware Institute
DIPRA Ductile Iron Pipe Research Association
EEI Edison Electric Institute
EJCDC Engineers' Joint Contract Documents Committee
EPA Environmental Protection Agency
FED SPEC Federal Specification
FCI Fluid Controls Institute
FGMA Flat Glass Marketing Association
FIA Factory Insurance Association
FM Factory Mutual
FSA Fluid Sealing Association
FTI Facing Tile Institute
HEI Heat Exchange Institute
HMI Hoist Manufacturers Institute
HPMA Hardwood Plywood Manufacturers Association
HTI Hand Tools Institute
ICBO International Conference of Building Officials
-B-R Institute of Boiler and Radiator Manufacturers
IEEE Institute of Electrical and Electronics Engineers
IES Illuminating Engineering Society
IFI Industrial Fasteners Institute
IPCEA Insulated Power Cable Engineers Association
DEFINITIONS AND ABBREVIATIONS
01 42 13-4
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/ea822 bat-bef7-482 b-935f-
b38d07baf840/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 42 13 Definitions&Abbreviations.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
ISA Instrument Society of America
JIC Joint International Conference (Hydraulic Institute)
MHI Materials Handling Institute
MIL Military Specification
MMA Monorail Manufacturers Association
MSS Manufacturers' Standardization Society
NAAMM National Association of Architectural Metals Manufacturers
NACE National Association of Corrosion Engineers.
MBBPVI National Board of Boiler and Pressure Vessel Inspectors
NBHA National Builders Hardware Association
NCSPA National Corrugated Steel Pipe Association
NEC National Electrical Code
NECA National Electrical Contractors Association
NEMA National Electrical Manufacturers Association
NEMI National Elevator Manufacturing Industry
NFPA National Fire Protection Association
NIST National Institute of Standards and Technology
NLA National Lime Association
NPC National Plumbing Code
NPT National Pipe Thread
NRCA National Roofing Contractors'Association
NRMCA National Ready Mixed Concrete Association
NSC National Safety Council
NSF National Sanitation Foundation
NTMA National Terrazzo and Mosaic Association
NWMA National Woodwork Manufacturers Association
OSHA Occupational Safety and Health Administration
PCA Portland Cement Association
PCI Prestressed Concrete Institute
PDI Plumbing and Drainage Institute
PFI Pipe Fabrication Institute
PS Product Standard
RTI Resilient Tile Institute (formerly AVATI)
SAE Society of Automotive Engineers
SCPRF Structural Clay Products Research Foundation
SI International Systems of Units (Metric)
SIGMA Sealed Insulating Glass Manufacturers Association
SFPA Southern Forest Products Association
SJI Steel Joist Institute
SMA Screen Manufacturers Association
SMACNA Sheet Metal and Air Conditioning Contractors National Association
SPFA Steel Plate Fabricators Association
SPI Society of the Plastics Industry
SPTA Southern Pressure Treaters Association
SSI Scaffolding and Shoring Institute
SSPC Steel Structures Painting Council
SSPWC Standard Specifications for Public Works Construction (Greenbook)
UL Underwriters' Laboratories
DEFINITIONS AND ABBREVIATIONS
01 42 13-5
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/ea822 bat-bef7-482 b-935f-
b38d07baf840/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 42 13 Definitions&Abbreviations.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
UPC Uniform Plumbing Code
USBR U.S. Bureau of Reclamation
USGS United States Geological Survey
WCLA West Coast Lumbermen's Association (Standard Grading and Dressing Rule)
WCLIB West Coast Lumber Inspection Bureau
WIC Woodwork Institute of California
WRI Wire Reinforcement Institute, Inc.
WWPA Western Wood Products Association
END SECTION
DEFINITIONS AND ABBREVIATIONS
01 42 13-6
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/ea822 bat-bef7-482 b-935f-
b38d07baf840/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 42 13 Definitions&Abbreviations.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 01 43 00
QUALITY CONTROL AND TESTING
PART 1 GENERAL
1.1 NOTICE OF DEFECTS
A. Prompt notice of all defective Work of which Owner or Engineer has actual
knowledge will be given to Contractor.
B. All defective Work may be rejected, ordered to be corrected, or accepted, at the
discretion of the Owner and Engineer.
1.2 ACCESS TO WORK
A. Owner, Engineer, their consultants and other representatives and personnel of
Owner, independent testing laboratories, and governmental agencies with
jurisdictional interests shall have access to the Site and the Work at reasonable
times for their observation, inspecting, and testing. Contractor shall provide them
proper and safe conditions for such access and advise them of Contractor's Site
safety procedures and programs so that they may comply therewith.
1.3 MATERIALS AND EQUIPMENT
A. Materials and equipment shall be subject to the requirements of Section 01 35 00—
Material Substitution Procedures.
1.4 PROJECT SITE TESTING
A. Contractor shall give Engineer timely notice of readiness of the Work for all required
inspections, tests, or approvals and shall cooperate with inspection and testing
personnel to facilitate required inspections or tests.
B. Except for specified material suitability tests, all initial routine field tests of materials
shall be at the expense of the Owner and shall be performed by an independent
certified laboratory designated by the Owner. Whenever a specified percent relative
compaction test is required and the material or portion thereof so tested fails to meet
or exceed the relative compaction specified, all subsequent retesting shall be
performed at the expense of the Contractor.
1.5 TEST STANDARDS
A. All sampling, specimen preparation, and testing of materials shall be in accordance
with the standards of nationally recognized technical organizations.
B. The physical characteristics of all materials not particularly specified shall conform
to the latest standards published by the ASTM, where applicable.
QUALITY CONTROL AND TESTING
01 43 00-1
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/addceea2-1 aad-4ad6-9ad3-
83662f011c7c/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 43 00 Quality Control and Testing.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1.6 UNCOVERING WORK
A. If any Work (or the work of others) that is to be inspected, tested, or approved is
covered by Contractor without concurrence of Engineer, it must, if requested by
Engineer, be uncovered for Engineer's observation and recovered at Contractor's
expense.
B. If Engineer considers it necessary or advisable that covered Work be re-observed
by Engineer or inspected or tested by others, Contractor, at Engineer's request, shall
uncover, expose, or otherwise make available for observation, inspection, or testing
as Engineer may require, that portion of the Work in question, furnishing all
necessary labor, material, and equipment.
1. If it is found that the uncovered Work is defective, Contractor shall promptly
correct said defects, including all work involved in uncovering and recovering
the work, at no cost to the Owner.
2. If, the uncovered Work is not found to be defective, Contractor shall be
allowed an increase in the Contract Price or an extension of the Contract
Times, or both, directly attributable to such uncovering, exposure,
observation, inspection, testing, replacement, and reconstruction.
1.7 CORRECTION OR REMOVAL OF DEFECTIVE OR REJECTED WORK
A. Upon receipt of notice, Contractor shall correct all defective or rejected Work and
replace it with Work that is not defective, at no cost to the Owner.
1.8 ACCEPTANCE OF DEFECTIVE WORK
A. If, instead of requiring correction or removal and replacement of defective Work,
Owner prefers to accept it, Owner may do so.
1. If any such acceptance occurs, a Change Order will be issued incorporating
the necessary revisions in the Contract Documents with respect to the Work,
and Owner shall be entitled to an appropriate decrease in the Contract Price,
reflecting the diminished value of Work so accepted.
2. Engineer shall determine the reasonableness of the diminished value of Work
so accepted and Contractor shall pay all costs involved in making such
determination.
END SECTION
QUALITY CONTROL AND TESTING
01 43 00-2
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/addceea2-1 aad-4ad6-9ad3-
83662f011c7c/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 43 00 Quality Control and Testing.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 01 50 00
TEMPORARY FACILITIES
PART 1 GENERAL
1.1 GENERAL
A. The Contractor shall provide all temporary facilities and utilities required for
completion of the Work as well as safety precautions and programs. No attempt is
made to set out in detail the Contractor's means or methods necessary to
accomplish the tasks involved.
1.2 TEMPORARY UTILITIES
A. Water
1. The Contractor may make arrangements with the Owner to use municipal
water where appropriate during construction. See Section 01 51 36 —
Watering of these specifications for details.
2. Water used for human consumption shall be kept free from contamination
and shall conform to the requirements of the State and local authorities for
potable water.
B. Sanitary Facilities
1. The Contractor shall provide suitable and adequate sanitary conveniences
for the use his staff at the site of the Work. Such conveniences shall include
chemical toilets or water closets and shall be located at appropriate locations
at the site of the Work. All sanitary conveniences shall conform to the
regulations of the public authority having jurisdiction over such matters.At the
completion of the Work, all such sanitary conveniences shall be removed,
and the site left in a sanitary condition.
2. With respect to sanitation facilities, the Contractor shall cooperate with and
follow directions of representatives of the Public Health Service and the State.
State and County Public Health Service representatives shall have access to
the Work, whether it is in preparation or progress, and the Contractor shall
provide facilities for such access and inspection.
1.3 TEMPORARY CONSTRUCTION FACILITIES
A. Construction hoists, shoring, and similar temporary facilities shall be of ample size
and capacity to adequately support and move the loads to which they will be
subjected. Railings, enclosures, safety devices, and controls required by law or for
adequate protection of life and property shall be provided.
B. Temporary supports shall be designed with an adequate safety factor to assure
adequate load bearing capability. The Contractor shall submit design calculations
TEMPORARY FACILITIES
01 50 00-1
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/15428477-4e37-472d-93ce-
2c894b41cd22/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 50 00 Temporary Facilities.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
prepared by a professional registered engineer for staging and shoring prior to
application of loads.
C. Barriers shall be placed at each end of all excavations and at such places as may
be necessary along excavations to warn all pedestrian and vehicular traffic of such
excavations from one hour before sunset each day to one hour after sunrise of the
next day until such excavation is entirely refilled, compacted, and paved. All
excavations shall be barricaded in such a manner as to prevent persons from falling,
walking, or otherwise entering any excavation in any street, roadway, parking lot,
treatment plant, or any other area, public or private.
D. The Contractor shall adequately identify and guard all hazardous areas and
conditions by visual warning devices and, where necessary, physical barriers. Such
devices shall, as a minimum, conform to the requirements of Cal/OSHA.
E. At such time or times any temporary construction facilities and utilities are no longer
required for the work, the Contractor shall notify the Engineer of his intent and
schedule for removal of the temporary facilities and utilities and obtain the
Engineer's approval before removing the same. As approved, the Contractor shall
remove the temporary facilities and utilities from the site as his property and leave
the site in such condition as specified, as directed by the Engineer, and/or as
indicated on the Plans.
1.4 ACCESS ROADS AND STAGING AREA
A. Adequate access shall be maintained to all storage areas and other areas to which
frequent access is required. The Contractor shall limit the location of his storage of
equipment and materials to the location indicated on the plans. The Contractor shall
provide any temporary storage required for the protection of equipment and
materials as recommended by manufacturers of such materials.
B. Storage and protection:
1. Materials and equipment shall be stored in accordance with supplier's written
instructions, with seals and labels intact and legible. Exposed metal surfaces
of valves, fittings and similar materials shall be coated in accordance with
manufacturer's recommendations to prevent corrosion.
2. Storage shall be arranged to provide access for inspection. The Contractor
shall periodically inspect to assure materials and equipment are undamaged
and are maintained under required conditions.
END SECTION
TEMPORARY FACILITIES
01 50 00-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/15428477-4e37-472d-93ce-
2c894b41cd22/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 50 00 Temporary Facilities.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 01 51 36
WATERING
PART 1 GENERAL
1.1 WORK INCLUDED
A. The work of this section consists of furnishing, hauling, and applying water required
for compaction of embankments, backfills, subgrade, and base course, and for
landscaping, and other construction operation.
1.2 RELATED WORK
A. Section 01 50 00 —Temporary Facilities
B. Section 01 57 27 — Dust Control
1.3 REFERENCES
A. State Standard Specifications Section 10-6, Watering
PART 2 PRODUCTS
2.1 WA TER
A. Free of debris, organic matter, and other objectionable substances.
PART 3 EXECUTION
3.1 WATER TRUCK
A. At least 1,000-gallon capacity.
B. Keep at least one water truck on site at all times, unless Engineer approves removal
of the truck from the site before final completion.
3.2 APPLICATION
A. Use pressure type distributors or a pipeline equipped with sprinkler system. Provide
approved meter devices near points of discharge.
B. Ensure a uniform application of water for optimum moisture content. Avoid
excessive runoff and minimize water waste.
C. The Contractor may water excavation areas before excavating. Drill full depth of
excavation to make moisture determinations.
D. If over watering occurs, de-water at no additional expense to the Owner.
WATERING
01 51 36-1
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/9 b672 b80-6439-4a8 b-a697-
278af80b1281/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 51 36 Watering.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3.3 SPECIAL CONTROLS
The Contractor shall take all reasonable means to minimize inconvenience and injury to
the public by dust, noise, diversion of storm water, or other agencies under his control.
A. Dust Control
1. As specified in Section 01 57 27, Dust Control
B. Water
1. The County will allow connection to the existing storage tank with the
following limitations.
a. Use of CSA 43 water from the system will not be allowed during peak
hours (6 am to 8 am and 5 pm to 8 pm daily).
b. Contractor shall be responsible for providing all necessary materials,
equipment, and labor (under County operator's supervision)
to connect to the tank, including necessary pump and water meter.
C. Furthermore, the Contractor shall be responsible to provide necessary
back up water supply or storage if Contractor feels the water provided
by County will not fulfill their needs during well drilling operations.
d. The water supply will be limited to 100 gpm during off peak demand
and/or when tank level is not less than 1/2 level. Contractor will be
forced to stop pumping out of the tank until it gets refilled. The tank has
a volume of approximately 200,000 gallons. The level on the tank can
be read from the existing gauge attached to the tank.
2. A potential alternative source of water is the fire suppression storage tank
located on the elementary school's property. Should Contractor require use
of this source, it is the Contractor's responsibility to coordinate directly with
the School district and arrange necessary fees and usage agreement.
3. Water used for human consumption shall be kept free from contamination
and shall conform to the requirements of the State and local authorities for
potable water.
4. Full compensation for furnishing all labor, materials, tools and equipment and
for doing all work involved in furnishing and applying water as required by the
Contract Documents and Specifications, State Standard Specifications, shall
be considered as included in the contract unit prices paid for other items of
work and no additional allowance will be made therefore.
END SECTION
WATERING
01 51 36-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/9 b672 b80-6439-4a8 b-a697-
278af80b1281/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 51 36 Watering.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
WATERING
01 51 36-3
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/9 b672 b80-6439-4a8 b-a697-
278af80b1281/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 51 36 Watering.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 01 57 13
EROSION CONTROL
PART 1 GENERAL
1.1 WORK INCLUDED
A. The work of this section consists of protecting from erosion all areas disturbed by
new construction and construction operations, including areas disturbed by
demolition, earthwork, and fence, piping and equipment installation.
1.2 RELATED WORK
A. Section 01 57 23 — Storm Water Pollution Prevention Plan
B. Section 01 57 27 — Dust Control
1.3 SUBMITTALS
A. As specified in Section 01 33 00— Submittal Procedures.
B. One-bale of proposed straw.
PART 2 PRODUCTS
2.1 RICE STRAW
A. Sterile rice straw.
PART 3 EXECUTION
3.1 PREPARATION
A. Loosen areas to be protected by raking or other approved method before
application. Maintain grading and drainage patterns.
3.2 PLACING STRAW
A. Exercise particular care to ensure application is made uniformly.
B. The Contractor shall install and maintain protected areas as required by the Storm
Water Pollution Prevention Plan.
3.3 ACCEPTANCE
A. Application will be considered complete when all soil disturbing activities are
completed and all unpaved disturbed areas have an even application of straw. No
gaps (larger than 6 inches x 6 inches) will be permitted.
EROSION CONTROL
01 57 13-1
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/56 bgf335-308 b-44d d-a ba9-
78c8e5427b02/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 57 13 Erosion Control.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
END SECTION
EROSION CONTROL
01 57 13-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/56 bgf335-308 b-44d d-a ba9-
78c8e5427b02/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 57 13 Erosion Control.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 01 57 23
STORM WATER POLLUTION PREVENTION PLAN
PART 1 GENERAL
1.1 WORK INCLUDES
A. It is assumed the Project total disturbed area is less than 1 acre. The Contractor
shall develop a Water Pollution Control Plan (WPCP) that shall prevent sediment
and/or pollutants from entering the ground, storm drains, streams, or water bodies
throughout the duration of the Work in compliance with the permit requirements,
including CalGreen Building Standards. Work shall be performed in accordance with
all Federal, State, and local regulations.
B. The Contractor shall furnish and exercise every reasonable precaution to protect
groundwater, channels, storm drains, and bodies of water from pollution and provide
all labor, materials, tools, and equipment necessary to prevent pollution associated
with construction activities, including preparation of a WPCP or Stormwater Pollution
Prevention Plan (SWPPP) and amendments if necessary for CGP Compliance,
installation, maintenance and final removal of all temporary and permanent erosion
and sediment control measures, in accordance with the requirements of the Contract
Documents.
C. Penalties: Failure to comply with this Section may result in significant fines and
possible imprisonment. The Regional Water Quality Control Board (RWQCB) or
other prosecuting authority may assess fines for each violation. Should the District
be fined or penalized as a result of the Contractor failing to comply with this Section
and applicable permit requirements, the Contractor shall reimburse the County for
any and all fines, penalties and related costs.
D. All costs for work required for compliance with this Section shall be included in the
price bid for "Prepare and Implement SWPPP (or WPCP)".
1.2 REFERENCES
A. California State Water Resources Control Board, Construction General Permit
2022-0057-DWQ,
https://www.waterboards.ca.gov/board decisions/adopted orders/water quality/20
22/wqo 2022-0057-dwg.pdf
B. California Stormwater Quality Association (CASQA), https://www.casga.org
1.3 SUBMITTALS
A. As specified in Section 01 33 00 — Submittal Procedures.
B. The contractor shall submit a Water Pollution Control Plan (WPCP) demonstrating
pollution prevention measures and steps to be taken to ensure no pollutant
discharges from the project site at least three weeks prior to beginning work and
within 2 days of issuance of the Notice to Proceed.
STORM WATER POLLUTION PREVENTION PLAN
01 57 23-1
https://us-partner-i ntegrations.eg nyte.com/msoffice/wopi/files/d98ab6eb-1738-487c-8e73-
80e2246d07f8/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 57 23 Storm Water Pollution Prevention_under 1 ac.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1.4 QUALITY ASSURANCE
At minimum, the following measures shall be taken to help ensure control of storm water and
non-storm water pollution. These measures shall not be construed to limit or override the
measures set forth and called for in the WPCP.
A. Control the rate and effect of dewatering in such a manner as to avoid all
objectionable settlement and subsidence and to assure the integrity of the finished
work.
B. Where critical structures or facilities exist immediately adjacent to areas of proposed
dewatering, establish reference points and observe at frequent intervals to detect
any settlement that may develop. Conduct the dewatering operation in a manner
that protects adjacent natural resources and facilities. Cost of repairing all damage
to adjacent resources and facilities shall be the sole responsibility of the Contractor.
C. Arrange demolition activities to minimize erosion to the maximum practical extent.
Clearing, excavation, and grading shall be limited to those areas of the Project site
necessary for demolition. Minimize the area exposed and unprotected.
D. Clearly mark and delineate the work limits activities.
1.5 GENERAL REQUIREMENTS
A. The Contractor shall exercise care in preserving vegetation and protecting property,
to avoid disturbing areas beyond the limits of the Work and promptly repair any
damage caused by Contractor operations.
B. The Contractor shall provide all necessary water pollution control devices to prevent,
control, and abate water pollution, and implement good housekeeping pollution
control measures to reduce the discharge of pollutants from the Site to the maximum
extent practicable. These water pollution control devices include structural BMPs,
drains, gutters, slope protection blankets and retention basins and shall be
constructed concurrently with other Work at the earliest practicable time.
C. Stockpiles of earth and other construction-related materials shall be protected from
being transported from the Site by wind or water using covers or equivalent.
D. The Contractor shall properly store and handle fuels, oils, solvents, and other toxic
materials in a manner not to contaminate the soil or surface waters, enter the
groundwater, or be placed where they may enter a live stream, channel, drain, or
other water conveyance facilities. All approved toxic storage containers shall be
protected from weather. Spills shall be cleaned immediately, and soiled materials
shall be properly disposed of. Spills shall not be discharged.
E. Excess or waste concrete (including concrete decant water) shall not be washed
onto bare ground, into the public way or any drainage systems. The concrete wastes
shall be retained on-site until they can be appropriately disposed of or recycled.
Concrete wastes shall not be discharged.
STORM WATER POLLUTION PREVENTION PLAN
01 57 23-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/d 98a b6eb-1738-487c-8e73-
80e2246d07f8/WOPlServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 57 23 Storm Water Pollution Prevention_under 1 ac.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
F. Non-stormwater runoff from equipment washing, vehicle washing, and any other
activities shall be contained at the work site and properly disposed of. Non-
stormwater runoff shall not be allowed to discharge.
G. The Contractor shall prevent sediments and other materials to be tracked from the
Site by vehicle traffic. Construction entrance roadways shall be stabilized to inhibit
sediments from being deposited onto public ways. The Contractor shall immediately
sweep up accidental depositions and not allow depositions to be washed away by
rain or by any other means.
1.6 REGULATORY REQUIREMENTS
A. The Contractor shall comply with the requirements of the State Water Resources
Control Board (SWRCB), RWQCB, California Administrative Code, 2016 California
Green Building Standards Code Section 5, Owner and any other agencies having
jurisdiction in storm water and non-storm water discharges and waste management.
PART 2 PRODUCTS
2.1 GENERAL
A. Materials furnished for BMPs shall meet the requirements of the California
Stormwater Quality Association, Stormwater Best Management Practice Handbook,
Construction — August 2023 edition (or most current version) unless otherwise
indicated.
PART 3 EXECUTION
3.1 GENERAL DESCRIPTION
A. The Contractor shall install and maintain all pollution, erosion, and sediment control
measures and carry out inspections in accordance the approved WPCP.
3.2 FIELD QUALITY CONTROL
A. The Contractor shall maintain the BMPs and other protective measures in good and
effective operating condition by performing routine inspections to determine
condition and effectiveness, by restoration of destroyed vegetative cover, and by
repair of erosion and sediment control measures and other protective measures.
3.3 MAINTENANCE OF TEMPORARY FACILITIES
A. Inspect erosion and sediment control structures daily, including site exit locations,
and as specified in the SWPPP.
B. Sediment shall be removed from behind run off control structures after each storm,
or as directed by the Engineer or Owner.
C. If areas are seeded, Contractor shall examine those areas during and after major
storms to check that grass is becoming established.
STORM WATER POLLUTION PREVENTION PLAN
01 57 23-3
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/d 98a b6eb-1738-487c-8e73-
80e2246d07f8/WOPlServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 57 23 Storm Water Pollution Prevention_under 1 ac.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3.4 DISPOSAL OF SEDIMENT FROM STORM WATER POLLUTION CONTROL
STRUCTURES
A. Sediment excavated from temporary sediment control structures shall be disposed
on the site with general fill or with topsoil. Sediment shall be allowed to dry out as
required before reuse. All trash shall be removed before reuse.
B. Contractor shall place the sediment removed from traps and other structures where
it will not enter a storm drain or water course and where it will not immediately
reenter the basin.
3.5 REMOVAL OF TEMPORARY STORM WATER POLLUTION CONTROL MEASURES
A. In accordance with SWPPP requirements, temporary control measures shall be
removed once all drainage area ground disturbance is completed, permanent
drainage works have been constructed and full stabilization is achieved. Contractor
shall not breach any temporary control structures until the associated catchment
area is complete unless approved by the Engineer.
END SECTION
STORM WATER POLLUTION PREVENTION PLAN
01 57 23-4
https://us-partner-i ntegrations.eg nyte.com/msoffice/wopi/files/d98ab6eb-1738-487c-8e73-
80e2246d07f8/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 57 23 Storm Water Pollution Prevention_under 1 ac.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 01 57 27
DUST CONTROL
PART 1 GENERAL
1.1 WORK INCLUDED
A. The work of this section consists of implementing measures to prevent air pollution
during construction activities, in accordance with Federal, State, and local
regulations. It is assumed that the Project will have a total disturbed area less than
5 acres.
1.2 RELATED WORK
A. Section 01 50 00 —Temporary Facilities
B. Section 01 51 36 —Watering
C. Division 2 — Existing Conditions
D. Division 31 — Earthwork
1.3 REFERENCES
A. San Joaquin Air Pollution Control District (SJVAPCD) Regulation VIII.
1.4 SUBMITTALS
A. As specified in Section 01 33 00 — Submittal Procedures.
B. Submittals under this section shall be completed and submitted at least 48 hours
prior to beginning work.
C. Proof of submittal of San Joaquin Air Pollution Control District (SJVAPCD)
Construction Notification Form.
1.5 QUALITY ASSURANCE
A. Control the rate and effect of watering in such a manner as to avoid all objectionable
settlement and subsidence as approved by the Engineer and to assure the integrity
of the finished work.
B. Clearly mark and delineate the work limits activities.
1.6 REGULATORY REQUIREMENTS
A. Contractor shall comply with all provisions of the SJVAPCD regulations, as well as
Federal and State regulations.
DUST CONTROL
01 57 27-1
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/eee2fd 00-0 bOf-4459-b938-
5d90ee896048MOPIServiceld_TP_EGNYTE_PLUSMOPIUserld_189.ppeng.egnyte.com/01 57 27 Dust Control_under 5 ac.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
PART 2 PRODUCTS
2.1 EQUIPMENT
A. Before the work begins, sufficient equipment and resources shall be available on
the site to assure that the operation and adequacy of the dust control measures can
be continuously maintained.
2.2 DUST CONTROL MEASURES
A. Water shall be available to the contractor for dust control as specified in section 01
50 00 —Temporary Facilities.
PART 3 EXECUTION
3.1 GENERAL DESCRIPTION
A. Dust control measures shall include, but may not be limited to: Water application,
physical barriers limiting site access, reduction of vehicle speed on site, utilization
of gravel pads, and utilization of grizzlies. If physical barriers are utilized, the
Engineer shall approve the location, size, and type. Physical barriers shall be
removed upon project completion.
B. Furnish, install, maintain, and operate necessary control measures and other
equipment necessary to prevent dust. Temporary measures shall be to Contractor's
own design and Contractor shall be solely responsible for risks related to the
management of dust control during construction.
3.2 DUST CONTROL
A. The Contractor shall take whatever steps, procedures, or means as are required to
limit dust generated by his operations during the Work, including Saturdays,
Sundays, and Holidays. Dust shall be controlled to the standards of the local
governing agency or, in the absence of local standards, to the satisfaction of the
Engineer. Dust control shall extend to any unpaved road which the Contractor or
any of his subcontractors are using, to excavation or fill areas, to demolition
operations, and to other activities. Control shall be by sprinkling, use of dust
palliatives, modification of operations, or any other means acceptable to the local
governing agency or, in the absence of same, the Engineer.
B. If the dust control is not adequate in the opinion of the Engineer, this work may be
done by others, and the cost shall be deducted from the total payment due the
Contractor.
END SECTION
DUST CONTROL
01 57 27-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/eee2fd 00-0 bOf-4459-b938-
5d90ee896048MOPIServiceld_TP_EGNYTE_PLUSMOPIUserld_189.ppeng.egnyte.com/01 57 27 Dust Control_under 5 ac.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 01 57 50
CONSTRUCTION STAKES, LINES, AND GRADES
PART 1 GENERAL
1.1 LINES AND GRADE
A. The Work shall be executed in accordance with the lines and grades indicated in
the Contract Documents. Distances and measurements, except elevations and
structural dimensions, shall be made on horizontal planes.
1.2 CONSTRUCTION STAKING
A. Engineer or Engineer's representative will provide project control monuments as
shown on the Plans (vertical and horizontal) at the Owner's expense. The Engineer
will provide one set of grade control stakes.
B. All other construction staking necessary for the work shall be done by Contractor
with compensation included in bid item(s), as deemed appropriate by the Contractor.
C. The Contractor shall be responsible for preserving construction survey stakes,
permanent survey monuments and benchmarks for the duration of their usefulness.
If any construction survey stakes permanent survey monuments or benchmarks are
lost or disturbed and need to be replaced, such replacement shall be made by the
Engineer at the expense of the Contractor.
D. The Contractor shall notify the Engineer at least three (3) working days before he
will require survey services in connection with laying out of any portion of the Work.
The Contractor at his own expense shall dig all holes necessary for line and grade
stakes prior to requesting survey services that depend on such digging.
END SECTION
CONSTRUCTION STAKES, LINES, AND GRADES
01 57 50-1
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/8e3a9477-af5e-47fd-a 1 ef-
9f4d0a9384e1/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 57 50 Construction Staking.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
This Page is Intentionally Left Blank
CONSTRUCTION STAKES, LINES, AND GRADES
01 57 50-2
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/8e3a9477-af5e-47fd-a 1 ef-
9f4d0a9384e1/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 57 50 Construction Staking.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 01 74 19
CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
PART 1 GENERAL
1.1 WORK INCLUDED
A. The provisions of this Section apply to newly constructed buildings, building additions
of 1,000 square feet or greater, and/or building alterations with a permit valuation of
$200,000 or above (for occupancies within the authority of California Building
Standards Commission)
B. This section includes administrative and procedural requirements for the following:
1. Recycling nonhazardous demolition and construction waste.
2. Disposing of nonhazardous demolition and construction waste.
C. Related Requirements
1. Comply with local regulations for disposal of waste resulting from site clearing
and removal of above- and below-grade improvements.
2. Comply with the local codes and requirements governing construction waste
management for municipal construction waste management requirements.
1.2 RELATED WORK
A. Section 02 41 00 - Demolition
1.3 REFERENCES
A. California Green Building Standards Code, latest revision.
1.4 DEFINITIONS
A. Construction Waste: Building and site improvement materials and other solid waste
resulting from construction, remodeling, renovation, or repair operations, including
packaging.
B. Demolition Waste: Building and site improvement materials resulting from demolition
or selective demolition operations.
C. Disposal: Removal off-site of demolition or construction waste and subsequent
recycling, salvage, reuse, or disposal, as acceptable to authorities having jurisdiction.
CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 74 19-1
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bO967a46-4234-4 b40-84eb-
dff9ad2a8fe5/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 74 19 Construction Waste Management and Disposal.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
D. Recycle: Recovery of demolition or construction waste for subsequent processing
in preparation for reuse.
E. Salvage: Recovery of demolition or construction waste and subsequent sale or
reuse in another facility, or delivery to the Owner as specified in Section 02 41 00
Demolition.
F. Salvage and Reuse: Recovery of demolition or construction waste and subsequent
incorporation into the Work.
1.5 PERFORMANCE REQUIREMENTS
A. Recycle and/or salvage for reuse a minimum of 65 percent of the nonhazardous
construction and demolition waste, in accordance with the `Guide to the 2016 California
Green Building Standards Code, Nonresidential", Section 5.408.1.1, 5.408.1.2, or
5.408.1.3; or meet the local construction and demolition waste management
ordinance, whichever is more stringent.
1.6 SUBMITTALS
A. Waste Management Plan
1. Submit Waste Management Plan within 7 days of date established for the Notice
to Proceed.
2. The Waste Management Plan shall be prepared in accordance with the
California Green Building Standards Code, latest revision, and shall include the
following:
a. Identify the construction and demolition waste materials to be diverted
from disposal by efficient usage, recycling, reuse on the project, or
salvage for future use or sale.
b. Indicate if construction and demolition waste materials will be sorted on-
site (source-separated) or bulk mixed (single stream).
C. Identify diversion facilities where construction and demolition waste
material collected will be taken.
d. Specify that the amount of construction waste and demolition materials
diverted shall be calculated by weight or volume, but not by both.
e. Construction Waste Management Acknowledgement Form. The
Acknowledgement Form shall be signed by all subcontractors, to
acknowledge that they have read the Waste Management Plan for the
project, they understand the goals of the plan, and agree to follow the
procedures described in the plan.
CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 74 19-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bO967a46-4234-4 b40-84eb-
dff9ad2a8fe5/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 74 19 Construction Waste Management and Disposal.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
B. Waste Reduction Progress Reports
1. Documentation shall be provided to the Owner,which demonstrates compliance
with Sections 5.408.1.1 through 5.408.1.3 of the `Guide to the 2016 California
Green Building Standards Code, Nonresidential". The Waste Management Plan
shall be updated as necessary and shall be accessible during construction for
examination by the enforcing agency.
2. Concurrent with each Application for Payment, submit report. Include the
following information, as applicable:
a. Material type.
b. Total quantity of waste in tons.
C. Quantity of waste salvaged, both estimated and actual in tons.
d. Quantity of waste recycled, both estimated and actual in tons.
e. Total quantity of waste recovered (salvaged plus recycled) in tons.
f. Total quantity of waste recovered (salvaged plus recycled) as a
percentage of total waste.
C. Construction Waste Management Final Report
1. A construction waste management final report containing information and
supporting documentation that demonstrates compliance with the Waste
Management Plan, shall be provided to the enforcing agency before the final
inspection. The required documentation shall include, but is not necessarily
limited to, the following:
a. Documentation of the quantity by weight of each material type diverted
or disposed, consistent with the requirements of the approved Waste
Management Plan, and receipts or written certification from all facilities
and waste management companies utilized to divert or dispose waste
generated by the project to substantiate the amounts specified on the
construction waste management final report.
b. For projects that satisfy the waste stream reduction alternative specified
in Section 5.408.1.3, documentation of the quantity by weight of each
material type disposed and the total combined weight of construction and
demolition waste disposed in landfills as a result of the project, the
corresponding pounds disposed per square foot of the building area, and
receipts or written certification form all facilities and waste management
companies utilized to dispose waste generated by the project that
substantiate the amounts specified on the construction waste
management final report.
CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 74 19-3
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bO967a46-4234-4 b40-84eb-
dff9ad2a8fe5/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 74 19 Construction Waste Management and Disposal.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1.7 QUALITYASSURANCE
A. Waste Management Conference: Contractor will conduct regular meetings at Project
site to review methods and procedures related to waste management. Meetings shall
be conducted as needed, but not less than one time per month, and shall include, but
not be limited to, the following:
1. Review and discuss Waste Management Plan including responsibilities of
Contractor and subcontractors.
2. Review requirements for documenting quantities of each type of waste and its
disposition.
3. Review and finalize procedures for materials separation and verify availability
of containers and bins needed to avoid delays.
4. Review procedures for periodic waste collection and transportation to recycling
and disposal facilities.
5. Review waste management requirements for each trade.
PART 2 PRODUCTS (NOT USED)
PART 3 EXECUTION
3.1 PLAN IMPLEMENTATION
A. General: Implement approved Waste Management Plan. Provide handling,
containers, storage, signage, transportation, and other items as required to
implement waste management plan during the entire duration of the Contract, or
contract with an acceptable Waste Management firm to pick up and sort construction
waste materials for recycling and disposal.
B. Contractor shall be responsible for implementing, monitoring, and reporting status
of Waste Management Plan.
1. At the Contractor's option, they may contract with a qualified Waste
Management firm to manage and process the construction waste.
C. Training: Train workers, subcontractors, and suppliers on proper waste management
procedures, as appropriate for the Work.
1. Distribute waste management plan to all subcontractors.
CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 74 19-4
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/b0967a46-4234-4b40-84eb-
dff9ad2a8fe5/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 74 19 Construction Waste Management and Disposal.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
D. Site Access and Temporary Controls: Conduct waste management operations to
ensure minimum interference with roads, streets, walks, walkways, and other
adjacent occupied and used facilities.
3.2 RECYCLING DEMOLITIONAND CONSTRUCTION WASTE
A. General: Recycle paper and beverage containers used by on-site workers.
B. Preparation of Waste: Prepare and maintain recyclable waste materials according to
recycling or reuse facility requirements. Maintain materials free of dirt, adhesives,
solvents, petroleum contamination, and other substances deleterious to the recycling
process.
C. Procedures for On-Site Separation: Unless Waste Management firm is coordinating
all construction waste recycling and disposal, comply with requirements for separating
recyclable waste from other waste materials, trash, and debris. Separate recyclable
waste by type at Project site to the maximum extent practical according to approved
construction waste management plan.
1. Provide appropriately marked containers or bins for controlling recyclable waste
until removed from Project site. Include list of acceptable and unacceptable
materials at each container and bin.
a. Inspect containers and bins for contamination and remove contaminated
materials if found.
2. Stockpile processed materials on-site without intermixing with other materials.
Place, grade, and shape stockpiles to drain surface water. Cover to prevent
windblown dust.
3. Stockpile materials away from construction area.
4. Store components off the ground and protect from the weather.
5. Remove recyclable waste from Owner's property and transport to recycling
receiver or processor.
3.3 RECYCLING CONSTRUCTION WASTE
A. Packaging:
1. Cardboard and Boxes: Break down packaging into flat sheets. Bundle and store
in a dry location.
2. Polystyrene Packaging: Separate and bag materials.
CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 74 19-5
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bO967a46-4234-4 b40-84eb-
dff9ad2a8fe5/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 74 19 Construction Waste Management and Disposal.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3. Pallets: As much as possible, require deliveries using pallets to remove pallets
from Project site. For pallets that remain on-site, break down pallets into
component wood pieces and comply with requirements for recycling wood.
4. Crates: Break down crates into component wood pieces and comply with
requirements for recycling wood.
B. Wood Materials:
1. Clean Cut-Offs of Lumber: Recycle.
2. Clean Sawdust: Bag sawdust that does not contain painted or treated wood.
a. Comply with requirements in Landscaping Specification Sections for use
of clean sawdust as organic mulch.
C. Gypsum Board: Stack large clean pieces on wood pallets or in container and store
in a dry location.
3.4 DISPOSAL OF WASTE
A. General: Except for items or materials to be salvaged, recycled, or otherwise reused,
remove waste materials from Project site and legally dispose of them in a landfill or
incinerator acceptable to authorities having jurisdiction.
1. Except as otherwise specified, do not allow waste materials that are to be
disposed of accumulate on-site.
2. Remove and transport debris in a manner that will prevent spillage on adjacent
surfaces and areas.
B. Burning: Do not burn waste materials.
C. Disposal: Remove waste materials from project property and dispose in a legal
manner.
3.5 PAYMENT
A. The work under this section will be paid under the various items of work included in
the Bid Schedule. Not additional payment shall be made thereto.
END SECTION
CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 74 19-6
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bO967a46-4234-4 b40-84eb-
dff9ad2a8fe5/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 74 19 Construction Waste Management and Disposal.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 74 19-7
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bO967a46-4234-4 b40-84eb-
dff9ad2a8fe5/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 74 19 Construction Waste Management and Disposal.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 01 77 00
CONTRACT CLOSEOUT
PART 1 GENERAL
1.1 GENERAL
A. It is the intent of these Contract Documents that the Contractor shall deliver a
complete and operable facility capable of performing its intended functions and
ready for use.
1.2 CLEANING
A. Throughout the period of construction, the Contractor shall keep the Work site free
and clean of all rubbish and debris, and shall promptly remove from the site, or from
property adjacent to the site of the Work, all unused and rejected materials, surplus
earth, concrete, plaster, and debris, excepting select material which may be required
for refilling or grading.
1.3 FINAL SITE CLEAN-UP
A. Upon completion of the Work, and prior to final acceptance, the Contractor shall
remove from the vicinity of the Work all paint, surplus material, and equipment
belonging to him or used under his direction during construction.
B. The Contractor shall restore to original condition all property not designated for
alteration by these Contract Documents.
1.4 WASTE DISPOSAL
A. The Contractor shall dispose of surplus materials, waste products, demolition
materials, and debris. The Contractor shall transport and dispose of waste materials
in accordance with applicable laws and regulations.
1.5 PROJECT RECORD DOCUMENTS
A. The Contractor shall maintain at the site, available to the Owner and Engineer, one
copy of the Contract Documents, Drawings, Shop Drawings, Change Orders, and
other modifications in good order and annotated to show all changes made during
construction. These Documents shall be delivered to the Engineer for the Owner
upon completion of the Work.
B. Record documents shall be reviewed during progress meetings to ascertain that all
changes have been recorded.
C. Store Record Documents separate from documents used for construction.
CONTRACT CLOSEOUT
01 77 00-1
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/9a046f2f-d 3f4-40f2-9122-
021ec619d32e/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 77 00 Contract Closeout.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1.6 TOUCH-UP AND REPAIR
A. The Contractor shall touch-up or repair finished surfaces on structures, equipment,
fixtures, or installations that have been damaged prior to final acceptance. Surfaces
on which such touch-up or repair cannot be successfully accomplished shall be
completely refinished or in the case of hardware and similar small items, the item
shall be replaced. Such items shall include, but not be limited to, the following:
1. Exposed structure surfaces
2. Exposed equipment surfaces
3. Exposed piping surfaces
1.7 EQUIPMENT START-UP
A. After all acceptance tests have been completed by the Contractor and Owner but
prior to final acceptance, the Contractor shall recheck all equipment for proper
alignment and adjustment, check oil levels, re-lubricate all bearings and wearing
points, and in general assure that all equipment is in proper condition for continuous
operation.
1.8 OPERATION AND MAINTENANCE (O&M) MANUALS
A. See Section 01 33 00— Submittal Procedures.
1.9 FINAL EQUIPMENT CHECK
A. After testing and before acceptance, all equipment shall be test run by the Owner
for a minimum of 7 days to ensure proper operation. At the end of the test run each
piece of machinery shall be lubricated and all components and couplings checked
for proper alignment and adjustment.
B. Submit written certification that Contract Documents have been reviewed, Work has
been inspected, and that Work is complete in accordance with Contract Documents
and ready for Engineer's inspection.
C. Provide submittals to the Owner required by other governing authorities.
1.10 MANUFACTURER'S CERTIFICATES OF PROPER INSTALLATION
1. The Contractor shall submit manufacturers' certificates of proper installation
for all items of equipment.
PART 2 PRODUCTS
(Not Used)
PART 3 EXECUTION
(Not Used)
CONTRACT CLOSEOUT
01 77 00-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/9a046f2f-d 3f4-40f2-9122-
021ec619d32e/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 77 00 Contract Closeout.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
END SECTION
CONTRACT CLOSEOUT
01 77 00-3
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/9a046f2f-d 3f4-40f2-9122-
021ec619d32e/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 77 00 Contract Closeout.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
This Page is Intentionally Left Blank
CONTRACT CLOSEOUT
01 77 00-4
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/9a046f2f-d 3f4-40f2-9122-
021ec619d32e/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/01 77 00 Contract Closeout.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 02 01 20
PROTECTION OF UNDERGROUND
FACILITIES AND SURVEY MONUMENTS
PART 1 GENERAL
1.1 UNDERGROUND FACILITIES
A. Shown or Indicated: The information and data shown or indicated in the Contract
Documents with respect to existing underground facilities at or contiguous to the
Site is based on information and data furnished to Owner or Engineer by the owners
of such underground facilities, including Owner, or by others.
1. Owner and Engineer shall not be responsible for the accuracy or
completeness of any such information or data; and
2. The cost of all of the following will be included in the Contract Price, and
Contractor shall have full responsibility for:
a. Reviewing and checking all such information and data,
b. Locating all Underground Facilities shown or indicated in the Contract
Documents,
C. Coordination of the Work with the owners of such underground
facilities, including Owner, during construction, and
d. The safety and protection of all such underground facilities and
repairing any damage thereto resulting from the Work.
B. Not Shown or Indicated: If an underground facility is uncovered or revealed at or
contiguous to the Site which was not shown or indicated with reasonable accuracy
in the Contract Documents, the following shall apply.
1. Contractor shall develop and execute a work-plan, subject to Engineer's
approval to protect underground facilities.
2. The Contractor shall expose, prior to staking and trenching, all existing
utilities and existing facilities which may control proposed facility grades, and
alignment. Two working days notice shall be given to the Engineer prior to
commencing this work.
3. Full compensation for all costs involved in locating, verifying, protecting,
exposing, and otherwise providing for utilities shall be included in the amounts
bid for the various items of work, and no separate payment shall be made
therefore.
PROTECTION OF UNDERGROUND FACILITIES
0201 20-1
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/89fe5d ee-3226-4e53-8373-
895de3238f61/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/02 01 20 Protection of Underground Facilities&Monuments.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1.2 PROTECTION
A. The Contractor shall not interrupt the service function or disturb the supporting base
of any Utility by disrupting any facility identified in the Plans and Specifications
without authority from the Owner or order from the Engineer. Where protection of
such facilities is required to ensure support of utilities, the Contractor shall, unless
otherwise provided, furnish and place the necessary protection at the Contractor's
expense.
B. The Contractor shall be prepared at all times with labor, equipment and materials to
make repair on damaged mains or Utility facilities. The Contractor shall immediately
notify the Engineer and the Utility owner if he disturbs, disconnects or damages any
Utility. The Contractor shall bear the costs of repair or replacement of any Utility
facility described with reasonable accuracy in the Plans and Specifications that is
damaged by the Contractor. No extra compensation will be made for the repair of
any services or mains damaged by the Contractor, nor for any damage incurred if
the neglect or failure of providing protective barriers, lights and other devices or
means required to protect such existing utilities or facilities described with
reasonable accuracy in the Plans and Specifications.
1.3 SURVEY MARKERS AND PERMANENT REFERENCE POINTS
A. Surveying and Permanent Survey Markers
The Engineer will take measurements to assure the preservation of survey markers
(monuments and benchmarks). The Contractor shall not disturb permanent survey
markers without the consent of Engineer and shall bear the expense of replacing
any that may be disturbed without permission.
1. Replacement of survey markers shall be done only by the Engineer.
2. If disturbing of markers cannot be avoided, the Owner shall pay the cost of
replacing said markers.
B. Lot Corner Monuments
The Contractor shall preserve property line and corner survey markers except where
their destruction is unavoidable and the Contractor is proceeding in accordance with
accepted practice. Markers that are lost or disturbed by his operations shall be
replaced at the Contractor's expense by the Engineer.
END SECTION
PROTECTION OF UNDERGROUND FACILITIES
0201 20-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/89fe5d ee-3226-4e53-8373-
895de3238f61/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/02 01 20 Protection of Underground Facilities&Monuments.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 02 41 00
DEMOLITION
PART 1 GENERAL
1.1 DESCRIPTION
A. The work of this section consists of demolition and removal of concrete curb,
fencing, trees, miscellaneous debris, and salvaged items.
B. This work may also include all operations associated with crushing of Portland
cement concrete for aggregate base.
C. Definitions:
1. Portland Cement Concrete: A mixture of Portland cement, fine aggregate,
coarse aggregate, admixtures (if used) and water, proportioned and mixed.
Also, included is rebar.
1.2 WORK INCLUDED
A. Repair and restoration of areas damaged due to demolition work.
B. Salvaging of equipment for Owner.
C. Removal of demolished materials from site.
D. Remove existing fencing and other existing structures as shown on the Plans to be
removed.
E. Properly dispose of all removed materials.
F. Dewatering as needed in order to complete the proposed demolition.
G. Removal of trees and landscaping as required for construction.
1.3 RELATED WORK
A. Section 01 57 23 — Storm Water Pollution Prevention Plan
B. Section 01 57 27 — Dust Control
C. Section 03 33 00 — Cast In Place Concrete
D. Section 31 11 00 — Clearing and Grubbing
E. Section 31 23 35 — Disposal of Materials
DEMOLITION
0241 00-1
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/10b71 b4d-491 b-41 cc-945b-
712ca4c2722c/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/02 41 00 Demolition.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1.4 SEQUENCING
A. Sequence work to minimize interference with water distribution facilities
operation. The existing water well must remain in operation throughout
construction with only temporary shut-downs allowed with storage tank full.
1.5 REGULATORY REQUIREMENTS
A. Obtain all required permits.
B. Dispose of removed materials in an approved disposal or salvage facility.
1.6 REFERENCES
A. Section 17-2 — Clearing and Grubbing, State Standard Specifications
B. Section 19 — Earthwork, State Standard Specifications
1.7 SUBMITTALS
A. As specified in Section 01 33 00— Submittal Procedures
B. Demolition plan including sequence of operations. The plan shall specifically
address methods of demolition, schedule, sequence of demolition, and procedures
for archeological monitoring. Demolition shall not proceed until the plan has been
approved.
1.8 QUALITY ASSURANCE
A. General: Take all necessary precautions with regard to safety in carrying out the
demolition and site work. Erect suitable barriers around open excavations and fulfill
all appropriate requirements of CAL/OSHA. Comply with safety requirements for
demolition, ANSI A10.6-90.
1.9 PROJECT CONDITIONS
A. Underground utilities exist at this site. Contractor shall take all necessary
precautions to protect said utilities. Notify Engineer of any deviation in utility location
from that which is shown on the drawings.
B. Keep dust to a minimum at removal site and on haul roads. Use sprinklers or water
trucks as necessary or as directed by the Engineer.
C. Ensure safety of persons in demolition area. Provide temporary barricades as
required.
D. Excavations may encounter groundwater and require dewatering depending on the
time of year and amount of seasonal run-off. Loose sands exposed in excavation
sidewalls may be unstable and require shoring or lying back in accordance with
OSHA requirements. Flowing sands may also be encountered in excavations below
groundwater levels.
DEMOLITION
0241 00-2
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/10b71 b4d-491 b-41cc-945b-
712ca4c2722c/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/02 41 00 Demolition.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1.10 CLOSEOUT SUBMITTALS
A. As specified in Section 01 77 00— Contract Closeout.
B. Show all capped and abandoned utility terminations and location of remaining
facilities on project Record Drawings.
PART 2 PRODUCTS
2.1 REPAIR AND RESTORATION MATERIALS
A. Concrete shall be as specified in Section 03 33 00 — Cast In Place Concrete.
B. Backfill materials shall be as required by Section 19 — Earthwork, State Standard
Specifications.
C. Concrete shall match existing materials and conditions.
D. Concrete shall be replaced in conformance with governing authority standards.
2.2 TOPSOIL
A. Not used.
2.3 MATERIALS
A. Salvaged Materials: No materials shall be salvaged.
B. Materials and items demolished and not designated for reuse, salvage or transfer to
the Owner, as well as all debris, rubbish and other materials resulting from the
demolition operations, shall become the property of the Contractor and shall be
removed from the site within 48 hours of demolition.
C. Storage or sale of the removed items will not be permitted at the site.
PART 3 EXECUTION
3.1 INSPECTION
A. Prior to demolition, inspect the site conditions, verifying all governing dimensions,
notes and specification. Notify the Engineer of any errors or omissions in the
contract documents.
B. Make such explorations and probes as are necessary to ascertain any required
protection measures before proceeding with the demolition and removal work.
3.2 PREPARATION
A. Protect existing, appurtenances, structures, which are not to be demolished.
DEMOLITION
0241 00-3
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/10b71 b4d-491 b-41cc-945b-
712ca4c2722c/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/02 41 00 Demolition.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
B. Prior to demolition work, all soil erosion control measures specified in Section 01 57
23 - Stormwater Pollution Prevention Plan (SWPPP) and inlet protection barriers
shall be in place. Contractor shall provide appropriate measures to prohibit
demolition debris and/or soil from entering any watercourse.
1. Protect all buildings, structures, utilities, and vegetation to remain.
3.3 DEMOLITION REQUIREMENTS
A. Conduct demolition to protect and minimize damage to structures and existing
improvements.
B. Conduct salvaging to protect and minimize damage to salvaged equipment.
C. All work within a Caltrans right of way shall conform to Section 15 of the State
Standard Specifications.
D. Execute the work in a careful, orderly and safe manner, with the least possible
disturbance to the public. Cease operations immediately if adjacent work appears
to be endangered. Do not resume operations until corrective measures have been
taken.
E. Pavement and Slabs:
1. Remove completely all Portland cement concrete slabs-on-grade including,
but not limited to, curbs and footings. If approved by the Engineer, the
Contractor may crush Portland concrete for use as aggregate base.
2. Saw cut existing concrete curbs cleanly in straight continuous lines. Remove
concrete as shown on the drawings.
3. Any material thus processed shall conform to the specifications for Section
32 11 23 —Aggregate Base.
3.4 ORDER OF WORK
A. Existing facilities shall remain in operation until the new well is in operation.
Coordination will be required with the Owner for temporary shut-off of existing well
for connection of new pipeline to existing pipelines and new chlorination connection.
Contractor shall submit plans to Owner for approval for shut-off duration at least 10
days prior to shut-off.
1. Hours and duration of shut-off will be limited to a maximum of 4 hours in any
single day.
3.5 PRESERVATION
A. If indicated or required, preserve trees, plants, rock outcroppings, or other features
designated to remain. Protect trees and plants from damage; fell trees in a manner
which shall not injure standing trees, plants and improvements which are to be
preserved.
DEMOLITION
0241 00-4
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/10b71 b4d-491 b-41cc-945b-
712ca4c2722c/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/02 41 00 Demolition.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3.6 RESTORATION
A. All demolition areas, staging/stockpiling, and open excavations shall be filled in
accordance with the Earthwork Sections. Fill all open excavations deeper than one
foot to an elevation to match the surrounding topography.
1. New Construction Areas: As shown on drawings.
3.7 DISPOSAL
A. As specified in Section 01 50 00 —Temporary Facilities.
END SECTION
DEMOLITION
0241 00-5
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/10b71 b4d-491 b-41 cc-945b-
712ca4c2722c/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/02 41 00 Demolition.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
This Page is Intentionally Left Blank
DEMOLITION
0241 00-6
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/10b71 b4d-491 b-41cc-945b-
712ca4c2722c/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/02 41 00 Demolition.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 03 30 00
CAST-IN-PLACE CONCRETE (SITE WORK)
PART 1 GENERAL
1.1 WORK INCLUDED
A. Work required under this section consists of furnishing all materials, supplies,
equipment, tools, transportation, and facilities, and performing all labor and services
incidental to furnishing and installing concrete work as described in this section of
the Specifications, shown on the accompanying Plans, or reasonably implied
therefrom, except as hereinafter specifically excluded. The work shall include, but
is not necessarily limited to:
1. All form work including special forms as required for any special construction
and/or to accommodate the work of others and removal of forms.
2. All concrete reinforcement, placement, bending and forming thereof.
3. All concrete and cement finishing, all surface treatment and curing including
non-slip finishes.
B. Where prior inspection and test of materials are required, documentary evidence, in
the form of test reports, shall be furnished prior to the time the material is
incorporated into the work. All rejected material shall be promptly removed from the
premises.
1.2 RELATED WORK
A. Division 3 — Concrete
B. Section 05 05 20 — Bolts, Washers, Anchors and Eyebolts
C. Section 09 90 00 — Painting and Coating
D. Division 31 — Earthwork
E. Division 32 — Exterior Improvements
F. Division 33 — Utilities
1.3 REFERENCES
A. American Concrete Institute (ACI)
B. American Society for Testing and Materials (ASTM)
C. State Standard Specifications
D. California Building Code (CBC)
CAST-IN-PLACE CONCRETE (SITE WORK)
03 30 00-1
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/fd4a6d8f-dc67-4e31-b0ec-
8c5405f952ce/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/03 30 00 Cast-In-Place Concrete(Site Work).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1.4 DEFECTIVE WORK
A. Work considered to be defective may be ordered by the Engineer to be replaced in
which case the Contractor shall remove and replace the defective work at his
expense. Work considered to be defective shall include, but not be limited to, the
following:
1. Concrete incorrectly formed, or not conforming to details and dimensions on
the Plans or with the intent of these documents or concrete the surfaces of
which are out of plumb or level.
2. Concrete in which defective or inadequate reinforcing steel has been placed.
3. Concrete containing wood, cloth, or other foreign matter, rock pockets, voids,
honeycombs, cracks or cold joints not scheduled or indicated on the Plans.
4. Concrete below specified strength.
1.5 SUBMITTALS
A. Submittals shall be in accordance with Section 01 33 00 of these Specifications.
B. Provide material certificates, mix designs including laboratory testing, shop
fabrication and placement drawings, and schedule for all reinforcing steel,
embedded items, form release and curing compounds.
C. The Contractor shall provide a proposed concrete placement plan (to minimize the
effects of cracking and differential settlement) to the Engineer, and gain approval of
said plan, prior to ordering of reinforcing steel. As a minimum this plan shall contain
the layout of horizontal and vertical construction joints, spaced no greater than 50
feet apart (unless specifically approved otherwise by the Engineer), and a pour
schedule for the individual slab and wall pours. All construction joints shall be sized
in conformance with the Typical Longitudinal Keys Detail and shall contain water
stops as shown on the Construction Joint with Waterstop Detail.
PART 2 PRODUCTS
2.1 CONCRETE
A. Concrete shall conform to Section 90 of the State Standard Specifications. Unless
otherwise shown on the concrete note sheet or specified in other sections, all
concrete shall conform to the following table of Portland cement mix requirements
and minimum 28-day compressive strength. Portland cement shall be Type II.
Location Mx Requirements
Paving, Exterior Slabs, and Sidewalks Exposed 3,500 PSI, F1, SO, W1, C1
to Freezing (W/C Max 0.55)
Paving, Exterior Slabs, and Sidewalks 2,500 PSI, F0, SO, W1, C1
Structural Footings and Interior Slabs 3,000 PSI, F0, SO, W1, C1
CAST-IN-PLACE CONCRETE (SITE WORK)
03 30 00-2
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/fd4a6d8f-dc67-4e31-b0ec-
8c5405f952ce/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/03 30 00 Cast-In-Place Concrete(Site Work).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
All Other Structural Concrete 4,000 PSI, FO, SO, WO, CO
1. Water/cement ratio shall not exceed 0.45 (by weight).
2. Slump at placement shall be 4 inches +/- 1 inch.
B. Concrete used for thrust blocks or for pipe encasement shall contain not less than
517 pounds of Type II Portland Cement per cubic yard of concrete (5 1/2 sack) with
a slump of 4 inches +/- 1 inch.
C. Slurry cement backfill used in lieu of compacted soil shall contain not less than 188-
pounds of Type II Portland Cement per cubic yard of concrete (2 sack) and shall
comply with Section 19-3.02E of the State Standard Specifications.
2.2 AGGREGATE
A. Aggregate for normal weight concrete shall conform to Section 90-1.02C,
"Aggregates" of the State Standard Specifications. Aggregates shall be free of dirt,
clay balls, roots, bark and other deleterious substances and shall be thoroughly
washed before use.
B. The combined aggregates for concrete shall conform to the grading limits for the
one-inch, maximum size specified in Section 90-1.02C(4)(d), "Aggregate Gradation"
of the State Standard Specifications, Combined Aggregate Gradings.
2.3 WA TER
A. Water shall comply with Section 90-1.02D, "Water" of the State Standard
Specifications, and shall be clean and free from injurious amounts of acids, alkalis,
salts, oils, organic materials or other deleterious substances.
2.4 FLYASH
A. Fly Ash: Shall comply with SSS Section 90-1.02B(3), "Supplementary Cementitious
Materials", and shall comply with AASHTO M 295, Class F or N.
1. Type of fly ash shall be compatible with the type of cement and the intended
use of the concrete.
B. The combined weight of fly ash conforming to AASHTO M 295, Class F or N shall
not exceed the amount provided for in Section 90-1.02B(3), "Supplementary
Cementitious Materials" of the State Standard Specifications.
2.5 ADMIXTURES
A. Admixtures shall comply with Section 90-1.02E, "Admixtures", of the State Standard
Specifications
B. Air Entraining: ASTM C260
CAST-IN-PLACE CONCRETE (SITE WORK)
03 30 00-3
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/fd4a6d8f-dc67-4e31-b0ec-
8c5405f952ce/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/03 30 00 Cast-In-Place Concrete(Site Work).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
C. Water Reducing: ASTM C494, Type A, D or F
D. Accelerating: ASTM C494, Type C or E
1. No admixture containing any chloride ions is acceptable.
E. Retarding: ASTM C494, Type B, D or G
2.6 REINFORCING STEEL
A. Rebar shall be ASTM A615, Grade 60.
B. Welded wire fabric shall conform to ASTM A1064.
2.7 EXPOSED-TO-VIEW CONCRETE
A. For exposed-to-view concrete, where legs of metal supports are in contact with
forms, provide supports with legs which are plastic protected (CRSI, Class 1).
B. Metal bar supports in slab covers for sewage-containing structures shall also be
provided with plastic coated legs.
2.8 FORM MATERIALS
A. Exposed Concrete: Plywood complying with U.S. Plywood Standard PS-1 "BB
(Concrete Form) Plywood" Class I, or better.
B. Textured Finish Concrete: Units of face design, size arrangement and configuration
to match control sample.
C. Cylindrical Columns and Supports: Metal, fiberglass or waxed paper tubes of
sufficient wall thickness to resist imposed loads without deformation.
D. Form Release Agent shall leave behind a paintable concrete surface.
1. Release #1, The Burke Co., or Engineer approved equivalent.
2.9 CURING MATERIALS
A. Polyethylene film
B. Reinforced waterproof paper
1. Sisal Kraft, Orange Label, or approved equal.
C. Liquid-membrane curing compound
1. Curing compound shall comply with ASTM C309, Type 2.
a. White pigmented material
CAST-IN-PLACE CONCRETE (SITE WORK)
03 30 00-4
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/fd4a6d8f-dc67-4e31-b0ec-
8c5405f952ce/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/03 30 00 Cast-In-Place Concrete(Site Work).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
b. Clear pigment may be used for concrete that will be exposed to public
view.
2.10 WATERS TOP
A. Comply with the provisions of Section 03 15 00 —Concrete Accessories.
PART 3 EXECUTION
3.1 REINFORCING STEEL
A. Comply with CRSI, "Placing Reinforcing Bars" and as specified herein.
B. Place reinforcing steel and embedded items in accordance with approved shop
drawings.
C. Splicing of bars shall be by lapping. Lapped splices shall be 50 bar diameters for
bar size through #6 and 62 bar diameters for larger bars, unless otherwise shown
on the Plans.
D. Splicing of the wire fabric shall be by lapping. Lapped splices shall be two full mesh,
minimum.
E. All rebar in vertical walls shall be supported by concrete block spacers or metal
chairs.
F. Prior to placement of the concrete, reinforcing steel shall be cleaned and free of all
concrete, dirt, oil, mill scale, rust or other coatings that would reduce or destroy the
bond.
G. All reinforcing steel and embedded items shall be reviewed and approved by the
Engineer prior to concrete placement.
3.2 FORMS
A. All forms shall be cleaned and an approved agent applied each time they are used
and shall be so constructed and set as to resist, without springing or settlement, the
pressure of the concrete and the placing operations.
B. In designing forms and falsework, the concrete shall be treated as a liquid weighing
at least 150 lbs. per cubic foot for vertical loads and not less than 85 lbs. per cubic
foot for horizontal pressure. The design of the forms and falsework system shall
include allowances for temporary construction loads. The rate of placement of
concrete shall be so regulated that the pressures caused by the wet concrete will
not exceed the designed form pressure. The unsupported length of wooden
columns and compression members shall not exceed 30 times the width of the least
side.
C. All forms shall be set and maintained in true alignment, grade and section until the
concrete has sufficiently set. The interior surfaces of forms shall be adequately
treated with an acceptable material to insure non-adhesion of mortar. All forms shall
CAST-IN-PLACE CONCRETE (SITE WORK)
03 30 00-5
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/fd4a6d8f-dc67-4e31-b0ec-
8c5405f952ce/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/03 30 00 Cast-In-Place Concrete(Site Work).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
be mortar-tight. When forms appear to be unsatisfactory in any way, concrete
placement shall be stopped until the defects have been corrected.
D. All exposed outside corners, including the top edges of all walls, machinery bases
and curbs shall have a 3/4-inch chamfer.
E. Metal tie rods or anchorages within the forms shall be fitted with suitable cones or
comparable devices. Metal tie rods or anchorages shall be removed to a depth of
1" from the surface without injury to the concrete. All fittings for metal ties shall be
of such design that upon their removal, the cavities which are left will be of the
smallest possible size, but of sufficient diameter to allow the cavity to be "dry
packed" with cement mortar. The cavities shall be filled with cement mortar and the
surface left sound, smooth and even.
F. Form release agent shall be applied to the form so that no agent comes in contact
with reinforcing steel.
3.3 PLACING
A. All concrete shall be placed before it has taken its initial set and shall be placed in
horizontal layers and in such a manner as to avoid segregation. The concrete
adjacent to the forms and joints shall be thoroughly consolidated with a vibrator
operating at not less than 4,500 vibrations per minute.
1. Pumping equipment shall be of suitable type, without Y-sections, and with
adequate pumping capacity.
2. Loss of slump in pumping shall not exceed V/2".
3. Concrete shall not be placed through reinforcing that may cause separation
of aggregates.
B. The concrete shall be deposited as nearly as possible in its final position. Drop
chutes and elephant trunks shall be used on drops greater than 5 feet. Concrete
shall be placed at such a rate that all concrete in the same lift will be deposited on
plastic concrete. The concrete comprising each unit of work shall be placed in a
continuous lift.
C. The Contractor shall notify the Engineer 24 hours (1 working day) prior to concrete
placement.
1. The form work and reinforcing steel placement shall be approved by the
Engineer prior to ordering concrete.
D. Form Removal. Minimum times for removal after concrete placement are as follows:
Beam sides but not shoring 3 days
Column forms and wall forms 2 days
Forms for supported slabs but not shoring 14 days
CAST-IN-PLACE CONCRETE (SITE WORK)
03 30 00-6
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/fd4a6d8f-dc67-4e31-b0ec-
8c5405f952ce/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/03 30 00 Cast-In-Place Concrete(Site Work).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
E. Construction Joints
1. At ends of the first concrete pour, provide forms that positively locate any
waterstop. Ensure the end forms of walls are removable without releasing the
side forms. Provide seals around reinforcement and water stop to prevent
mortar leaks.
2. Overlap the hardened concrete of the first pour with forms for the second
pour. Brace the ends of the forms against the hardened concrete to prevent
joint offsets and mortar leakage. Align any exterior features required on the
finished surface.
3.4 CONCRETE JOINTS
A. General
1. Provide joints:
a. As shown on the Drawings and as noted below in these Specifications.
b. As required for constructability
C. After favorable review of layout, sequence and concrete placement
program.
2. Provide minimum curing times before the second placement:
a. 2 days after the first concrete placement at the joint.
b. 10 days after each adjacent concrete placement, for infill pours or
checkerboard placement pattern.
B. Control Joints:
1. Space typical control joints in slabs on grade or suspended slabs not
exceeding 10 feet, or as shown on the Drawings. Control joints shall not be
provided in water containment structures.
2. If cast-in with the concrete, positively locate the preformed joint filler and hold
rigidly in place during concreting.
3. If saw-cut, use a wheeled power saw as soon as the concrete surface is firm
enough. Saw-cut control joints must be constructed within 8-hours after
concrete placement. Fill the groove with sealant over a backer rod.
C. Construction Joints:
1. Produce quality concrete, with full continuity of reinforcing and water
tightness across the joints.
2. Space typical slab joints not exceeding 20 feet in the direction of the
transverse or secondary reinforcing, typically the smaller reinforcing nearer
CAST-IN-PLACE CONCRETE (SITE WORK)
03 30 00-7
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/fd4a6d8f-dc67-4e31-b0ec-
8c5405f952ce/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/03 30 00 Cast-In-Place Concrete(Site Work).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
to the center of the slab thickness. Space typical vertical wall joints no more
than 30 feet apart.
3. Provide all joints in walls and slabs, retaining liquids, or earth with 6-inch
waterstops. Continue all reinforcing through the joint unless otherwise noted.
4. After the first concrete placement at the joint, do not walk on or disturb any
reinforcing extending into the second placement area for at least 48 hours.
5. Before depositing new concrete on or against concrete that has hardened,
clean and roughen the entire surface of the joint exposing clean coarse
aggregate solidly embedded in mortar matrix. Provide typically 1/4-inch
roughness or amplitude of the concrete surface measured from the top of the
exposed aggregate to the bottom of pockets between stones.
6. Drench the prepared joint with clean water and remove prior to the concrete
pour.
7. Cover horizontal wall joints and wall-to-slab joints with a minimum thickness
of 2 inches and a maximum of 6 inches of the modified concrete mix,
consisting of the designated concrete mix with one-half of the coarse
aggregate removed.
8. Use special care in vibrating adjacent to construction joints to ensure
thorough consolidation of the concrete around the waterstops and against the
hardened portion of the joint. Additional hand tamping may be required.
9. For joints that are shown on architectural drawings as having a continuous
reveal or recess, leave the wood form or pour strip used to create the reveal
or recess in place or re-insert before roughening. Prevent the next concrete
placement from filling the reveal or recess.
D. Expansion Joints
1. Stop all steel reinforcing clear of the joint at each side.
2. Provide 9-inch center bulb waterstop continuously around the joint in walls
and slabs retaining liquids.
3. Prepare a smooth first concrete surface with all voids filled.
4. Provide preformed joint filler, securely fastened to the existing concrete as
directed by the Manufacturer.
5. Install bond breaker and sealant after curing is completed and when directed.
E. Bonding to Pre-existing Concrete: Mechanically roughen the old surface to a 1/4-
inch amplitude, as defined in construction joint paragraph above. Apply epoxy
bonding material prior to concreting, as recommended by the manufacturer.
F. Waterstop
CAST-IN-PLACE CONCRETE (SITE WORK)
03 30 00-8
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/fd4a6d8f-dc67-4e31-b0ec-
8c5405f952ce/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/03 30 00 Cast-In-Place Concrete(Site Work).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1. Restrict field splices to butt joints in straight runs. For PVC type, make by heat
welding, using a splicing iron. For rubber, provide sleeve joints and glue.
Follow the manufacturer's specifications.
2. Positively locate and support in the forms so that concrete may be placed,
consolidated, and vibrated on both sides of the embedded portion without
displacement of the waterstop and without causing voids in the concrete.
Protect the outstanding portion from damage during the first concrete pour
and clean and positively support prior to the second pour. Place, consolidate
and vibrate the second pour without displacement of the waterstop and
without causing voids in the concrete.
3.5 CONCRETE CURING
A. Exposed concrete surfaces shall be protected from premature drying by covering as
soon as possible with canvas, plastic sheets with sealed joints, burlap, sand or other
satisfactory materials and kept continuously moist; or, if the surfaces are not
covered, they shall be kept continuously moist by flushing or sprinkling.
1. Curing shall continue for a period of not less than 7 days after placing the
concrete. If curing compound is used, two (2) applications will be made for
even coverage. Curing methods must be approved by the Engineer.
3.6 FINISHING
A. Defective and honeycombed surfaces shall be chipped back to such a depth to
expose solid concrete. The surface shall be dampened and coated with a bonding
agent and packed with mortar.
B. Concrete Finishes for Vertical Wall Surfaces:
1. Form facing material shall produce a smooth, hard, uniform texture.
a. Use forms specified for surfaces exposed to view in accordance with
the Plans and other Specification Sections.
2. At a minimum, repair the following surface defects:
a. Tie holes
b. Honeycombs deeper than
C. Air pockets deeper than
d. Rock holes deeper than
e. Scabbing
3. Chip or rub off fins exceeding 1/8" in height.
4. Provide SF/ESF 3.0 finish and a smooth-rubbed finish for:
CAST-IN-PLACE CONCRETE (SITE WORK)
03 30 00-9
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/fd4a6d8f-dc67-4e31-b0ec-
8c5405f952ce/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/03 30 00 Cast-In-Place Concrete(Site Work).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
a. Walls being waterproofed, painted, coated with some other material.
b. Use at all exposed surfaces not specified to receive another finish.
C. Related Uniform Surfaces (Except Slabs):
1. Strike smooth tops of walls or buttresses, horizontal offsets, and similar
unformed surfaces occurring adjacent to formed surfaces after concrete is
placed.
2. Float surface to a texture consistent with that of formed surfaces.
3. Continue treatment uniformly across unformed surfaces.
D. Concrete Finishes for Horizontal Slab Surfaces:
1. General: Tamp concrete to force coarse aggregate down from surface.
Screed with straightedge, eliminate high and low places, bring surface to
required finish elevations; slope uniformly to drains. Dusting of surface with
dry cement or sand during finishing processes not permitted.
2. Slab Finish shall be as follows:
a. Surfaces intended to receive damp proofing or water proofing
membranes: Float finish.
b. Floors intended to receive floor coverings and MCC rooms: Trowel
finish.
c. Sidewalks, garage floors, drive-throughs and ramps: Broom finish.
d. Exterior slabs, platforms, steps and landings, exterior and interior
pedestrian ramps and interior stairs and all process equipment areas,
not covered by other finish materials: Broom finish.
3. Deviation in finish surface shall not exceed 1/4" in 10 ft.
4. No tolerance will be allowed that will result in the maximum running, or cross,
slope exceeding the requirements of the Americans with Disabilities Act.
3.7 TESTING
A. Testing of concrete shall be as required by the Engineer and in accordance with
ACI 301, Chapter 1.6.
1. All costs of initial testing will be paid by the Owner unless otherwise noted.
2. All costs involved, including those required by the Engineer, in retesting of
concrete required because of a failure to meet these Specifications shall be
at the expense of the Contractor.
CAST-IN-PLACE CONCRETE (SITE WORK)
03 30 00-10
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/fd4a6d8f-dc67-4e31-b0ec-
8c5405f952ce/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/03 30 00 Cast-In-Place Concrete(Site Work).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3.8 WATERTIGHTNESS OF CONCRETE WORK
A. It is the intent of this Specification to obtain concrete and grout with homogenous
structure, which when hardened will have the required strength, is watertight, and
resistance to weathering.
3.9 HYDRAULIC TESTING OF STRUCTURES
A. It is the intent of this Specification to obtain concrete and grout with homogenous
structure, which when hardened will have the required strength, watertightness, and
resistance to weathering.
B. General: Test all concrete tanks, hydraulic channels, sumps, basins and other
structures designed to contain water, after concrete has reached the design
strength, prior to backfilling, and application of any coating system. Test shall be
performed by filling the structure with water.
C. Preparation: Provide the following.
1. All water necessary for testing shall be of acceptable Quality.
2. All evaporation and level measuring devices required.
3. All pumps, power, piping and any other equipment required. Make all hook-
ups necessary to fill tanks for testing.
4. The water disposal method after testing is complete, including pumping if
necessary.
5. Fill the structure with water to the extreme high operating surface level or to
overflow weir level. Furnish and install temporary bulkheads, if required.
6. Maintain full for 48 hours before beginning the test period to permit concrete
absorption and adjustment of valves, slide gates, or temporary bulkheads.
7. At completion of tests remove all temporary piping and connections. Dispose
of wastewater without creating a nuisance of damage to adjacent property.
D. Test Period: Five consecutive 24-hour periods totaling 5 consecutive days. Take
daily measurements of air and water temperature, rainfall and water level.
E. Test Procedure
1. After test period, measure water level at each side of the tank to determine
leakage and loss from evaporation.
2. Determine evaporation loss, using a standard 48-inch evaporation pan and
level measuring device located adjacent to the tank.
3. Mark all observed damp areas, running or dripping leaks on exposed surfaces
that have not healed autogenously during the test. Damp areas include areas
CAST-IN-PLACE CONCRETE (SITE WORK)
03 30 00-11
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/fd4a6d8f-dc67-4e31-b0ec-
8c5405f952ce/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/03 30 00 Cast-In-Place Concrete(Site Work).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
if moisture can be transferred from the exterior surface to a dry hand. Repair
all those areas.
4. If leakage from the structure exceeds that permitted for the types of
mechanical equipment providing closure plus 0.075% of the storage capacity,
in each 24-hour period over a period of five consecutive days, perform a
retest after completing repairs.
5. Provide acceptable procedures prior to repairs. Repairs by painting or surface
treatment will not be acceptable.
6. Continue the test and repair procedure until the structure satisfies both the
leakage calculation requirement and the visible leakage requirement.
F. Test for Manholes
1. Furnish and dispose of water used for testing.
2. Hydraulically test all manholes installed.
3. After all pipe has been laid, backfilling has been completed, and after the
testing of the pipes, plug the end of the pipe stubs in each manhole with
flexible-joint caps, or acceptable alternate, securely fastened.
4. Fill the manhole with water and measure leakage over a period of not less
than one hour.
5. Allowable Leakage: less than one (1) gallon per hour per 10-foot depth of
manhole.
6. When leakage from the manhole exceeds the above amount, determine the
source or sources of the leakage, and repair or replace defective
materials and workmanship.
7. Repair all visible leaks even if manhole passes the leakage test.
END SECTION
CAST-IN-PLACE CONCRETE (SITE WORK)
03 30 00-12
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/fd4a6d8f-dc67-4e31-b0ec-
8c5405f952ce/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/03 30 00 Cast-In-Place Concrete(Site Work).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
CAST-IN-PLACE CONCRETE (SITE WORK)
03 30 00-13
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/fd4a6d8f-dc67-4e31-b0ec-
8c5405f952ce/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/03 30 00 Cast-In-Place Concrete(Site Work).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 05 05 20
BOLTS, WASHERS, ANCHORS AND EYEBOLTS
PART 1 GENERAL
1.1 WORK INCLUDED
A. This section describes materials and installation of anchor bolts, connecting bolts,
washers, drilled anchors, epoxy anchors, screw anchors, eyebolts, and stainless
steel fasteners.
1.2 DESIGN CRITERIA
A. Structural Connections: AISC Specification for Structural Steel Buildings (June 22,
2010), except connection details are shown in the Drawings.
1.3 REFERENCES
A. American Institute of Steel Construction (AISC)
B. American Society for Testing and Materials (ASTM)
C. Research Council on Structural Connections (RCSC)
1.4 SUBMITTALS
A. Submit shop drawings in accordance with Section 01 33 00 — Submittals.
B. Submit manufacturer's catalog data and ICC Evaluation Service Reports for bolts,
washers, and concrete anchors. Show dimensions and reference materials of
construction by ASTM designation and grade.
C. Submit anchor bolt layout drawings.
PART 2 PRODUCTS
2.1 GENERAL
A. Anchor bolts, drilled anchors, and epoxy anchors for buried service, immersion
service and in splash zones shall be stainless steel. All other anchor bolts, drilled
anchors and epoxy anchors shall be galvanized steel unless otherwise specified on
the Plans.
2.2 ANCHOR BOLTS
A. Steel anchor bolts shall conform to ASTM F1554, Grade 36, Class 1A or 2A unless
otherwise indicated. Size, length and thread length shall be as shown on the
Drawings.
BOLTS, WASHERS, ANCHORS AND EYEBOLTS
05 05 20-1
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/56659 b97-7e3 b-4f3a-a784-
fcffaf1432b1/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/05 05 20 Bolts,Washers,Anchors and Eyebolts_v2.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
B. Bolts shall be provided with a head and two washers of a minimum of inch thick
and 2 inches square. One washer shall be embedded in the concrete at the head
of the bolt.
C. Anchor bolts, nuts and washers shall be galvanized per ASTM F2329.
2.3 CONNECTION BOLTS
A. Steel connection bolts shall conform to ASTM A325, Type 1 with the threads
included in the shear plane.
B. Provide galvanized bolts where shown in Drawings. Galvanizing of bolts, nuts, and
washers shall be in accordance with ASTM F2329.
2.4 STAINLESS STEEL BOLTS
A. Stainless steel bolts shall be ASTM A193, Grade B8 or ASTM F593, Type 316. Nuts
shall be ASTM A194, Grade 316 or ASTM F594, Type 316. Use ASTM A194 nuts
with ASTM A193 bolts; use ASTM F594 nuts with ASTM F593 bolts. Provide washer
for each nut and bolthead. Washers shall be of the same material as the nuts.
2.5 LUBRICANT FOR STAINLESS STEEL BOLTS AND NUTS
A. Lubricant shall be chloride free and shall be RAMCO TG-50, Anti-Seize by RAMCO,
HuskeyTm Lube-O-Seal by HUSK-ITT Corporation, or equal.
2.6 WASHERS
A. Washers for bolts conforming to ASTM F1554 shall conform to ASTM F436, Type
1.
B. Washers for bolts conforming to ASTM A307 shall conform to ASTM F844.
C. Washers for bolts conforming to ASTM A325 shall be square or rectangular, tapered
in thickness, smooth, hot-dipped galvanized, conforming to ASTM F436.
D. Stainless steel washers shall be Type 316.
2.7 DRILLED ANCHORS
A. Unless otherwise indicated in the Drawings, drilled anchors shall be 316 stainless
steel wedge anchors as manufactured by ITW Red Head Trubolt+, Kwik Bolt TZ by
Hilti, or equal. Anchors shall have ICC-approved testing.
2.8 EPDXYANCHORS
A. Epoxy anchors in concrete shall be 316 stainless steel threaded rod adhesive
anchors. Adhesive shall be ITW Red Head Epcon S7, Hilti HIT RE 500-SD, or equal.
Epoxy anchor assemblies shall be ICC approved.
B. Epoxy anchors in grouted concrete masonry walls shall be 316 stainless threaded
rods. Epoxy adhesive shall be Hilti HIT HY 70, Simpson ET-HP, or equal.
BOLTS, WASHERS, ANCHORS AND EYEBOLTS
05 05 20-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/56659 b97-7e3 b-4f3a-a784-
fcffaf1432b1/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/05 05 20 Bolts,Washers,Anchors and Eyebolts_v2.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
PART 3 EXECUTION
3.1 STORAGE OF MATERIALS
A. Store material, either plain or fabricated, above ground on platforms, skids, or other
supports. Keep material free from dirt, grease, and other foreign matter and protect
from corrosion.
3.2 GALVANIZING
A. Zinc coating for bolts, anchor bolts, and threaded parts shall be in accordance with
ASTM F2329.
3.3 INSTALLING CONNECTION BOLTS
A. Use steel bolts to connect structural steel members. Use stainless steel bolts to
connect structural aluminum members.
B. Install ASTM A325 bolts and washers per the RCSC "Specification for Structural
Joints Using High Strength Bolts".
C. Bolt holes in structural members shall be 1/16 inch in diameter larger than bolt size.
Measure cast-in-place bolt locations in the field before drilling companion holes in
structural steel beam or assembly.
D. Slotted holes, if required in the Drawings, shall conform to AISC 360-10, Chapter J,
Section J3, Table J3.3.
E. Drive bolts accurately into the holes without damaging the thread. Protect boltheads
from damage during driving. Boltheads and nuts or washers shall rest squarely
against the metal. Where bolts are to be used on beveled surfaces having slopes
greater than 1 in 20 with a plane normal to the bolt axis, provide beveled washers
to give full bearing to the head or nut. Where self-locking nuts are not furnished, bolt
threads shall be upset to prevent the nuts from backing off.
F. Bolts shall be of the length that will extend entirely through but not more than 1/4
inch beyond the nuts. Draw boltheads and nuts tight against the work.
3.4 INSTALLATION OF STAINLESS STEEL BOLTS AND NUTS
A. Prior to assembly, coat threaded portions of stainless steel bolts and nuts with
lubricant.
3.5 INSTALLING ANCHOR BOLTS
A. Anchor bolts shall be delivered in time to permit setting before the structural concrete
is placed. Anchor bolts which are cast in place in concrete shall be provided with
sufficient threads to permit a nut to be installed on the concrete side of the concrete
form or supporting template.
B. Preset bolts and anchors by the use of templates. Do not use concrete anchors set
in holes drilled in the concrete after the concrete is placed for mechanical equipment.
BOLTS, WASHERS, ANCHORS AND EYEBOLTS
05 05 20-3
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/56659 b97-7e3 b-4f3a-a784-
fcffaf1432b1/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/05 05 20 Bolts,Washers,Anchors and Eyebolts_v2.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
Anchor bolts and threaded rod anchors which are to be epoxy grouted shall be clean
and free of coatings that would weaken the bond with epoxy.
C. Two nuts, a jam nut, and a washer shall be furnished for anchor bolts and threaded
rod anchors indicated on the drawings to have locknuts; two nuts and a washer shall
be furnished for all other anchor bolts.
D. Anti-seize thread lubricant shall be liberally applied to projecting, threaded portions
of stainless steel anchor bolts and threaded rod anchors immediately before final
installation and tightening of the nuts.
E. For static items such as storage tanks, use preset anchor bolts or drilled anchors
with ICC report data.
F. After anchor bolts have been embedded, protect projecting threads by applying
grease and having the nuts installed until the time of installation of the equipment or
metalwork.
3.6 INSTALLING DRILLED ANCHORS
A. Minimum depth of embedment of drilled mechanical anchors shall be as
recommended by the manufacturer, but no less than that shown in the Drawings.
B. Prepare holes for drilled anchors in accordance with the anchor manufacturer's
recommendations prior to installation.
3.7 INSTALLING EXPDXYANCHORS
A. Epoxy anchors shall be clean and free of coatings that would weaken the bond with
epoxy.
B. Minimum depth of embedment of epoxy anchors shall be as recommended by the
manufacturer, but no less than that shown in the Drawings.
C. Prepare holes for epoxy anchors in accordance with the anchor manufacturer's
recommendations prior to installation.
END SECTION
BOLTS, WASHERS, ANCHORS AND EYEBOLTS
05 05 20-4
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/56659 b97-7e3 b-4f3a-a784-
fcffaf1432b1/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/05 05 20 Bolts,Washers,Anchors and Eyebolts_v2.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 09 90 00
PAINTING AND COATING (SITE)
PART 1 GENERAL
1.1 WORK INCLUDED
A. Field painting including surface preparation, surface protection, clean up, and/or
other appurtenant work.
B. All labor, materials, tools and equipment, and incidentals necessary and required
for their completion.
C. All pipe, fittings, equipment, and structures are to be field coated except for those
specific exceptions contained in this specification or identified on the drawings. The
painting schedule included at the end of this specification summarizes the surfaces
to be coated, the required surface preparation, and the coating systems to be
applied. Coating notes on the drawings are used to show exceptions to the
schedules, to extend the limits of coating systems, or to clarify or show details for
application of the coating systems.
D. All coatings for potable water service shall be ANSI-NSF Standard 61 certified.
1.2 RELATED WORK
A. Section 03 30 00 — Cast-in-Place concrete
1.3 SUBMITTALS
A. Submittals shall be in accordance with Section 01 33 00 — Submittals.
1. Product technical data including:
a. Acknowledgement that products submitted meet requirements of
standards referenced.
b. Performance criteria as required by the Engineer to determine quality.
C. Manufacturer's installation instructions and environmental parameters.
d. Material Safety Data Sheets.
e. Color samples.
1.4 AIR QUALITY REGULATORY COMPLIANCE
A. All paint shall conform to the applicable air quality regulations at the point of
application. Any paint material which cannot be guaranteed by the manufacturer to
comply, whether specified by product designation or not, shall not be used.
PAINTING AND COATING (SITE)
09 90 00-1
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bf85d ee6-5614-4278-9d 22-
17abf8cec732/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 90 00 Painting and Coating(Site).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
B. The volatile organic compound (VOC) of coatings materials limits set forth in Rule
460.1 of the San Joaquin Valley Unified Air Pollution Control District shall apply to
this project. The manufacturers' products listed in paragraphs 09900-3.01 and 3.02
have been selected on the basis of their apparent compliance with Rule 460.1;
however, it shall remain the Contractor's responsibility to ensure that all coatings
materials furnished are in compliance with all regulatory agencies.
C. The product listed may meet the VOC requirement in the unthinned (as shipped)
condition, but may exceed the VOC requirement if thinned to the manufacturer's
allowable recommendations. In this situation, the product is not to be thinned
beyond the limit indicated in Rule 460.1, and if the product cannot be suitably
thinned for the intended application method or temperature requirements, it will be
necessary to use another manufacturer's product subject to acceptance by the
Engineer.
D. It shall be the responsibility of the Contractor to ensure the compatibility of the field
painting products which will be in contact with each other or which will be applied
over shop painted or previously painted surfaces. Paint used in successive field
coats shall be produced by the same manufacturer. Paint used in the first field coat
over shop or field primed surfaces, or previously painted surfaces shall cause no
wrinkling, lifting, or other damage to underlying paint.
E. All paint used for intermediate and finish coats shall be guaranteed by the paint
manufacturer to be fumeproof. Paint shall be lead-free and mercury-free.
1.5 QUALITY OF WORK
A. All finishes shall be applied by skilled workmen in accordance with the best practices
and standards of the painting trade. Brushes, rollers, all equipment, and the
techniques used in applying finishes shall be of sufficient quality to assure the
specified results. Work not conforming to this Specification shall be corrected by
touching up or refinishing as directed by the Engineer.
B. It is the purpose and intent of this Specification to cover the complete paint finishing
of all exterior and interior surfaces as scheduled or specified and all surfaces which
normally require a paint finish for corrosion resistance, weather protection, finished
appearance or utility. Finished surfaces shall be of the type of finish, color sheen
film thickness and quality specified.
1.6 DELIVERYAND STORAGE
A. Painting materials shall be delivered to site in manufacturer's original containers with
labels intact and seals unbroken. Painting materials and equipment shall be stored
and protected against freezing and mixed in rooms assigned for that purpose. No
chemicals, unauthorized thinners, or other materials, not included in the paint
formulation shall be added to the paint for any purpose. All necessary precautions
shall be taken to prevent fire. Rags or waste soiled with paint shall be removed from
premises at end of each day's work, or shall be stored in covered metal containers.
PAINTING AND COATING (SITE)
09 90 00-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bf85d ee6-5614-4278-9d 22-
17abf8cec732/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 90 00 Painting and Coating(Site).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1.7 EQUIVALENT PRODUCTS
A. Whenever a coating is specified using the name of a proprietary product or the name
of a particular manufacturer or vendor, the specified coating shall be understood as
establishing the type and quality of coating desired.
B. Other manufacturers' products will be accepted provided sufficient information is
submitted to allow the Engineer to determine that the coatings proposed are
equivalent to those named. Proposed coatings shall be submitted for review in
accordance with the Section 01 33 00 - Submittals.
C. Requests for review of equivalency will not be accepted from anyone except the
Contractor, and such requests will not be considered until after the contract has
been awarded.
D. Specific products for various applications shall be as specified in Part 2. In addition
to the products named in Part 2, equivalent products of the following manufacturers
will also be acceptable:
Ameron
Carboline
Devoe
PPG (Pittsburgh)
Sherwin Williams Co.
Sinclair
Tnemec
Valspar
E. Contractor shall provide verification that equivalent products are acceptable for the
desired application.
1.8 REFERENCE STANDARDS
A. SSPC — Society of Protective Coatings, Pittsburgh, PA
B. ASTM —American Society For Testing And Materials, West Conshohocken, PA
PART 2 PRODUCTS
2.1 GENERAL
A. All paint shall be the product of a recognized manufacturer exclusively engaged in
the manufacture of painting material. All paints for wood and metal surfaces shall
be well-ground and shall not skin, liver, curdle, or body excessively in the containers.
B. The paint shall not show laps or unevenness of color or texture. When applied to
vertical surfaces, it shall not sag.
PAINTING AND COATING (SITE)
09 90 00-3
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bf85d ee6-5614-4278-9d 22-
17abf8cec732/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 90 00 Painting and Coating(Site).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
C. All exposed surfaces, including sides and edges, shall be painted. Hangers,
brackets, fastenings and other miscellaneous items shall be painted with the same
system as the adjacent material. Paint systems shall be in addition to shop primers.
D. Paint shall be stored inside and shall be protected against freezing. No adulterant,
unauthorized thinner, or other material not included in the paint formation shall be
added to the paint for any purpose.
E. Paint used in successive field coats shall be produced by the same manufacturer.
Paint used in the first field coat over shop painted or previously painted surfaces
shall cause no wrinkling, lifting, or other damage to underlying paint. Any paint
system shall be the product of a single manufacturer.
F. All paint used for intermediate and finish coats shall be guaranteed by the paint
manufacturer to be lead-free, mercury-free, and fumeproof. Where paint materials
are referenced to Federal or military specifications, the reference shall define
general type and quality required but is not intended to limit acceptable materials to
an exact formulation.
G. For each paint, the Contractor shall follow the paint manufacturer's specific
application instructions. Upon the Engineer's request, the Contractor shall furnish
the following application instructions.
1. Surface preparation recommendations.
2. Type of primer to be used.
3. Maximum dry and wet mil thickness per coat.
4. Minimum and maximum curing times between coats.
5. Thinner to be used with each paint.
6. Ventilation requirements.
7. Atmospheric conditions during which the paint shall not be applied.
8. Allowable methods of application.
9. Maximum allowable moisture content and minimum age of plaster, concrete
and wood surfaces at time of paint application.
10. Curing time before submergence in water.
H. The minimum number of coats and minimum total dry mil thickness of the system
for each surface shall be as specified in the paint schedule.
2.2 PAINTING SCHEDULE
A. A schedule is appended to this section listing the surface preparation, primer, finish
and dry mil thickness to be used on each surface to be coated.
PAINTING AND COATING (SITE)
09 90 00-4
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bf85d ee6-5614-4278-9d 22-
17abf8cec732/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 90 00 Painting and Coating(Site).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2.3 PRIMERS AND PRETREATMENT
A. P-1 Epoxy Primer- Minimum dry thickness 4 mils. Devoe "Bar Rust 235H", Sherwin
Williams "Macropoxy 646 FC Epoxy B58-600", or Tnemec 69-1211 "Hi-Build
Expoxoline."
B. P-2 Rust Inhibitive, non-submerged - Minimum dry thickness 3 mils. Devoe "Devran
203 Waterborne Epoxy Primer", Sherwin Williams "Macropoxy 646 FC Epoxy B58-
600" or Tnemec 135 "Chem Build."
C. P-3 Rust inhibitive, submerged - Minimum dry thickness 4.0 mils. Devoe "Bar Rust
235H", Sherwin Williams "Macropoxy 646 FC Epoxy B58-600" or Tnemec 136
"Chem Build."
D. P-4 Primer for Wood — Maximum of 400 sq. ft/gal. Devoe 2010-1200 "Ultra- Hide
Durus Exterior Acrylic Primecoat", Sherwin Williams "A-100 Wood Primer B42W41"
or Tnemec 151 "Elaso-Grip."
E. P-5 Wallboard Primer — Maximum of 400 sq. ft/gal. Devoe1060-1200 "Ultra- Hide
Latex Primer- Sealer", Sherwin Williams "Preprite 200 Interior Latex Primer
B28W200", or Tnemec 51-792 "PVA Sealer."
F. P-6 High Build Acrylic— Maximum of 100 sq. ft/gal., Tnemec 180 WB Tneme-Crete,
Sherwin Williams "Heavy Duty Block Filler B42W46".
2.4 INTERMEDIATE AND FINISH PAINTS
A. F-1 Epoxy Resin - Minimum dry thickness 5 mils. Devoe "Bar Rust 235H", Sherwin
Williams "Macropoxy 646 FC Epoxy B58-600", or Tnemec 69 "Hi-Build" epoxy.
B. F-2 Gloss Acrylic Emulsion - Minimum dry thickness 2.0 mils Devoe " Devflex 4208
Waterbone Acrylic Enamel", Sherwin Williams "Shercryl Hi Performance Acrylic
Gloss B66-300", or Tnemec 1028.
C. F-3 Semi-gloss Acrylic Emulsion - Minimum dry thickness 2.5 mils Devoe "Devvflex
4216 HP Waterborne", Sherwin Williams "Shercryl Hi Performance Acrylic Semi-
Gloss B66-350", or Tnemec 1029 "Tuf Cryl".
D. F-4 High Build Epoxy (Substitute for Coal Tar) - Minimum dry thickness 6 mils.
Devoe "Devtar 5A HS", Sherwin Williams "Targuard Coal Tar Epoxy B69B60", or
Tnemec "V69F Black"
E. F-5 Polyurethane O - Minimum dry thickness 2 mils. Devoe "Devthane 379H
Aliphatic Urethane Gloss Enamel", Sherwin Williams "Hi Solids Polyurethane CA
B65j-300", or Tnemec 1075 "Endurasheild."
F. F-6 Acrylic Epoxy—Minimum dry film thickness 4 mils. Tnemec 113 Tneme-Tufcoat,
Sherwin Williams " Waterbased Tile Clad Epoxy B73-100".
G. F-7 High Build Acrylic— Maximum of 100 sq. ft./gal.Tnemec 180 WB Tneme-Crete,
Sherwin Williams "Heavy Duty Block Filler B42W46".
PAINTING AND COATING (SITE)
09 90 00-5
https://us-partner-i ntegrations.eg nyte.com/msoffice/wopi/files/bf85dee6-5614-4278-9d22-
17abf8cec732/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 90 00 Painting and Coating(Site).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2.5 FUSION BONDED EPDXY LINING AND COATING
A. Lining and coating shall be a 100%solids,thermosetting,fusion-bonded, dry powder
epoxy resin. Provide Scotchkote 134 or 206N, Lilly Powder Coatings "Pipeclad 1500
Red", or equal. Epoxy lining and coating shall meet or exceed the following
requirements:
Hardness (Minimum): Barcol 17 (ASTM D2583)
Rockwell 50 ("M" Scale)
Abrasion Resistance (Minimum) 1,000 cycles: 0.05 gram removed
5,000 cycles: 0.115 gram removed
ASTM D1044, Tabor CS 17 wheel
1,000 gram weight
Adhesion (Minimum) 3,000 psi (Elcometer)
Tensile Strength 7,300 psi (ASTM D2370)
2.6 ALUMINUM SURFACES
A. All aluminum in contact with steel or concrete: Sherwin Williams "Macropoxy 646
FC Epoxy B58-600 series or approved equivalent.
2.7 SHOP COATINGS
A. Shop coatings shall be applied as indicated in the individual equipment and
component specifications.
B. Electric motors, speed reducers, starters, and other self-contained or enclosed
components shall be shop primed or finished with a high grade, oil resistant enamel
suitable for top coating in the field with an alkyd enamel.
C. All shop coatings shall be compatible with the paint system specified in the Painting
Schedule contained at the end of this specification.
2.8 SURFACES NOT TO BE PAINTED
A. Except as otherwise required or directed, the following surfaces are to be left
unpainted:
1. Exposed surfaces of aluminum (aluminum in contact with concrete is to be
coated).
2. Polished or finished stainless steel. Unfinished stainless steel shall be
painted.
3. Nickel or chromium.
4. Galvanized surfaces, except piping, conduit, electrical conduit, pipe supports,
fasteners, hangers, bracing, brackets, and accessories.
PAINTING AND COATING (SITE)
09 90 00-6
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bf85d ee6-5614-4278-9d 22-
17abf8cec732/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 90 00 Painting and Coating(Site).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
5. Rubber and plastics, including fiberglass reinforced plastics.
6. Precast concrete.
2.9 SYSTEM IDENTIFICATION
A. Above Grade Piping: Provide markers on piping which is either exposed or
concealed in accessible spaces. For piping systems, otherthan drain and vent lines,
indicate the fluid conveyed or its abbreviation, either by preprinted marker or
stenciled marking, and include arrows to show the direction of flow. Comply with
ANSI Al3.1 for colors. Locate markers at ends of lines, near major branches and
other interruptions including equipment in the line, where lines pass through floor,
walls or ceilings or otherwise pass into inaccessible spaces, and at 50' maximum
intervals along exposed portion of lines. Marking of short branches and repetitive
branches for equipment connections is not required.
B. Equipment: All equipment shall be identified with a plastic laminated, engraved
nameplate which bears the unit mark number as indicated on the drawings (e.g. AC-
4). Provide 1/2" high lettering, white on black background. Nameplates shall be
permanently secured to the unit.
C. Valves: Provide valve tags on all valves of each piping system, excluding check
valves, valves within equipment, faucets, stops and shut-off valves at fixtures and
other repetitive terminal units. Provide brass tags or plastic laminate tags. Prepare
and submit a tagged valve schedule, listing each valve by tag number, location and
piping service. Mount in glazed frame where directed.
2.10 COLORS
A. All colors and shades of colors shall be as specifically indicated in the specifications
or plans, or, where not specifically indicated, selected from the manufacturer's
standard color samples by the Owner.
B. Electrical conduit shall be painted to match adjacent ceiling or wall surfaces as
directed by the Engineer.
PART 3 EXECUTION
3.1 PRELIMINARY EXAMINIATION
A. Notify the Engineer in writing of any uncorrected defects in surfaces to be painted.
Do not proceed with the finishing of surfaces in question until any discrepancies are
corrected. No work on any surface shall be started, unless the surface has been
inspected and approved for painting by the Engineer.
3.2 SURFACE PREPARATION
A. The Contractor shall prepare the surfaces to be coated as specified under the paint
schedule. Any surfaces to be coated which are not listed under the paint schedule
PAINTING AND COATING (SITE)
09 90 00-7
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bf85d ee6-5614-4278-9d 22-
17abf8cec732/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 90 00 Painting and Coating(Site).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
shall be prepared in accordance with the manufacturer's instructions for the material
to be applied.
B. All grease, oil, dirt, and other contaminants which may affect the bond between the
coating and the surface shall be removed by a cleaning agent which will leave the
surface clean and dry.
C. Cleaning and painting operations shall be performed in a manner which will prevent
dust or other contaminants from getting on freshly painted surfaces.
D. Surfaces shall be free of cracks, pits, projections, or other imperfections which would
prevent the formation of smooth, unbroken paint film, except for concrete block
construction where a rough surface is an inherent characteristic.
E. When applying touch-up paint, or repairing previously painted surfaces, the surfaces
to be painted shall be cleaned and sanded or wire brushed in such a manner that
the edges of adjacent paint are feathered or otherwise smoothed so that they will
not be noticeable when painted. All paint made brittle or otherwise damaged by
heat or welding shall be completely removed.
F. Hardware items such as bolts, screws, washers, springs, and grease fittings need
not be cleaned prior to painting if there is no evidence of dirt, corrosion, or foreign
material.
G. All galvanized surfaces shall have a metal conditioner applied prior to the first prime
coat.
H. All surfaces to be finished shall be clean and dry before any materials are applied.
Use a moisture meter to determine moisture content as follows. The moisture
content shall be less than 18% for wood; 8% for concrete or plaster.
1. Metal Surfaces - Where noted, the surface preparation for steel and other
metals refer to the specifications for surface preparation by the latest revision
of the Steel Structures Painting Council. All metal work shall be cleaned of
grease, oil and dirt by solvent cleaning (SSPC-SP1). Do not use hydrocarbon
based solvents for cleaning prior to use of acrylic materials.
a. Method SP-2: Surface shall be wire brushed where required to remove
loose rust and dirt, etc. (SSPC-SP2)
b. Method SP-3: Removal of loose rust, loose mill scale and other
detrimental foreign matter to degree specified by power wire brushing,
power impact tools or power sanders. (SSPC-SP3)
C. Method SP-6: Blast cleaning until at least two-thirds of each element
of surface area is free of all visible residues. (SSPC-SP6)
d. Method SP-10: Sandblast to near white condition. This method shall
remove all rust and scale, but streaks and shadows in the metal will be
acceptable. (SSPC-SP10)
2. Wood Surfaces
PAINTING AND COATING (SITE)
09 90 00-8
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bf85d ee6-5614-4278-9d 22-
17abf8cec732/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 90 00 Painting and Coating(Site).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
a. Method W-1: All unprimed millwork delivered to the jobsite shall be
given the specified first coat on all surfaces immediately upon arrival.
Give all unprimed woodwork the specified first coat as soon as
possible following installation. Prime any wood surface that is to be in
contact with concrete, or a caulking material, with the specified first
coat material before installation. Unless specified otherwise, all
casings and trim, and all woodwork shall be free of oil, dirt, loose fibers,
etc., sealed with a sanding sealer recommended by the coating
manufacturer, and sanded smooth and dusted thoroughly before
application of the priming coat. Give all knots, pitch pockets and sappy
areas a preliminary coat of Dutch Boy Knot Sealer, or approved
equivalent, prior to application of the prime coat.
3. Galvanized Surfaces
a. Method G-1: All galvanized surfaces shall be prepared for painting in
strict conformity with the instructions of the manufacturer. All
galvanized shall be cleaned per SSPC-SP7.
4. PVC Pipe
a. Method V-1: All wax and oil shall be removed from PVC plastic
surfaces by wiping with a solvent of the type used for the specified
primer.
3.3 PAINT APPLICATION
A. Apply all finishes evenly, free from sags, runs, crawls, brush marks, skips or other
defects. Apply products at the proper consistency and do not thin or otherwise alter
them except in accordance with the manufacturer's printed directions. All coats shall
be applied in such manner as to produce an even film of uniform thickness
completely coating all corners and crevices. All painting shall be done by thoroughly
experienced workmen.
B. Care shall be exercised during spraying to hold the nozzle sufficiently close to the
surfaces being painted to avoid excessive evaporation of the volatile constituents
and loss of material into the air, or the bridging over of crevices and corners. Spray
equipment shall be equipped with mechanical agitators, pressure gauges, and
pressure regulators. Nozzles shall be of proper size. Floors, roofs, and other
adjacent areas and installations shall be satisfactorily protected by drop cloths or
other precautionary measures. All over-spray shall be removed by approved
methods or the affected surface repainted. Care shall be exercised to avoid lapping
of paint on hardware of other unscheduled surfaces.
C. Each coat of material shall be thoroughly dry before the application of a succeeding
coat. In no case shall paint be applied at a rate of coverage per gallon which is
greater than the maximum rate recommended by the manufacturer. Paint films
showing sags, checks, blisters, teardrops, or fat edges will not be accepted. Paint
containing any of these defects shall be entirely removed and the surface repainted.
PAINTING AND COATING (SITE)
09 90 00-9
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bf85d ee6-5614-4278-9d 22-
17abf8cec732/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 90 00 Painting and Coating(Site).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
D. Sandpaper enamels and varnishes lightly between coats and dust thoroughly before
the application of a succeeding coat.
E. If the finish coat is to be colored, the prime coat and the intermediate coat shall be
tinted to have a slight variation in color from each other and from the finish coat.
3.4 PRIMING
A. Edges, corners, crevices, welds, and bolts shall be given a brush coat of primer
before the specified spot or touch-up painting of metal surfaces. Special attention
shall be given to filling all crevices with paint.
B. Abraded and otherwise damaged portions of shop applied paint shall be repainted.
Welded seams and other uncoated surfaces, heads and nuts of field installed bolts,
and surfaces where paint has been damaged by heat, shall be given a coat of the
specified primer. This patch, spot, or touch-up painting shall be completed, and
shall be dry and hard, before additional paint is applied.
3.5 LATEX PAINT
A. Latex paint shall be applied by brushing or rolling; spraying is not permitted. Latex
paint shall not be thinned excessively.
3.6 MIXING AND THINNING
A. Paint shall be thoroughly mixed each time any is withdrawn from the container.
Paint containers shall be kept tightly closed except while paint is being withdrawn.
B. Unless otherwise authorized, all paint shall be factory mixed to proper consistency
and viscosity for hot weather application without thinning. Thinning will be permitted
only as necessary to obtain recommended coverage at lower application
temperatures. In no case shall the wet film thickness of applied paint be reduced,
by addition of paint thinner or otherwise, below that represented by the
recommended coverage rate.
3.7 FILM THICKNESS FOR FERROUS METALS
A. It is intended that the dry film thickness and the continuity of painted ferrous metal
surfaces be subject to continual field check by the Engineer. Dry film thickness shall
be measured by the Contractor, using an approved Thickness Gauge, at locations
selected by Engineer. Testing equipment provided shall be provided by Contractor
and kept on site.
B. Measurement of Dry Coating Thickness shall conform with paint application
Standard SSPC-PA2
C. Thickness and Holiday Checking -Thickness of coatings and paint shall be checked
with a non-destructive, magnetic type thickness gauge.
D. Holiday Checking of all interior coated surfaces shall be tested with an approved
holiday detection device. Non-destructive holiday detectors shall not exceed 100
volts nor shall destructive holiday detectors exceed the voltage recommended by
PAINTING AND COATING (SITE)
09 90 00-10
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bf85d ee6-5614-4278-9d 22-
17abf8cec732/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 90 00 Painting and Coating(Site).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
the manufacturer of the coating system. For thicknesses between 10 and 20 mils
(0.25mm and 0.50mm) a non-sudsing type wetting agent such as Kodak Photo-Flo,
shall be added to the water prior to wetting the detector sponge. All pinholes shall
be marked, repaired in accordance with the manufacturer's printed
recommendations and re-tested. No pinholes or other irregularities will be permitted
in the final coating. Holiday detection devices shall be operated in the presence of
the Engineer.
E. Continuity shall be tested by a low voltage-wet sponge per RPO 188. Contractor
shall perform continuity tests as required by the Engineer on surfaces that will be
submerged.
3.8 ATMOSPHERIC CONDITIONS
A. Apply all material to dry and properly prepared surfaces when weather conditions
are favorable for painting. No materials shall be applied when the temperature of
the materials is below 50 degrees F, or when the temperature of the air, surface to
be painted or substrate, is below (or likely to fall below) 50 degrees F. Final ruling
on the favorability of weather conditions shall be in accordance with the
recommendations of the manufacturer and/or the Engineer.
B. No coating or paint shall be applied to wet or damp surfaces, in rain, snow, fog, or
mist, when the steel temperature or surrounding air temperature is less than 5
degrees above the dew point, nor in conditions not recommended by the
manufacturer
3.9 REPAIRING DAMAGED PAINT ON EQUIPMENT
A. Painted surfaces on equipment, which have become damaged prior to acceptance
by the Owner, shall be repainted with the same or equivalent paint used in the
original application.
3.10 PROTECTION OF SURFACES
A. Throughout the work the Contractor shall use drop cloths, masking tapes, and other
suitable measures to protect all surfaces from accidental spraying, splattering, or
spilling of paint. Contractor shall be liable for and shall correct and repair any
damaged condition resulting from its operations or from the operations of all those
who are responsible to the Contractor during the time its work is in progress and
until the work is accepted. In case bituminous paints are spilled or dropped on any
material except metals, the spots shall, after surface cleaning, be spot painted with
aluminum paint prior to applying the specified paint. Any exposed concrete or
masonry not specified to be painted which is damaged by paint shall be either
removed and rebuilt or, where so authorized by the Owner, painted with two coats
of masonry paint.
3.11 CLEANUP
A. All cloths and cotton waste which might constitute a fire hazard shall be placed in
metal containers or destroyed at the end of each work day. Upon completion of the
PAINTING AND COATING (SITE)
09 90 00-11
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bf85d ee6-5614-4278-9d 22-
17abf8cec732/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 90 00 Painting and Coating(Site).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
work all staging, scaffolding and containers shall be removed from the site or
destroyed in a manner approved by the Engineer.
PAINTING AND COATING (SITE)
09 90 00-12
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bf85d ee6-5614-4278-9d 22-
17abf8cec732/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 90 00 Painting and Coating(Site).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3.12 PAINTING SCHEDULE
FINISH
SURF. PRIME 2ND 3RD
SYSTEM SURFACE PREP. COAT COAT COAT
1. New ferrous metal in SP-10 P-1 F-1 F-1
submerged or damp
environment including all
submerged mechanical
components.
2. All exterior exposed new SP-2 or 3 P-2 F-2 F-2
structural and miscellane-
ous steel. All exterior
exposed surfaces of new
piping, pumps, motors,
electrical equipment and
other unsubmerged
mechanical and structural
items.
3. All surfaces of new SP-6 P-2 F-3 F-3
structural and miscellane-
ous steel pipe, pumps,
motors and electrical
equipment panels exposed
inside building.
4. All interior exposed new G-1 P-3 F-3 F-3
galvanized metalwork
including electrical conduit
inside buildings, including
fittings, boxes, supports and
accessories.
5. All exterior exposed new G-1 P-3 F-2 F-2
galvanized metalwork
including roof flashings ad
other architectural items.
6. Exposed new PVC piping V-1 F-5 F-5
PAINTING AND COATING (SITE)
09 90 00-13
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bf85d ee6-5614-4278-9d 22-
17abf8cec732/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 90 00 Painting and Coating(Site).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
7. All new buried valves and SP-10 F-4 F-4
flanged joints and other
buried miscellaneous
ferrous piping and metal
surfaces (excluding cast
iron pipe). All exterior
surfaces of new cast iron
and steel piping exposed in
manholes, wet wells and
similar locations, including
valves, fittings, flanges,
bolts, supports, and
accessories. Miscellaneous
new castings, including
manhole rings and covers
and manhole steps. (One
coat, if not foundry dipped.)
8. Interior wood P-4 F-2 F-2
9. Exterior wood P-4 F-3 F-3
10. Interior dry wall P-5 F-6
11. Exterior concrete block P-6 F-7
12. Concrete P-6 F-7
3.13 When conflicting painting specifications or requirements are encountered in the contract
documents, the more restrictive specifications or requirements shall be required.
END SECTION
PAINTING AND COATING (SITE)
09 90 00-14
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bf85d ee6-5614-4278-9d 22-
17abf8cec732/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 90 00 Painting and Coating(Site).docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 09 97 57
POLYETHYLENE TAPE PIPE COATING (AWWA C214)
PART 1 GENERAL
1.1 DESCRIPTION
A. This section describes materials, installation, and testing of a cold-applied
polyethylene pipe coating complying with AWWA C209 and C214 with a cement
mortar armor coat in accordance with AWWA C205 for pipe sizes 4 inches and
larger.
B. Supervisors of tape coating and cement mortar coating operations shall have at
least two years' continuous recent experience in the application of tape and cement-
mortar coating systems for steel pipe. The manufacturer of the tape coatings shall
demonstrate a minimum of five years' successful application of this product on large
diameter steel water pipelines.
1.2 RELATED WORK SPECIFIED ELSEWHERE
A. Section 09 90 00 — Painting and Coating
B. Section 40 05 00 — Pipe and Fittings
1.3 SUBMITTALS
A. Submit shop drawings in accordance with Section 01 33 00—Submittal Procedures.
B. Submit certificates of tests of physical and performance characteristics of each
batch of primer and tape.
C. Submit method approved by tape manufacturer to minimize voids at weld seams.
Submit method approved by tape manufacturer to minimize disbondment of free
ends of tape during shipping and storage.
D. Submit application procedure approved by tape manufacturer, including the pattern
of distribution and method of application of the weld seam tape system.
E. Submit an affidavit of compliance with the referenced standards (e.g., AWWA C209,
C214, etc.).
F. Submit schedule for application of tape coating. Schedule coating to be
accomplished during normal working hours. Provide a minimum of two weeks' notice
to the Construction Manager prior to commencing or rescheduling work.
G. Submit the names and qualifications of the workers and supervisors to be employed
on the coating operation a minimum of 14 days prior to the start of taping operations.
POLYETHYLENE TAPE PIPE COATING (AWWA C214)
09 97 57-1
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/636 beOcO-66d 9-4e95-99c5-
a6243454ab97/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 97 57 Polyethylene Tape Pipe Coating.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1.4 INSPECTION
A. The entire procedure of applying the protective coating material as herein described
will be inspected by the Construction Manager from surface preparation to
completion of coating. Such inspection shall not relieve the Contractor of
responsibility to furnish material and perform work in accordance with this
specification. All coating work shall be done in the presence of the Construction
Manager. Coating work not done in the Construction Manager's presence will be
subject to rejection.
PART 2 MATERIALS
2.1 POLYETHYLENE TAPE COATING
A. Polyethylene tape coating shall be in accordance with AWWA C214 as modified
herein. The entire taping operation shall be developed by the pipe manufacturer with
the assistance from and approval of the tape manufacturer. Inner layer and outer
layer polyethylene tape shall exhibit properties meeting the requirements of AWWA
C214. The total coating system shall be the Polyken YGIII System, Alta 100.20
Innerlayer/206.30 Outerlayer System, or equal. The application shall consist of one
inner layer and one outer layer with the inner layer tape of thickness 20 mils
minimum and the outer layer tape of thickness 35 mils minimum each. The total
coating thickness shall not be less than 55 mils measured in the unapplied state and
shall exhibit the properties meeting the requirements of AWWA C214, Table 4. Tape
width shall not exceed 12 inches regardless of pipe diameter.
B. Polyethylene tape coating for fittings and specials shall be three layers of 30-mil or
two layers of 50-mil Type I or Type II in accordance with AWWA C209. The tape
applied to fittings shall be compatible with the polyethylene tape coating system
applied to pipe. Width of tape used shall be selected on the basis of the geometry
of the particular fitting or special being coated. Alternatively, coat fittings and
specials with two layers of half lapped 50-mil hot-applied coal-tar tape in accordance
with AWWA C203. Total thickness shall be 100 mils in the unapplied state. Prepare
and coat weld seams as specified for normal straight pipe.
2.2 TAPE MATERIALS
A. Tape materials shall conform to the following criteria:
1. Inner Layer Tape:
Backing 98% blend of high- and low-density
polyethylene with the remaining portion
a blend of colorants and stabilizers.
Adhesive 100% butyl-based elastomers with
resins for adhesion, cathodic
disbonding, and long-term in- ground
performance.
POLYETHYLENE TAPE PIPE COATING (AWWA C214)
09 97 57-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/636 beOcO-66d 9-4e95-99c5-
a6243454ab97/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 97 57 Polyethylene Tape Pipe Coating.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
Tensile strength at break 30 lb/in. per ASTM D1000
Elongation at break 200% per ASTM D1000
Adhesion to steel 100 oz/in. width per ASTM D1000
Adhesion to primed steel 300 oz/in. width per ASTM D1000
Adhesion to backing 40 oz/in. width per ASTM D1000
Dielectric strength Greater than or equal to 20 kV per
ASTM D 149
Insulation resistance 1 x 1012 ohms per ASTM D1000
Water vapor transmission rate <0.2 gm/100 sq. in./24 hours at 70OF
per ASTM E96, Method B
Cathodic disbonding at 200C (68°F) 0.2 sq. in. per ASTM G8
for 30 days
Shear resistance at 660C (1500F) for 0.2 mm/day per ASTM D3654,
four weeks Procedure A
Hydrolytic stability for 200 hours at 980C H2O, adhesion > 150 oz/in.
Thermal stability for 2,000 hours at 100°C air, adhesion > 150 oz/in.
2. Outer Layer Tape:
Backing 96% blend of high- and low-density
polyethylene with the remaining portion a
blend of colorants and stabilizers.
Adhesive 100% butyl-based elastomer with resins for
adhesion, cathodic disbonding, and long-
term in-ground performance.
Tensile strength 45 lb/in. width (inner wrap) per ASTM D1000
Tensile strength 55 lb/in. width (outer wrap) per ASTM D1000
Elongation 200% per ASTM D1000
Adhesion to steel 80 oz/in. width per ASTM D1000
POLYETHYLENE TAPE PIPE COATING (AWWA C214)
09 97 57-3
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/636 beOcO-66d 9-4e95-99c5-
a6243454ab97/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 97 57 Polyethylene Tape Pipe Coating.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
Adhesion to backing 40 oz/in. width (inner wrap) per ASTM D1000
Adhesion to backing 60 oz/in. width (outer wrap) per ASTM D1000
Water vapor transmission <0.2 gm/100 sq. in./24 hours at 70OF per
ASTM E96, Method B
Dielectric strength Greater than or equal to 25 kV per ASTM
D149
Second mechanical outer layer shall have UV protection.
PART 3 EXECUTION
3.1 PIPE PREPARATION
A. Perform the entire coating operation as a one-station operation where the pipe is
supported at the ends in a manner that will permit the application of the specified
coatings. No additional handling following the initial setup of the pipe section, from
application of primer, tape coating, and cement-mortar coating, will be allowed. No
application involving rollers to support the pipe during the primer application, plastic
tape application will be permitted.
B. The pipe shall be of sufficient stiffness or have sufficient internal bracing to keep
pipe cylindrical during taping. Maintain the axis of pipe during application without
rocking, pitching, or yawing.
C. Perform the coating operation in an environmentally controlled area such that it is
protected from direct sunlight, wind, rain, snow, mist, fog, dust, and hail.
D. Remove welding slag or scale by wire brushing, hammering, or other means prior
to priming. Completely remove corrosion and foreign substances from the exterior
of the pipe by blasting. The blast profile depth shall not exceed 3 mils. Wipe and
broom the pipe surface after sandblasting and transport to coating station to remove
grit, dust, and foreign substances.
E. Prepare the exterior weld bead as follows:
1. Where the exterior weld bead has a rough or irregular surface or narrow profile
or is in excess of 1/16 inch in height, remove the exterior weld bead along the
entire exterior surface of the pipe. The exterior weld bead shall be flush with
the exterior surface of the pipe with a tolerance of +1/64 inch. Remove the
weld bead such that no gouging or nicking of the plate surface will occur. This
operation shall result in a smooth exterior surface with no ridges or valleys
that may allow bridging or disbonding of the tape from the surface of the pipe.
2. Where the exterior weld bead has a smooth surface and broad profile and is
not in excess of 1/16 inch in height, remove the exterior weld bead within 18
inches of the ends of the pipe. The resultant bead shall be flush with the
POLYETHYLENE TAPE PIPE COATING (AWWA C214)
09 97 57-4
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/636 beOcO-66d 9-4e95-99c5-
a6243454ab97/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 97 57 Polyethylene Tape Pipe Coating.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
exterior surface of the pipe with a tolerance of +1/64 inch. Remove the weld
bead such that no gouging or nicking of the plate surface will occur. Apply
primer as specified hereinafter, then prior to application of the inner wrap,
apply a thin 6-inch-wide weld seam tape by automatic means over the weld
seam. Construct the weld stripping tape of a low- density plastic backing not
more than 5 mils thick and soft adhesive not more than 20 mils thick (Polyken
932-25 or equal). Immediately upon application, mechanically press the tape
into place with a pressure roller to eliminate voids, wrinkles, or bubbles. Tape
width shall extend 2 inches beyond the weld bead in each direction and shall
be centered on the weld bead.
F. Where pipe is shop cement-mortar lined, apply the exterior coating after the pipe is
lined with mortar and the mortar is cured.
G. Surface temperature of pipe shall be uniform, between 50 degrees Fahrenheit and
100 degrees Fahrenheit, and greater than 5-degrees Fahrenheit above the dew
point.
3.2 APPLICATION OF PRIMER
A. Uniformly heat primer to maintain at 70 degrees Fahrenheit±10 degrees Fahrenheit
(or slightly above pipe surface temperature when greater than 70 degrees
Fahrenheit), throughout the application procedure. Use continuous recording chart-
type devices to monitor primer temperature. Thoroughly mix the primer and agitate
continuously during application to prevent settling of solids.
B. Wipe the pipe surface free of dust and grit. Apply the primer coating immediately
after surface preparation. Apply primer by automatic means with the spray shielded
from drafts to result in a uniform thin primer over the entire pipe surface. Primer
coverage shall be in accordance with manufacturer's recommendations but shall not
exceed 600 square feet per gallon.
C. Remove any imperfections from priming such as foreign material, drips, and runs.
Reprime at location of such imperfections. Primer shall be sufficiently tacky prior to
tape application to result in a void-free bond to steel.
D. Thoroughly mix and heat primer, if necessary, to apply at optimum temperature.
3.3 TAPE APPLICATION
A. The entire coating operation shall be performed by experienced workers skilled in
the application of prefabricated cold-applied tape wrap coating and cement-mortar
coating under qualified supervisors.
B. Apply pipeline tape at a uniform roll body temperature above 50 degrees Fahrenheit
and at an ambient temperature above 30 degrees Fahrenheit. Store up to the time
of application under such conditions and for a sufficient period of time that the roll
body temperature shall be within the temperature range recommended by the tape
system manufacturer at the time of application.
POLYETHYLENE TAPE PIPE COATING (AWWA C214)
09 97 57-5
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/636 beOcO-66d 9-4e95-99c5-
a6243454ab97/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 97 57 Polyethylene Tape Pipe Coating.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
C. Prime and hand press the free ends of outer wrap of each pipe section into place.
Immediately upon application, mechanically press the inner layer tape into place by
means of coating equipment with constant tension tape dispensing machines to
result in a void-free coating, bonded to the primed steel surface and weld seam tape
system. Spirally apply the inner layer tape with a 1-inch-minimum overlap,
incorporating a pressure roller wider than the tape width to provide maximum contact
at the step-down of the overlap and to eliminate air entrapment between the tape
and the pipe. The pressure roller shall be hard rubber applying 1,000 to 1,200 psi
against the pipe exactly at the tape-to-pipe contact.
D. Operators shall make adjustments, including spindle-brake tension adjustments, to
provide a continuous, uniform, tight coating. Apply tape at a uniform rate throughout
the entire length of pipe at a tape speed not in excess of 3 fps.A smooth,taut coating
accomplished with a tape-width drawdown not in excess of 2 percent shall be
considered adequate. Keep wrinkles, puckers, and voids to a minimum and maintain
the specified lap.
E. Simultaneously with tape application, apply the specified outer wraps spirally. Make
necessary adjustments to achieve a uniform, tightly applied outer wrap, essentially
free of wrinkles, puckers, and voids, with a 1-inch-minimum lap width. Continuously
record tape temperature near the point of application, and provide automatic means
to adjust tape temperature during application.
F. When solvent is used to remove coating or primer prior to welding, none of it shall
be permitted to contact the exposed tape adhesive. Precautions shall be taken to
protect the exposed tape, and only solvents approved by the tape manufacturer shall
be used.
G. Hold back the tape coating a sufficient length to provide clearance for welding joints
in the field.
3.4 CEMENT MORTAR ARMOR COATING
A. Apply a 1-inch-thick reinforced cement mortar armor coating over the tested and
holiday-free completed tape coating, in accordance with AWWA C205. The cement
mortar shall consist of not more than 4.5 cubic feet of sand to one sack (94 Ibs) of
cement.
B. Leave 3 inches of tape uncoated at each end of the pipe in order to facilitate field
tape coating of the joints.
3.5 COATING OF WELDED FIELD JOINTS
A. When the joints are bell-and-spigot (weld bell) for field welding and the drawings or
specifications do not require a full fillet weld or when the welding is accomplished
from the inside only, apply a moldable filler material (per Section 09 90 00— Painting
and Coating)to fill all voids at the step down prior to tape coating the joint. Place the
filler material firmly against the primed steel surfaces to eliminate voids under the
tape and provide a smooth transition surface between bell and spigot.
POLYETHYLENE TAPE PIPE COATING (AWWA C214)
09 97 57-6
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/636 beOcO-66d 9-4e95-99c5-
a6243454ab97/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 97 57 Polyethylene Tape Pipe Coating.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
B. Complete the coating of the joint in accordance with Section 09 90 00 — Painting
and Coating, then after successful holiday testing of the joint, apply mortar coating
over the joint in accordance with AWWA C205.
3.6 MECHANICAL COUPLINGS AND PIPE ENDS
A. Where rubber-gasketed joints or mechanical couplings are used, apply a moldable
filler material as specified for field-welded joints to fill all surface irregularities prior
to application of tape. Alternatively for mechanical couplings, apply petrolatum or
petroleum wax tape coating in accordance with AWWA C217.
END SECTION
POLYETHYLENE TAPE PIPE COATING (AWWA C214)
09 97 57-7
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/636 beOcO-66d 9-4e95-99c5-
a6243454ab97/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 97 57 Polyethylene Tape Pipe Coating.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
This Page is Intentionally Left Blank
POLYETHYLENE TAPE PIPE COATING (AWWA C214)
09 97 57-8
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/636 beOcO-66d 9-4e95-99c5-
a6243454ab97/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/09 97 57 Polyethylene Tape Pipe Coating.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 26 05 19
CONDUCTORS AND CABLES
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes
1. Provide all labor, materials and equipment necessary for the installation of all
conductors and cables under this Section related to lighting, power, mechanical,
control and signal systems.
B. Related sections
1. Where items specified in other Division 26 sections conflict with the requirements
of this Section, the most stringent requirement shall govern.
2. The requirements of this Section apply to all Division 26 work, as applicable.
3. Consult all other sections, determine the extent and character of related work
and properly coordinate work specified herein with that specified elsewhere to
produce a complete installation.
1.2 REFERENCES
A. Comply with the latest edition of the following applicable specifications and standards
except as otherwise shown or specified:
1. ASTM -American Society for Testing and Materials
a. 133; Standard Specification for Soft or Annealed Copper Wire
b. 138; Standard Specification for Concentric-Lay-Stranded Copper Conductors,
Hard, Medium-Hard, or Soft
c. 13787/13787M; Standard Specification for 19 Wire Combination Unilay-
Stranded Copper Conductors for Subsequent Insulation
d. D1000; Standard Test Method for Pressure-Sensitive Adhesive-Coated
Tapes Used for Electrical and Electronic Applications
2. CCR —California Code of Regulations, Title 24
a. Part 3 -California Electrical Code(CEC); NFPA 70 National Electrical Code
(NEC) with California amendments
3. UL -Underwriters Laboratories, Inc.
a. UL 83; Thermoplastic-Insulated Wire and Cables
CONDUCTORS AND CABLES
26 05 19-1
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
b. UL 486A 48613; Wire Connectors
c. UL 486C; Splicing Wire Connectors
d. UL 486D; Standard for Insulated Wire Connector Systems For Underground
Use Or In Damp Or Wet Locations
e. UL 486E; Standard for Equipment Wiring Terminals for Use with Aluminum
and/or Copper Conductors
f. UL 493; Thermoplastic-Insulated Underground Feeders and Branch Circuit
Cables
g. UL 510; Standard for Polyvinyl Chloride, Polyethylene and Rubber Insulating
Tape
h. UL 854; Service-Entrance Cables
4. NEMA—National Electrical Manufacturer's Association
a. WC 70-1999; Nonshielded Power Cables Rated 2000 Volts or less for the
Distribution of Electrical Energy
5. IEEE —Institute of Electrical and Electronic Engineers
a. 82; Standard Test Procedure for Impulse Voltage Tests on Insulated
Conductors
1.3 DELIVERY
A. Wire shall be in original unbroken package. Obtain approval of Inspector or
Engineer before installation of wires.
PART2 - PRODUCTS
2.1 BUILDING WIRE
A. Conductor material
1. Provide annealed copper for all wire, conductor and cable of not less than 98%
conductivity.
2. Wire #8 AWG and larger shall be stranded.
3. Wire #10 AWG and smaller shall be solid.
B. Insulation material
1. All insulated wire, conductor and cable shall be 600 Vac rated.
CONDUCTORS AND CABLES
26 05 19-2
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2. Feeder and branch circuits larger than #6 AWG shall be type THW, XHHW or
THHN/THWN.
3. Feeder and branch circuits #6 AWG and smaller shall be type TW, THW, XHHW
or THHN/THWN.
4. Control circuits shall be type THW or THHN/THWN.
5. Wires shall bear the UL label, be color-coded and marked with gauge, type and
manufacturer's name on 24" centers.
2.2 FLEXIBLE CORDS AND CABLES
A. Provide flexible cords and cables of size, type and arrangement as indicated on
Drawings.
B. Type S flexible cords and cable shall be manufactured in accordance with CEC
Article 400 and composed of two or more conductors and a full sized green insulated
grounding conductor with an outer rubber or neoprene jacket.
C. Flexible cords and cables shall be fitted with wire mesh strain relief grips either as a
integral connector component or an independently supported unit.
D. Suspended flexible cords and cables shall incorporate safety spring(s).
2.3 WIRE CONNECTIONS AND TERMINATIONS
A. Electrical spring wire connectors
1. Provide multi-part construction incorporating a non-restricted, zinc coated square
cross-sectional steel spring enclosed in a steel sheet with an outer jacket of
plastic and insulating skirt.
2. Self-striping pigtail and tap U-contact connectors are not acceptable.
B. Compression type terminating lugs
1. Provide tin-plated copper high compression type lugs for installation with hand or
hydraulic crimping tools as directed by manufacturer. Notch or single point type
crimps are not acceptable.
2. Two hole, long barrel lugs shall be provided for size #4/0 AWG and larger wire
where terminated to bus bars. Use minimum of three crimps per lug where
possible.
C. Splicing and insulating tape
1. Provide black, UV resistant, self extinguishing, 7 mil thick vinyl general purpose
electrical tape per UL 510 and ASTM D1000. 3M Scotch 33 or equal.
D. Insulating putty
CONDUCTORS AND CABLES
26 05 19-3
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1. Provide pads or rolls of non-corrosive, self-fusing, 125 mil thick rubber putty with
PVC backing sheet per UL 510 and ASTM D1000. 3M Scotchfil or equal.
E. Insulating resin
1. Provide two-part liquid epoxy resin with resin and catalyst in pre-measured,
sealed mixing pouch. 3M Scothcast 4 or equal.
2. Use resin with thermal and diaelectric properties equal to the cable's insulating
properties.
F. Terminal strips
1. Provide box type terminal strips in the required quantities plus 25% spare. Install
in continuous rows.
2. Use the box type terminal strips with barrier open backs and with ampere ratings
as required.
3. Identify all terminals strips and circuits.
G. Crimp type connectors
1. Provide insulated fork or ring crimp terminals with tinned electrolytic copper-
brazed barrel with funnel wire entry and insulation support.
2. Fasten crimp type connectors or terminals using a crimping tool recommended
by the manufacturer.
3. Provide insulated overlap splices with tinned seamless electrolytic copper-brazed
barrel with funnel wire entry and insulation support.
4. Provide insulated butt splices with tinned seamless electrolytic copper-brazed
barrel with center stop, funnel wire entry and insulation support.
H. Cable ties
1. Provide harnessing and point-to-point wire bundling with nylon cable ties. Install
using tool supplied by manufacturer as required.
I. Wire lubricating compound
1. UL listed for the wire insulation and conduit type, and shall not harden or become
adhesive.
2. Shall not be used on wire for isolated type electrical power systems.
J. Bolt termination hardware
1. Bolts shall be plated, medium carbon steel heat-treated, quenched and tempered
equal to ASTM A-325 or SAE Grade 5; or silicon bronze alloy ASTM B-9954
Type B.
CONDUCTORS AND CABLES
26 05 19-4
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2. Nuts shall be heavy semi-finished hexagon, conforming to ANSI B18.2.2, threads
to be unified coarse series (UNC), class 2B steel or silicon bronze alloy.
3. Flat washers shall be steel or silicon bronze, Type A plain standard wide series,
conforming to ANSI B27.2. SAE or narrow series shall be used.
4. Belleville conical spring washers shall be hardened steel, cadmium plated or
silicon bronze.
5. Each bolt connecting lug(s) to a terminal or bus shall not carry current exceeding
the following values:
a. 1/4" bolt— 125 A
b. 5/16" bolt— 175 A
c. 3/8" bolt—225 A
d. 1/2" bolt— 300 A
e. 5/8" bolt— 375 A
f. 3/4" bolt—450 A
PART 3 - EXECUTION
3.1 EXAMINATION
A. Thoroughly examine site conditions for acceptance of wire and cable installation to
verify conformance with manufacturer and specification tolerances. Do not
commence with work until all conditions are made satisfactory.
3.2 INSTALLATION
A. All wire, conductor, and cable with their respective connectors, fittings and supports
shall be UL listed for the installed application and ambient conditions.
B. Feeders and branch circuits in wet locations shall be rated 750C minimum.
C. Feeders and branch circuits in dry locations shall be rated 900C minimum.
D. Minimum conductor size
1. #12 AWG copper for all power and lighting branch circuits.
2. #14 AWG copper for all line voltage signal and control wiring, unless otherwise
indicated.
E. Remove and replace conductors under the following conditions at no additional costs
to the Owner:
CONDUCTORS AND CABLES
26 05 19-5
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1. Installed within wrong specified conduit or raceway.
2. Damaged during installation.
3. Of insufficient length to facilitate proper splice of conductors
3.3 WIRING METHODS
A. Install wires and cable in accordance with manufacturer's written instructions, as
shown on Drawings and as specified herein.
B. Install all single conductors within raceway system, unless otherwise indicated.
C. Parallel circuit conductors and terminations shall be equal in length and identical in
all aspects.
D. Provide adequate length of conductors within electrical enclosures and neatly train to
termination points with no excess. Terminate such that there is no bare conductor at
the terminal.
E. Splice cables and wires only in junction boxes, outlet boxes, pull boxes, manholes or
handholes.
F. Group and bundle with tie wrap each neutral with its associated phase conductors
where more than one neutral conductor is present within a conduit.
G. Install cable supports for all vertical feeders in accordance with CEC Article 300.
Provide split wedge type fittings, which firmly clamp each individual cable and tighten
due to cable weight.
H. Seal cable where exiting a conduit from an exterior underground raceway with a non-
hardening compound (i.e., duct seal or equal).
I. Provide UL listed factory fabricated, solder-less metal connectors of size, ampacity
rating, material, type and class for applications and for services indicated. Use
connectors with temperature ratings equal or greater than the conductor or cable
being terminated.
J. Stranded wire shall be terminated using fittings, lugs or devices listed for the
application. Under no circumstances shall stranded wire be terminated solely by
wrapping it around a screw or bolt.
K. Flexible cords and cables supplied as part of a pre-manufactured assembly shall be
installed according to manufacturer's published instructions.
3.4 WIRING INSTALLATION IN RACEWAYS
A. Install wire in raceway after interior of building has been physically protected from
weather, and all mechanical work likely to injure conductors has been completed.
B. Pull all conductors into raceway at the same time.
CONDUCTORS AND CABLES
26 05 19-6
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
C. Use UL listed, non-petroleum base and insulating type pulling compound as needed.
D. Completely mandrel all underground or concrete encased conduits prior to
installation.
E. Completely and thoroughly swab raceway system prior to installation
F. Do not use block and tackle, power driven winch or other mechanical means for
pulling conductors smaller than #1 AWG.
G. Wire pulling
1. Provide installation equipment that will prevent cutting or abrasion of insulation
during installation.
2. Maximum pull tension shall not exceed manufacturer's recommended value
during installation for cable being measured with tension dynometer.
3. Use rope made of non-metallic material for pulling.
4. Attach pulling lines by means of either woven basket grips or pulling eyes
attached directly to the conductors.
5. Pull multiple conductors simultaneously within same conduit.
3.5 WIRE SPLICES, JOINTS AND TERMINATIONS
A. Join and terminate wire, conductors and cables in accordance with UL 486, CEC and
manufacturer's instructions.
B. Thoroughly clean wires before installing lugs and connectors.
C. Make splices, taps and terminations to carry full conductor ampacity without
perceptible temperature rise, and shall be made mechanically and electrically
secure.
D. Terminate wires in terminal cabinets using terminal strips, unless otherwise
indicated.
E. Insulate spare conductors with electrical tape and leave sufficient length to terminate
anywhere within panel or cabinet.
F. Encapsulate splices in wet locations using specified insulating resin kits.
G. Make up all splices and taps in accessible junction or outlet boxes with connectors
as specified herein. Pigtails and taps shall be the same color as feed conductor with
at least 6 inches of tail, all neatly packed within box.
H. Where conductors are to be connected to metallic surfaces, coated surfaces shall be
cleaned to base metal surface before installing connector. Remove lacquer coating
of conduits where ground clamps are to be installed.
CONDUCTORS AND CABLES
26 05 19-7
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
I. Branch circuits (#10 AWG and smaller) connectors shall comply with 2.03.A and
2.03.13 above.
J. Branch circuits (#8 AWG and larger)
1. Join or tap conductors using insulated mechanical compression taps with pre-
molded, snap-on insulating boots or specified conformable insulating pad and
over-wrapped with two half-lapped layers of vinyl insulating tape starting and
ending at the middle of joint.
2. Terminate conductors using mechanical compression lugs in accordance with
manufacturer's recommendation or as specified elsewhere.
3. Field installed compression connectors for 250 MCM and larger shall have not
less than two clamping elements or compression indents per wire.
4. Insulate splices and joints with materials approved for the particular use, location,
voltage and temperature.
K. Termination hardware assemblies
1. AI/Cu lugs connected to aluminum plated or copper bus shall be secured with
steel bolt, flat washer (two per bolt), Belleville washer and nut.
2. Copper lugs connected to copper buss shall bus shall be secured using silicon
bronze alloy bolt, flat washer (two per bolt), Belleville washer and nut.
3. The crown of Belleville washers shall be under the nut.
4. Bolt assemblies shall be torque to manufacturer's recommendations. Where
manufacturer recommendation is not obtainable, the following shall be used:
a. 1/4" -20 bolt at 80 inch-pound torque
b. 5/16" -18 bolt at 180 inch-pound torque
c. 3/8" -20 bolt at 20 inch-pound torque
d. 1/2" -20 bolt at 40 inch-pound torque
e. 5/8" -20 bolt at 55 inch-pound torque
f. 3/4" -20 bolt at 158 inch-pound torque
3.6 IDENTIFICATION
A. Securely tag all branch circuits. Mark conductors with specified vinyl wrap-around
markers. Where more than two conductors run through a single outlet, mark each
conductor with the corresponding circuit number.
B. Provide all terminal strips with each individual terminal identified using specified vinyl
markers.
CONDUCTORS AND CABLES
26 05 19-8
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
C. In manholes, pullboxes and handholes provide tags of embossed brass type with
cable type and voltage rating. Attach tags to cable with slip-free plastic cable lacing
units.
D. Color coding
1. For 120/208 Volt (or 120/240 Volt), 1 phase, 3 wire systems:
a. Phase A— Black
b. Phase B — Red
c. Neutral —White
d. Ground — Green
2. For 120/208 Volt, 3 phase, 4 wire systems:
a. Phase A— Black
b. Phase B — Red
c. Phase C — Blue
d. Neutral —White
e. Ground — Green
3. For 277/480 Volt, 3 phase, 4 wire systems:
a. Phase A— Brown
b. Phase B — Orange
c. Phase C —Yellow
d. Neutral — Gray
e. Ground — Green
4. Switch leg individually installed shall be the same color as the branch circuit to
which they originate, unless otherwise indicated.
5. Travelers for 3-way and 4-way switches shall be a distinct color and pulled with
the circuit switch leg or neutral.
3.7 FIELD QUALITY CONTROL
A. Supply labor, materials and test equipment required to perform continuity and ground
tests.
B. Electrical testing
CONDUCTORS AND CABLES
26 05 19-9
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1. Perform feeder and branch circuit insulation test after installation and prior to
connection to device.
2. Tests shall be performed by 600 Vdc megger for a continuous 10 seconds from
phase-to-phase and phase-to-ground.
3. Torque test conductor connections and terminations for conformance to
Specifications.
4. If any failure is detected, locate failure, determine cause and replace or repair
cable to Engineer's satisfaction at no additional costs.
5. Furnish test results in type written report form for review by Engineer.
END OF SECTION
CONDUCTORS AND CABLES
26 05 19-10
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 26 05 26
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes
1. Provide all labor, materials and equipment necessary to complete the installation
required for the item specified under this Section, including but not limited to
power system grounding
B. Related sections
1. Where items specified in other Division 26 sections conflict with the requirements
of this Section, the most stringent requirement shall govern.
2. The requirements of this Section apply to all Division 26 work, as applicable.
3. Consult all other sections, determine the extent and character of related work
and properly coordinate work specified herein with that specified elsewhere to
produce a complete installation.
1.2 REFERENCES
A. Comply with the latest edition of the following applicable specifications and standards
except as otherwise shown or specified:
1. CCR —California Code of Regulations, Title 24
a. Part 3 -California Electrical Code (CEC); NFPA 70 National Electrical Code
(NEC) with California amendments
2. IEEE —Institute of Electrical and Electronic Engineers
a. 142; Recommend Practices for Grounding of Industrial and Commercial
Power Systems
3. NFPA—National Fire Protection Association
a. 780; Lightning Protection Code
4. UL —Underwriters Laboratories, Inc.
a. 467; Grounding and Bonding Equipment
1.3 SYSTEM DESCRIPTION
A. This Section provides for the grounding and bonding of all electrical and
communication apparatus, machinery, appliances, components, fittings and
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
26 05 26-1
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
accessories where required to provide a permanent, continuous, low impedance,
grounded electrical system.
B. Ground the electrical service system neutral at service entrance equipment as shown
on the Drawings.
C. Ground each separately derived system, as defined in CEC 250.5 (D) and on the
Drawings, unless specifically noted otherwise.
D. Except as otherwise indicated, the complete electrical installation including the
neutral conductor, equipment and metallic raceways, boxes and cabinets shall be
completely and effectively grounded in accordance with all CEC requirements,
whether or not such connections are specifically shown or specified.
1.4 SUBMITTALS
A. Submit manufacturer's data for equipment and materials specified within this Section
in accordance to Section 26 05 00.
1.5 QUALITY ASSURANCE
A. All materials, equipment and parts comprising the materials specified herein shall be
new and unused, bearing UL labels where applicable.
PART2 - PRODUCTS
2.1 CONCRETE ENCASED GROUNDING ELECTRODE (LIFER GROUND)
A. #3/0 AWG minimum bare stranded copper conductor.
2.2 DRIVEN (GROUND) RODS
A. Copper clad steel, minimum %" diameter by 10'-0" length, sectional type with copper
alloy couplings and carbon steel driving stud; Weaver, Cadweld or equal.
2.3 INSULATED GROUNDING BUSHINGS
A. Plated malleable iron body with 150°C molded plastic insulated throat and lay-in
ground lug; OZ/Gedney BLG, Thomas & Betts #TIGB series or equal.
2.4 CONNECTION TO PIPE
A. Cable to pipe connections; OZ/Gedney G-100B series, Thomas & Betts #290X
series or equal.
2.5 CONNECTIONS TO STRUCTURAL STEEL, GROUND RODS OR SPICES
A. Where required by the Drawings, grounding conductors shall be spliced together,
connected to ground rods or connected to structural steel using exothermic welds,
Cadweld or equal, or high pressure compression type connectors, Cadweld, Thomas
& Betts or equal.
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
26 05 26-2
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2.6 BONDING JUMPERS
A. OZ/Gedney Type BJ, Thomas & Betts #3840 series or equal.
2.7 GROUND CONDUCTOR
A. Ground conductor shall be code size UL labeled, Type THWN insulated copper wire,
green in color.
2.8 MAIN BUILDING REFERENCE GROUND BUS (BGB)
A. Provide 1 24"x4"x1/4" TK copper bus bar mounted on wall with insulating stand-offs
at +18" AFF. Furnish complete with cast copper alloy body Thomas Betts Series 310
or equal lugs for connecting grounding conductors. Attach lugs to bus with
appropriate size bronze bolt, flat washer and Belleville washer. All connections shall
be torque, and all holes shall be drilled and tapped for single hole lugs. Provide 4
spare lugs with respective spaces.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Grounding electrodes
1. Concrete encased grounding electrode (Ufer ground)
a. Provide a #3/0 AWG minimum bare copper conductor encased along the
bottom of concrete foundation, footing or trench which is in direct contact with
the earth and where there is no impervious waterproofing membrane
between the footing and soil. The electrode shall extend through a horizontal
length of 30' minimum and shall be encased in not less than 2" or more than
5" of concrete separating it from surrounding soil. The electrode shall
emerge from the concrete slab through a protective non-metallic sleeve and
shall be extended to BGB or as shown on Drawings.
2. Supplementary grounding electrode (ground ring, grid and driven rod)
a. Provide as shown driven ground rod(s). Interconnect ground rod with
structural steel and adjacent rods with code size bare copper conductor.
Ground rods shall be space no less than 6'-0" on centers from any other
electrode or electrodes of another electrical system.
3. Separately derived electrical system grounding electrode
a. Ground each separately derived system per CEC 250-26 or as shown on
Drawings, whichever is greater.
4. Metal underground water pipe
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
26 05 26-3
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
a. Contractor shall install am accessible grounding electrode conductor from the
main incoming cold water line to BGB. The electrode conductor shall be
sized per CEC Table 250-94 or as shown on Drawings, whichever is greater.
B. Grounding electrode conductor
1. Provide grounding electrode conductors per CEC Table 250-94 or as shown on
Drawings, whichever is greater.
C. Power system grounding
1. Connect the following items using code size copper grounding conductors to
BGB or as shown on Drawings:
a. Concrete encased electrode (Ufer ground)
b. Ground rod(s)
c. Incoming cold and fire water pipes
d. Gas pipe
e. Structural steel
f. Distribution transformer secondary
D. Equipment Bonding/Grounding
1. Provide a code sized copper ground conductor, whether indicated or noted on
the drawings, in each of the following:
a. All power distribution conduits and ducts
b. Distribution feeders
c. Motor and equipment branch circuits
d. Device branch circuits
2. Provide a separate grounding bus at distribution panelboards, loadcenters,
switchboards and motor control centers. Connect all metallic enclosed
equipment so that with maximum fault current flowing, shall be maintained at not
more than 35V above ground.
3. Metallic conduits terminating in concentric, eccentric or oversized knockouts at
panelboards, cabinets, gutters, etc. shall have grounding bushings and bonding
jumpers installed interconnecting all such conduits.
4. Provide bonding jumpers across expansion and deflection coupling in conduit
runs, pipe connections to water meters and metallic cold water dielectric
couplings.
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
26 05 26-4
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
5. Provide ground wire in flexible conduit connected at each end via grounding
bushing.
6. Provide bonding jumpers across all cable tray joints.
7. Bond each end of metallic conduit longer than 36" in length to grounding
conductor using a #6 AWG pigtail.
3.2 FIELD QUALITY CONTROL
A. Contractor using test equipment expressly designed for that purpose shall perform all
ground resistance tests in conformance with IEEE quidelines. Contractor shall
submit typewritten records of measured resistance values to Engineer for review and
approval prior to energizing the system.
B. Obtain and record ground resistance measurements both from electrical equipment
ground bus to the ground electrode and from the ground electrode to earth. Furnish
and install additional bonding and add grounding electrodes as required to comply
with the following resistance limits:
1. Resistance from ground bus to ground electrode and to earth shall not exceed 5
ohms unless otherwise noted.
2. Resistance from the farthest panelboard, loadcenter, switchboard or motor
control center ground bus to the ground electrode and to earth shall not exceed
20 ohms maximum.
C. Inspection
1. The Engineer or Inspector prior to encasement, burial or concealment thereto
shall review the grounding electrode and connections.
END OF SECTION
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
26 05 26-5
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 26 05 33
RACEWAYS AND BOXES
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes
1. Provide all labor, materials and equipment necessary to complete the installation
required for the items specified under this Section, including but not limited to
electrical conduits; outlet, junction and pull boxes; and related supports.
B. Related sections
1. Where items specified in other Division 26 sections conflict with the requirements
of this Section, the most stringent requirement shall govern.
a. 26 05 26 — Grounding and Bonding for Electrical Systems
2. The requirements of this Section apply to all Division 26 work, as applicable.
3. Consult all other sections, determine the extent and character of related work
and properly coordinate work specified herein with that specified elsewhere to
produce a complete installation.
1.2 REFERENCES
A. Comply with the latest edition of the following applicable specifications and standards
except as otherwise shown or specified:
1. ANSI —American National Standards Institute
a. C33.91; Specification for Rigid PVC Conduit
b. C80.1; Specification Rigid Steel Conduit, Zinc-Coated
c. C80.3; Specification for Electrical Metallic Tubing, Zinc-Coated
d. C80.6; Intermediate Metal Conduit (IMC), Zinc-Coated
2. CCR —California Code of Regulations, Title 24
a. Part 2 -California Building Code (CBC); International Building Code (IBC) with
California amendments
b. Part 3 -California Electrical Code(CEC); NFPA 70 National Electrical Code
(NEC) with California amendments
3. NECA—National Electrical Contractors Association
RACEWAYS AND BOXES
26 05 33-1
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
a. 101, Standard for Installing Steel Conduit (Rigid, IMC, EMT)
b. 111, Standard for Installing Nonmetallic Raceways (RNC, ENT, LFNC)
(ANSI)
4. NEMA—National Electrical Manufacturer's Association
a. FB 1; Fittings, Cast Metal Boxes, and Conduit Bodies for Conduit, Electrical
Metallic Tubing, and Cable
b. FB 2.10; Selection and Installation Guidelines for Fittings for Use with Non-
flexible Electrical Metal Conduit or Tubing (Rigid Metal Conduit, Intermediate
Metal Conduit, and Electrical Metallic Tubing)
c. FB 2.20; Selection and Installation Guidelines For Fittings for Use With
Flexible Electrical Conduit and Cable
d. OS 1; Sheet-Steel Outlet Boxes, Device Boxes, Covers, and Box Supports
e. OS 3; Selection and Installation Guidelines for Electrical Outlet Boxes
f. RN 1; Polyvinyl-Chloride Externally Coated Galvanized Rigid Steel Conduit
and Electrical Metallic Tubing
g. TC 2; Electrical Plastic Tubing and Conduit
h. TC 3; PVC Fittings for Use with Rigid PVC Conduit and Tubing
i. TC 14; Reinforced Thermosetting Resin Conduit (RTRC) and Fittings
5. OSHPD Anchorage Pre-approvals
a. OPA-0003; Superstrut Seismic Restraint System
b. OPA-0114; B-Line Seismic Restraints
c. OPA-0120; Unistrut Seismic Bracing System
d. OPA-0242; Power-Strut Seismic Bracing System
6. UL—Underwriter's Laboratories, Inc.
a. 1; Standard for Flexible Metal Conduit
b. 6; Rigid Metal Electrical Conduit
c. 360; Standard for Liquid-Tight Flexible Steel Conduit
d. 514A; Metallic Outlet Boxes, Electrical
e. 51413; Fittings for Conduit and Outlet Boxes
RACEWAYS AND BOXES
26 05 33-2
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
f. 651; Schedule 40 & 80 PVC Conduit
g. 797; Electrical Metallic Tubing
h. 1242; Intermediate Metal Conduit
i. 1684; Reinforced Thermosetting Resin Conduit (RTRC) and Fittings
1.3 SYSTEM DESCRIPTION
A. Furnish, assemble, erect, install, connect and test all electrical conduits and related
raceway apparatus required and specified to form a complete installation.
1.4 SUBMITTALS
A. Submit manufacturer's data for materials specified within this Section in accordance
to Section 26 05 00.
1.5 QUALITY ASSURANCE
A. All materials, equipment and parts comprising the materials specified herein shall be
new and unused, bearing UL labels where applicable.
B. Installation shall conform to the NECA installation guidelines unless otherwise
indicated within this Section
PART2 - PRODUCTS
2.1 MATERIALS
A. Conduits and Fittings
1. Rigid steel conduit (RMC)
a. Conduit: Standard weight, mild steel pipe, and zinc coated on both inside and
outside by a hot dipping or shearardizing process manufactured in
accordance with UL 6 and ANSI C80.1 specifications.
b. Fittings (couplings, elbows, bends, etc.)
1) Shall be steel or malleable iron.
2) Coupling and unions shall be threaded type, assembled with anti-
corrosion, conductive and anti-seize compound at joints made absolutely
tight to exclude water.
c. Bushings
1) Insulating bushings: Threaded polypropylene or thermosetting phenolic
rated at 150°C minimum.
RACEWAYS AND BOXES
26 05 33-3
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2) Insulating grounding bushing: Threaded cast body with insulating throat
and steel "lay-in" ground lug.
3) Insulating metallic bushing: Threaded cast body with plastic insulated
throat rated at 150°C minimum.
2. Stainless steel conduit (SSC)
a. Conduit: Same as rigid steel conduit except Type 304 stainless steel.
b. Fittings (couplings, elbows, bends, etc.): Same as rigid steel conduit except
Type 304 stainless steel.
c. Bushings: Same as rigid steel conduit except Type 304 stainless steel.
3. Coated rigid steel conduit (CRMC)
a. Conduit: Equivalent to RMC with a Polyvinyl chloride (PVC) coated bonded to
the galvanized outer surface of the conduit. The bonding between the PVC
coating and conduit surface shall be ETL PVC-001 compliant. The coating
thickness shall be a minimum of 40mil.
b. Fittings (couplings, elbows, bends, etc.)
1) Equivalent to RMC above with bonded coating same as conduit.
2) The PVC sleeve over fittings shall extend beyond hub or coupling
approximately one diameter or 1 1/2" whichever is smaller.
c. Bushing equivalent to RMC above.
4. Intermediate metallic conduit(IMC)
a. Conduit: Intermediate weight, mild steel pipe, meeting the same requirements
for finish and material as rigid steel conduit manufactured in accordance with
UL 1242 and ANSI C80.6 specifications.
b. Fittings (couplings, elbows, bends, etc.) equivalent to RMC above.
c. Bushing equivalent to RMC above.
5. Electrical metallic tubing (EMT)
a. Conduit: Cold rolled steel tubing with zinc coating on outside and protective
enamel on inside manufactured in accordance with UL 797 and ANSI C80.3
specifications.
b. Couplings: Steel or malleable iron with compression type fastener via a nut.
c. Connectors: Steel or malleable iron with compression type fastener via a nut
with plastic insulated throat rated at 1500C minimum.
RACEWAYS AND BOXES
26 05 33-4
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
6. Rigid non-metallic conduit (PVC)
a. Conduit: PVC composed Schedule 40, 90°C manufactured in accordance
with NEMA TC 2 and UL 651 specifications.
b. Fittings: Molded PVC, slip on solvent welded type in accordance to NEMA TC
3.
7. Reinforced thermosetting resin conduit (RTRC)
a. Conduit: Fiber impregnated with a cured thermosetting resin compound in
accordance with NEMA TC 14 and UL1684.
b. Fittings: Molded resin with glass reinforcement manufactured in the same
process as the conduit bonded with an epoxy adhesive.
8. Flexible metallic conduit (FMC)
a. Conduit: Continuous, flexible steel spirally wound with zinc coating on both
inside and outside in accordance with UL 1.
b. Connectors: Steel or malleable iron with compression type fastener via a nut
with plastic insulated throat rated at 1500C minimum.
9. Liquidtight flexible metallic conduit (LFMC)
a. Conduit: PVC coated, continuous, flexible steel spirally wound with zinc
coating on both inside and outside in accordance with UL 360.
b. Connectors: Steel or malleable iron with compression type fastener via a nut
with plastic insulated throat rated at 1500C minimum.
10. Miscellaneous Fittings and Products
a. Conduit sealing bushings: Steel or cast malleable iron body and pressure
clamps with PVC sleeve, neoprene sealing grommets and PVC coated steel
pressure rings. Supplied with neoprene sealing rings between body and PVC
sleeve.
b. Watertight cable terminators: One piece, compression molded sealing ring
with PVC coated steel pressure disks, stainless steel screws and zinc plated
cast iron locking collar.
c. Watertight cable/cord connectors: Liquidtight steel or cast malleable iron body
with sealing neoprene bushing and stainless steel retaining ring.
d. Expansion fittings: Multi-piece unit of hot dip galvanized malleable iron or
steel body and outside pressure bussing design to allow a maximum of 4"
movement (2" in either direction). Furnish with external braid tinned copper
bonding jumper. UL listed for both wet and dry locations.
RACEWAYS AND BOXES
26 05 33-5
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
e. Expansion/deflection couplings: Multi-piece unit comprised of a neoprene
sleeve, internal flexible tinned copper braid attached to bronze end couplings
with stainless steel bands. Coupling to provide minimum of 3/4" movement
and 30 degrees deflection from normal. UL listed for both wet and dry
locations.
f. Conduit bodies: Raintight, malleable iron, hot-dip galvanized body with
threaded hubs, stamped steel cover, stainless steel screws and neoprene
gasket.
g. Other couplings, connectors and fittings shall be equal in quality, material and
construction to items specified herein.
B. Boxes
1. Outlet boxes
a. Standard: Galvanized one-piece of welded pressed steel type in accordance
with NEMA OS 1 and UL 514. Boxes shall not be less than 4" square and at
least 1 1/2" deep.
b. Concrete: Galvanized steel, 4" octagon ring with mounting lug, backplate and
adapter ring type in accordance with NEMA OS 1 and UL 514. Depth as
required by application.
c. Masonry: Galvanized steel, 3.75" high gang box in accordance with NEMA
OS 1 and UL 514.
d. Surface cast metal: Cast malleable iron body, surface mounted box with
threaded hubs and mounting lugs as required in accordance with NEMA OS
1 and UL 514. Furnish with ground flange, steel cover and neoprene gasket.
2. Pull and junction boxes
a. Sheet metal boxes: Standard or concrete outlet box wherever possible;
otherwise use 16 gauge galvanized sheet metal, NEMA 1 box sized per CEC
with machine screwed cover.
b. Cast metal boxes: Install standard cast malleable iron outlet or device box
when possible.
c. Flush mounted boxes: Install overlapping cover with flush head screws.
d. In-ground mounted pull holes/boxes: Install pre-cast concrete box, sized per
Drawing or CEC with pre-cast or traffic rated lid.
3. Floor boxes
a. Floor boxes shall be adjustable, cast metal body with threaded conduit
openings, adjustable rings, brass flange or Lexan ring and cover plate with
threaded plug. Include provisions to accommodate surface mounted
RACEWAYS AND BOXES
26 05 33-6
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
telephone or receptacle outlet, or flush floor mounted telephone or receptacle
outlet where shown on Drawings.
C. Pull line/cord
1. Polypropylene braided line or Let-line #232 or equal of 1/8" diameter with a
minimum break strength of 200 pounds.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Thoroughly examine site conditions for acceptance of wire and cable installation to
verify conformance with manufacturer and specification tolerances. Do not
commence with work until all conditions are made satisfactory.
3.2 PREPARATION
A. Conduit
1. Provide all necessary conduit fittings, connectors, bushings, etc. required to
complete conduit installation to meet the CEC and intended application whether
noted, shown or specified within.
2. Location of conduit runs shall be planned in advance of the installation and
coordinated with other trades.
3. Where practical, install conduits in groups in parallel vertical or horizontal runs
that avoid unnecessary offsets.
4. All conduits shall be parallel or at right angles to columns, beams and walls
whether exposed or concealed.
5. Conduits shall not be placed closer than 12" to a flue, parallel to hot water, steam
line or other heat sources; or 3" when crossing perpendicular to the above said
lines when possible.
6. Install exposed conduit as high as practical to maintain adequate headroom.
Notify Engineer if headroom will be less than 102".
7. Do not obstruct spaces required by Code in front of electrical equipment, access
doors, etc.
8. The largest trade size conduit in concrete floors and walls shall not exceed 1/3
thickness or be spaced a less than three conduit diameters apart unless
permitted by Engineer. All conduits shall be installed in the center of slab or wall,
and never between reinforcing steel and bottom of floor slab.
9. Install additional pull boxes, not shown on Drawings, in sufficient quantities to
facilitate pulling of conductors and cables such that total spacing does not
RACEWAYS AND BOXES
26 05 33-7
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
exceed 150 feet or 270 degrees, total; and maximum pulling tension will not be
exceeded.
10. When installing underground conduits to specified depth; depth shall be taken
from finished grade as it will be at project completion. Should finish grade be
above existing grade by an amount equal to or greater than specified depth,
conduit shall be installed not less than 6" below existing grade.
11. Verify that information concerning finish grade is accurate, for should the
underground run be less than the specified depth, Contractor may be required to
re-install conduit to meet the required depth.
12. Unless otherwise specified, underground conduits shall be installed with top side
not less than 24" below finished grade; this depth applies to all conduits outside
of building foundations including those under walks, open corridors or paved
areas.
13. Utility company service conduits installation depth shall be as directed by their
respective specifications and requirements.
B. Boxes
1. Before locating outlet boxes, check Construction Documents for type of
construction and make sure that there is no conflict with other equipment. Locate
outlet boxes as shown and locate so as not to interfere with other Work or
equipment.
2. Install all outlet boxes flush within walls, ceiling and floors except where installed
within non-finished rooms, cabinetry, attic spaces or as indicated on Drawings.
3. Locate pull boxes and junction boxes within concealed, accessible locations
where possible.
4. Do not install outlet boxes back-to-back with same stud space. Where shown
back-to-back, offset as required, and fill void with sound dampening material
where requested by Owner.
5. In fire rated walls separate boxes by 24" minimum and with stud member.
6. Adjust position of outlet boxes within masonry wall to accommodate course lines.
3.3 INSTALLATION
A. Conduit
1. Minimum conduit size shall be 3/4" unless otherwise indicated.
2. All conduit work shall be concealed unless otherwise indicated. Exposed
conduits shall be permitted within unfinished rooms/spaces to facilitate
installation.
3. Install conduit in complete runs prior to installing conductors or cables.
RACEWAYS AND BOXES
26 05 33-8
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
4. Make long radius conduits bends free from kink, indentations or flattened
surfaces. Make bends carefully to avoid injury or flattening. Bends 1 1/4" size
and larger shall be factory made ells or be made with a manufactured
mechanical bender. Heating of steel conduit to facilitate bending or that damage
galvanized coating will not be permitted.
5. Remove burrs and sharp edges at end of conduit with tapered reamer.
6. Protect and cover conduits during construction with metallic bushings and
bushing "pennies" to seal exposed openings.
7. Assemble conduit threads with anti-corrosion, conductive, anti-seize compound
and tighten securely.
8. Install conduits shall that no traps to collect condensation exist.
9. Fasten conduit securely to boxes with locknuts and bushings to provide good
grounding continuity.
10. Install pull cords/line within any spare or unused conduits of sufficient length to
facilitate future cable installation.
11. Penetrations
a. Locate penetrations within structural members as shown on Drawings and as
directed by Engineer. Should it be necessary to notch any framing member,
make such notching only at locations and in a manner as approved by
Engineer.
b. Do not chase concrete or masonry to install conduit unless specifically
approved by Engineer.
c. Cutting or holes
1) Install sleeves for cast-in-place concrete floors and walls. After installing
conduit through penetration, seal using dry-pack grouting compound
(non-iron bearing, chloride free and non-shrinking) or fire rated assembly
if rated floor or wall. Use escutcheon plate on floor underside to contain
compound as necessary.
2) Cut holes with a hole saw for penetrations through non-concrete or non-
masonry members.
3) Provide chrome plated escutcheon plates at all publicly exposed wall,
ceiling and floor penetrations.
d. Sealing
1) Non-rated penetration openings shall be packed with non-flammable
insulating material and sealed with gypsum wallboard taping compound.
RACEWAYS AND BOXES
26 05 33-9
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2) Fire rated penetration shall be sealed using a UL classified fire stop
assembly suitable to maintain the equivalent fire rating prior to the
penetration.
3) Use escutcheon plates to hold sealing or fire rated compound as
necessary.
e. Waterproofing
1) Make penetrations through any damp-proofed/waterproofed surfaces
within damp/wet locations as such as to maintain integrity of surface.
2) Install specified watertight conduit entrance seals at all below grade wall
and floor penetrations.
3) At roof penetrations furnish roof flashing, counter flashing and pitch-
pockets compatible to roof assembly.
4) Where possible conduits that horizontally penetrate a waterproof
membrane shall fall away from and below the penetration's exterior side.
5) Make penetrations through floors watertight with mastic, even when
concealed within walls or furred spaces.
12. Supports
a. Conduits shall be support and braced per OSHPD pre-approved anchorage
systems when those methods are implemented and installed.
b. Sizes of rods and cross channels shall be capable of supporting 4 times and
5 times actual load, respectively. Anchorage shall support the combined
weight of conduit, hanger and conductors.
c. Support individual horizontal conduit 1 1/2" and smaller by means of 2 hole
straps or individual hangers.
d. Galvanized iron hanger rods sizes 1/4" diameter and larger with spring steel
fasteners, clips or clamps specifically design for that purpose for 1 1/2"
conduits and larger.
e. Support multi-parallel horizontal conduits runs with trapeze type hangers
consisting of 2 or more steel hanger rods, preformed cross channels, `J' bolts,
clamps, etc.
f. Support conduit to wood structures by means of bolts or lag screws in shear,
to concrete by means of insert or expansion bolts and to brickwork by means
of expansion bolts.
g. Support multi-parallel vertical conduits runs with galvanized Unistrut, Power-
Strut or approved equal type supports anchored to wall. Where multi-floored
conduits pass through floors, install riser clamps at each floor.
RACEWAYS AND BOXES
26 05 33-10
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
h. Maximum conduit support spacing shall be in accordance with NECA
Standard of Installation:
1) Horizontal runs:
a) 3/4" and smaller at 60" on centers, unless building construction
prohibits otherwise, then 84" on centers.
b) 1" and larger at 72" on centers, unless building construction prohibits
otherwise or any other condition, then 120" on centers.
2) Vertical runs:
a) 3/4" and smaller @ 84" on centers.
b) 1" and 1 1/4" @ 96" on centers.
c) 1 1/2" and larger @ 120" on centers.
d)Any vertical condition such as shaftways and concealed locations for
any sized conduit, 120" on centers.
i. Anchorage for RMC/IMC supports unless otherwise specified:
1) < 1" IMC/RMC = #10 bolt/screw.
2) 1" IMC/RMC = 1/4" bolt/screw.
3) 1 1/2" and 2" IMC/RMC = 3/8" bolt/screw.
4) 3" IMC/RMC, 4" EMT = 1/2" bolt/screw.
5) > 3"IMC/RMC = 5/8" bolt/screw.
j. Anchorage for EMT supports unless otherwise specified:
1) < 1 1/2" EMT = #10 bolt/screw.
2) 1 1/2" EMT = 1/4" bolt/screw.
3) 2, 2 1/2" and 3" EMT = 3/8" bolt/screw.
4) 4" EMT = 1/2" bolt/screw.
5) > 4"EMT = 5/8" bolt/screw.
B. Boxes
1. Install boxes as shown on Drawings and as required for splices, taps, wire
pulling, equipment connections and Code compliance.
RACEWAYS AND BOXES
26 05 33-11
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2. Install additional pull boxes, not shown on Drawings, in sufficient quantities to
facilitate pulling of conductors and cables such that total spacing does not
exceed 150 feet or 270 degrees, total; and maximum pulling tension will not be
exceeded.
3. Install plaster rings on all outlet boxes in stud walls or in furred, suspended or
exposed ceilings. Covers shall be of a depth suited for installation.
4. Provide gasketed cast metal cover plates where boxes are exposed in damp or
wet locations
5. Install access door for boxes installed within concealed locations without access.
6. Install approved factory made knockout seal where knockouts are not present.
7. Refer to Architectural interior elevations and details shown for exact mounting
heights of all electrical outlets. In general, locate outlets as shown or specific
and complies with Americans with Disabilities Act:
a. Convenience outlets: +18"AFF or +6" above counter or splash.
b. Local switches: +48"AFF or +6" above counter or splash.
c. Telecommunication outlets: +18"AFF or +48"AFF for wall telephone or
intercom device.
d. Verify all mounting heights with Drawings, and where heights are not suited
for construction or finish please consult Engineer.
8. Use conduit bodies to facilitate pulling of conductor or cables or change conduit
direction. Do not splice within conduit bodies.
9. Enclose pull box with additional rated gypsum board as necessary to maintain
wall's original fire rating.
10. Install galvanized steel coverplates on all open boxes within dry listed areas.
11. Install in-ground pull holes/boxes flush to grade finish at finished areas or 1"
above finished landscaped grade. Seal all conduits terminating in pull hole/box
watertight. Install and grout around bell ends where shown. Cover and lids shall
be removable without damage to adjacent finish surfaces.
12. Support
a. Accurately place boxes for finish, independently and securely supported by
adequate blocking or manufacturer channel type heavy-duty box hangers for
stud walls. Do not use nails to support boxes.
b. Support boxes independent of conduit system.
c. Mount boxes installed within ceilings to 16 gauge metal channel bars
attached to main runners or joists.
RACEWAYS AND BOXES
26 05 33-12
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
d. Support boxes within suspended acoustical tile ceilings directly from structure
above when light fixture are to be installed from box.
e. Use auxiliary plates, bar or clips and grouted in place for masonry, block or
pour-in-place concrete construction.
3.4 APPLICATION
A. Conduit
1. RMC/IMC suitable for all damp, dry and wet locations except when in contact
with earth. IMC not suitable for hazardous locations as stated within CEC.
2. CRMC suitable for damp or wet locations, concealed within concrete or in contact
with earth.
3. EMT suitable for exposed or concealed dry, interior locations.
4. PVC/RTRC suitable for beneath ground floor slab, except when penetrating, and
direct earth burial. Do not run exposed within concrete walls or in floor slab
unless indicated on Drawings or per Engineer's permission.
5. FMC suitable for dry locations only for connections to motors, transformers,
vibrating equipment/machinery, controllers, valves, switches and light fixtures in
less than 6 foot lengths.
6. LFMC application same as FMC above but for damp or wet locations.
B. Termination and joints
1. Use raceway fittings compatible with associated raceway and suitable for the
location.
2. Raceways shall be joined using specified couplings or transitions where
dissimilar raceway systems are joined.
3. Conduits shall be securely fastened to cabinets, boxes and gutters using (2) two
locknuts and insulating bushing or specified insulated connector. Where joints
cannot be made tight and terminations are subject to vibration, use bonding
jumpers, bonding bushings or wedges to provide electrical continuity of the
raceway system. Use insulating bushings to protect conductors where subjected
to vibration or dampness. Install grounding bushings or bonding jumpers on all
conduits terminating at concentric or eccentric knockouts.
4. Terminations exposed at weatherproof enclosures and cast outlet boxes shall be
made watertight using specified connectors and hubs.
5. Stub freestanding equipment conduits through concrete floors for connections
with top of coupling set flush with finished floor. Install plugs to protect threads
and entrance of debris.
RACEWAYS AND BOXES
26 05 33-13
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
6. Install specified cable sealing bushings on all conduits originating outside the
building walls and terminating within interior switchboard, panel, cabinet or
gutters. Install cable sealing bushings or raceway seal for conduit terminations in
all grade level or below grade exterior pull, junction or outlet boxes.
7. Where conduits enter building from below grade inject into filled raceways pre-
formulated rigid 2 lbs. density polyurethane foam suitable for sealing against
water, moisture, insects and rodents.
8. Install expansion fitting or expansion/deflection couplings per manufacturer's
recommendations where:
a. Any conduit that crosses a building structure expansion joint; secure conduit
on both sides to building structure and install expansion fitting at joint.
b. Any conduit that crosses a concrete expansion joint; install
expansion/deflection at joint.
c. Any conduit greater than 1-1/4" is routed along roof top in runs greater than
100 feet; install expansion fittings every 100 feet.
d. Engineer may allow FMC or LFMC in lieu of expansion fitting or
expansion/deflection couplings on conduits 2" and smaller within accessible
locations upon further review and written consent.
C. Boxes
1. Standard type suitable for all flush installations and all dry concealed locations.
2. Concrete type suitable for all flush concrete installations.
3. Masonry type suitable for all flush concrete and block installations.
4. Surface cast meta type suitable for all exposed damp and wet surface mounted
locations, and dry surface mounted locations less than 96" from finished floor
END OF SECTION
RACEWAYS AND BOXES
26 05 33-14
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 26 05 53
ELECTRICAL IDENTIFICATION
PART GENERAL
1.1 SUMMARY
A. Section includes requirements for:
1. Identifying electrical, instrumentation, and process equipment and
components.
2. Material, manufacturing, and installation requirements for identification
devices.
B. Related Sections:
1. Contract Documents are a single integrated document, and as such all
Divisions and Sections apply. It is the responsibility of the CONTRACTOR
and its subcontractors to review all sections to ensure a complete and
coordinated project.
1.2 REFERENCES
A. Refer to Section 26 05 00.
1.3 DEFINITIONS
A. Refer to Section 26 05 00.
1.4 SYSTEM DESCRIPTION
A. Nameplates:
1. Provide a nameplate for each control device or major item of electrical
equipment, either located in the field or within panels.
2. Provide all nameplates of identical style, color, and material throughout the
facility.
3. Device nameplates information:
a. Designations as indicated on the Drawings and identified on the
Process and Instrumentation Drawings.
b. Device tag and loop number ID (e.g. EDV-60.0101.01).
c. Circuit ID (e.g. LPA-11).
d. Area served (e.g. Lighting Chemical Building).
ELECTRICAL IDENTIFICATION
26 05 53-1
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
B. Wire Numbers:
1. Coordinate the wire numbering system with all vendors of equipment so that
every field wire has a unique number associated with it for the entire system:
a. Wire numbers shall correspond to the wire numbers on the control
drawings or the panel and circuit numbers for receptacles and lighting.
b. Wire numbers shall correspond to the terminal block number to which
they are attached in the control panel.
c. Internal panel wires on a common terminal shall have the same wire
number.
d. All instrumentation cables shall be identified at pull points as
described above.
2. Provide the following wiring numbering schemes throughout the project for
field wires between Process Control Module, (PCM), Vendor Control
Panels, (VCP), Motor Control Centers, (MCC), field starters, field
instruments, etc.
(ORIGIN LOC.)-(ORIGIN TERM.)/(DEST. LOC.)-(DEST. TERM.)
OR
(ORIGIN LOC.)—(ORIGIN TERM.)
(DEST. LOC.)—(DEST. TERM.)
Where:
ORIGIN LOC. = Designation for originating panel or device
ORIGIN TERM. = Terminal designation at originating panel or device
DEST. LOC. = Designation for destination panel or device
DEST. TERM. = Terminal designation at destination panel or device or PLC
1/0 address at destination panel
a. Identify equipment and field instruments as the origin.
b. PCM's are always identified as the destination.
C. Location is the panel designation for VCP, LCP, or PCM. For
connections to MCC's, location is the specific starter tag and loop
number. Location is the tag and loop number for motor starters, field
instruments and equipment. Any hyphen in the panel designation or
ELECTRICAL IDENTIFICATION
26 05 53-2
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
tag and loop number shall be omitted.
d. Terminal designation is the actual number on the terminal block
where the conductor terminates at field devices and vendor control
panels. For multiconductor cables, all terminal numbers shall be
shown, separated by commas.
e. Terminal designations at motor leads shall be the motor
manufacturer's standard terminal designation (e.g.T1, T2, T3, etc.).
f. Terminal designations at PCM's where the field conductor connects to
a PLC input or output shall be the PLC address (Note: the following
PLC 1/0 numbering scheme is typical for Allen Bradley, the numbering
scheme should be modified to match that of the actual PLC
manufacturer used for the project):
1) Discrete Point: W:X:Y/Z
Analog Point: W:X:Y.Z
Where:
W = I for input, O for output
X = PLC number (1, 2, 3...)
Y = Slot number (01, 02, 03...)
Z = Terminal number (00,01,02...) for a discrete point
or a word number for an analog point (1,2,3...)
g. Terminal designations at PCM's where the conductor does not
connect to a PLC 1/0 point shall be the terminal number with a "C"
prefix (e.g. 010). For common power after a fuse or neutrals after a
switch, the subsequent points shall have and capital letter suffix
starting with "A" (e.g.. C0010A).
3. Case 1: Vendor Control Panel (VCP) to Process Control Module (PCM):
Field Wire Number/Label: A-B/C-D
A = Vendor Control Panel number without hyphen (VCP60.0101.01)
B = Terminal number within VCP (manufacturer's or vendor's standard
terminal number)
C = Process Control Module number without hyphen (PCM60.0101)
D = Either the PLC address if the field terminal is connected directly to a PLC
input or output point or the terminal number with a "C" prefix if not
connected directly to a PLC 1/0 point (C0010)
ELECTRICAL IDENTIFICATION
26 05 53-3
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
Examples: VCP60.0101.01-10/PCM60.0101-1:1:01/01
VCP60.0101.01-10/PCM60.0101-0:1:10/07
VCP60.0101.01-10/PCM60.0101-00100
4. Case 2: Field Instrument to Process Control Module
(PCM): Field Wire Number/Label: E-F/C-D
C = Process Control Module number without hyphen (PCM60.0101)
D = Either the PLC address if the field terminal is connected directly to a
PLC input or output point or the terminal number with a "C" prefix if not
connected directly to a PLC 1/0 point (C0010)
E = Field mounted instrument tag and loop numbers without hyphen
(EDV60.0101.01)
F = Manufacturer's standard terminal number within instrument. Use
both terminal numbers for analog points separated by a comma
Examples: TIT60.0101.01-2,3/PCM60.0101-1:1:01.1
TSH60.0101-1/PCM60.0101-1:2:01/00
5. Case 3: Motor Control Center (MCC) to Process Control Module
(PCM): Field Wire Number/Label: G-B/C-D
B = Terminal number within Motor Control Center (manufacturer's or
vendor's standard terminal number)
C = Process Control Module without hyphen (PCM60.0101)
D = Either the PLC address if the field terminal is connected directly to a PLC
input or output point or the terminal number with a "C" prefix if
not connected directly to a PLC 1/0 point (C0010)
G = Actual starter designation in the Motor Control Center without hyphen
(MMS60.0101)
Examples: MMS60.0101-10/PCM60.0101-1:1:01/01
MMS60.0101-10/PCM60.0101-0:1:10/07
MMS60.0101-10/PCM60.0101-00100
6. Case 4: Motor Control Center (MCC) to Vendor Control Panel
(VCP): Field Wire Number/Label: G-B/A-B
ELECTRICAL IDENTIFICATION
26 05 53-4
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
A = Vendor Control Panel number without hyphen (VCP60.0101.01)
B = Terminal number within motor control center or vendor control panel
(manufacturer's or vendors standard terminal number)
G = Actual starter designation in the Motor Control Center without hyphen
(MMS60.0101)
Example: MMS60.0101-X2/VCP60.0101.01-10
7. Case 5: Motor leads to a Motor Control Center (MCC): Field Wire
Number/Label: H-I/G-B
B = Terminal number within motor control center (manufacturer's
standard terminal number)
G = Actual starter designation in the Motor Control Center without hyphen
(MMS60.0101)
H = Equipment tag and loop number without hyphen (PMP60.0101.01)
I = Motor manufacturer's standard motor lead identification (e.g.T1, T2,
T3, etc.)
Example: PMP-60.0101.01-T3/MMS60.0101.01-T3
8. Case 6: Remote or separately mounted starter or Variable Frequency Drive
(VFD) to Process Control Module (PCM): Field Wire Number/Label: J-B/C-D
B =Terminal number within starter or Variable Frequency Drive (manufacturer's
standard terminal number)
C = Process Control Module number without hyphen (VCP60.0101.01)
D = Either the PLC address if the field terminal is connected directly to a
PLC input or output point or the terminal number with a "C" prefix if not
connected directly to a PLC 1/0 point (C0010)
J = Starter or Variable Frequency Drive tag and loop number without hyphen
(MMS60.0101)
Examples: MMS60.0101-10/PCM60.0101.01-1:1:01/01
MMS60.0101-10/PCM60.0101.01-0:2:10/07
MMS60.0101-10/PCM60.0101.01-00010
ELECTRICAL IDENTIFICATION
26 05 53-5
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
9. Terminate all spare conductors on terminal blocks and identify as required
for other field wires with an "S" prefix:
Example: S MMS60.0101-10/PCM60.0101.01-0011
1.5 SUBMITTALS
A. Furnish submittals in accordance with Section 26 05 00.
B. Product Data:
1. Nameplates:
a. Color.
b. Size:
1) Outside dimensions.
2) Lettering.
C. Material.
d. Mounting means.
2. Nameplate Schedule:
a. Show exact wording for each nameplate.
b. Include nameplate and letter sizes.
3. Wire Numbers:
a. Manufacturer's catalog data for wire labels and label
printer.
C. Record Documents:
1. Update the conduit schedule to reflect the exact quantity of wire numbers
including spares and destination points for all wires.
1.6 QUALITY ASSURANCE
A. Schedule a pre-installation conference in accordance with Section 26 05 00 in
order to clearly define the requirements specified for equipment identification:
1. Representatives of the CONTRACTOR, OWNER, and ENGINEER shall
convene before any major purchases of cable or conductors and before the
installation or termination of any cables or conductors.
1.7 DELIVERY, STORAGE, AND HANDLING
ELECTRICAL IDENTIFICATION
26 05 53-6
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
A. Refer to Section 26 05 00.
1.8 WARRANT
A. Refer to Section 26 05 00.
1.9 SYSTEM START UP
A. Refer to Section 26 05 00.
PART2 PRODUCTS
2.1 MANUFACTURERS
A. Nameplates and Signs:
1. One of the following or equal:
a. Brady.
b. Seton.
B. Conductor and Cable Markers:
1. Heat-shrinkable tubing:
a. One of the following or equal:
1) Raychem.
2) Brady.
3) Thomas & Betts.
4) Kroy.
C. Conduit and Raceway Markers:
1. One of the following or equal:
a. Almetek: Almetek type mini-tag.
b. Lapp Group: Maxi System
D. Medium Voltage Raceway Voltage Labels:
1. One of the following or equal:
a. Brady.
ELECTRICAL IDENTIFICATION
26 05 53-7
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
b. Seton.
2.2 MATERIALS
A. Nameplates:
1. Fabricated from white-center and red or black face laminated plastic
engraving stock:
a. 3/32-inch thick material.
b. Two-ply.
c. With chamfered edges.
d. Block style engraved characters of adequate size to be read easily from
a distance of 6 feet:
1) No characters smaller than 1/8-inch in height.
B. Signs:
1. Automatic equipment and high voltage signs:
a. Suitable for exterior use.
b. In accordance with OSHA regulations.
C. Conductor and Cable Markers:
1. Machine printed black characters on white tubing.
2. Ten point type or larger.
D. Conduit and Raceway Markers:
1. UV resistant holder and letters.
2. Black letters on yellow background.
3. Minimum 1/2-inch high letters.
E. Medium Voltage Circuit Raceway Labels:
1. Vinyl plastic.
2. Minimum 1-inch high letters.
2.3 SOURCE QUALITY CONTROL
A. Nameplates:
ELECTRICAL IDENTIFICATION
26 05 53-8
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1. Provide all nameplates for control panel operator devices (e.g. pushbuttons,
selector switches, pilot lights, etc.):
a. Same material and same color and appearance as the device
nameplates, in order to achieve an aesthetically consistent and
coordinated system.
PART 3 EXECUTION
3.1 INSTALLATION
A. Refer to Section 26 05 00.
B. Nameplates:
1. Attach nameplates to equipment with rivets, bolts or sheet metal screws,
approved waterproof epoxy-based cement or install in metal holders welded
to the equipment.
2. On NEMA 4or NEMA 4X enclosures, use epoxy-based cement to attach
nameplates.
3. Nameplates shall be aligned and level or plumb to within 1/64 inch over the
entire length:
a. Misaligned or crooked nameplates shall be remounted, or provide new
enclosures at the discretion of the ENGINEER.
C. Conductor and Cable Markers:
1. Apply all conductor and cable markers before termination.
2. Heat-shrinkable tubing:
a. Tubing shall be shrunk using a heat gun that produces low temperature
heated air.
b. Tubing shall be tight on the wire after it has been heated.
c. Characters shall face the open panel and shall read from left to right or
top to bottom.
d. Marker shall start within 1/32 inch of the end of the stripped insulation
point.
D. Conduit Markers:
1. Furnish and install conduit markers for every conduit in the electrical system
ELECTRICAL IDENTIFICATION
26 05 53-9
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
that is identified in the conduit schedule or part of the process system:
a. Conduit markings shall match the conduit schedule; refer to Section
26 05 53.
2. Mark conduits at the following locations:
a. Each end of conduits that are greater than 10 feet in length.
b. Where the conduit penetrates a wall or structure.
c. Where the conduit emerges from the ground, slab, etc.
d. The middle of conduits that are 10 feet or less in length.
3. Mark conduits after the conduits have been fully painted.
4. Position conduit markers so that they are easily read from the floor.
5. Secure all conduit markers with nylon cable ties:
a. Provide with ultraviolet resistant cable ties for conduit markers exposed
to direct sunlight.
b. Adhesive labels are not acceptable.
6. Mark conduits before construction review by ENGINEER for punch list
purposes.
E. Medium Voltage Raceway Labels:
1. Apply at 50 foot intervals stating the voltage level contained within the
raceway.
F. Signs and Labeling:
1. Furnish and install permanent warning signs at mechanical equipment that
may be started automatically or from remote locations:
a. Fasten warning signs with round head stainless steel screws or bolts.
b. Locate and mount in a manner to be clearly legible to operations
personnel.
2. Furnish and install permanent and conspicuous warning signs on equipment
(front and back), doorways to equipment rooms, pull boxes, manholes, etc.
where the voltage exceeds 600 volts.
3. Furnish and install warning signs on equipment that has more than one
ELECTRICAL IDENTIFICATION
26 05 53-10
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
source of power.
a. Warning signs to identify every panel and circuit number of the
disconnecting means of all external power sources.
4. Place warning signs on equipment that has 120 VAC control voltage source
used for interlocking.
a. Identify panel and circuit number or conductor tag for control voltage
source disconnecting means.
3.2 FIELD QUALITY CONTROL
A. Replace any nameplates, signs, conductor markers, cable markers, or raceway
labels that in the sole opinion of the ENGINEER do not meet the ENGINEER's
aesthetic requirements.
END OF SECTION
ELECTRICAL IDENTIFICATION
26 05 53-11
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 26 18 11
OVERCURRENT PROTECTION DEVICES
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes
1. Provide all labor, materials and equipment necessary to complete the installation
required for the items specified under this Section, including but not limited to
overcurrent protection devices.
B. Related sections
1. Where items specified in other Division 26 sections conflict with the requirements
of this Section, the most stringent requirement shall govern.
2. The requirements of this Section apply to all Division 26 work, as applicable.
3. Consult all other sections, determine the extent and character of related work
and properly coordinate work specified herein with that specified elsewhere to
produce a complete installation.
1.2 REFERENCES
A. Comply with the latest edition of the following applicable specifications and standards
except as otherwise shown or specified:
1. CCR—California Code of Regulations, Title 24
a. Part 3 -California Electrical Code(CEC); NFPA 70 National Electrical Code
(NEC)with California amendments
2. Federal Specification
a. W-C-375; Circuit Breakers, Molded Case, Branch Circuit And Service
3. NEMA—National Electrical Manufacturer's Association
a. AB 1; Molded-Case Circuit Breakers, Molded Case Switches, and Circuit-
Breaker Enclosures
b. PB 2.2; Application Guide for Ground Fault Protective Devices for Equipment
4. UL -Underwriters Laboratories, Inc.
a. 248; Low Voltage Fuses
b. 468; Wire Connectors
OVERCURRENT PROTECTION DEVICES
26 18 11-1
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
c. 508E; IEC Type "2" Coordination Short Circuit Tests
d. 489; Molded-Case Circuit Breakers and Circuit Breaker Enclosures
e. 943; Standard for Ground-Fault Circuit-Interrupters
1.3 SUBMITTALS
A. Submit manufacturer's data for materials specified within this Section in accordance
to Section 26 05 00.
B. Production test of circuit breakers upon request of Engineer.
C. Submittal shall show the following information: circuit breaker numbering, circuit
breaker type and short circuit rating, provisions for future circuit breakers, bussing,
including neutral and ground, ratings and enclosure dimensions and trims.
1.4 QUALITY ASSURANCE
A. All materials, equipment and parts comprising the materials specified herein shall be
new and unused, bearing UL labels where applicable.
B. The manufacturing facility shall be registered by Underwriters Laboratories Inc. to the
International Organization for Standardization ISO 9002 Series Standards for quality.
1.5 DELIVERY, STORAGE AND HANDLING
A. Handle carefully to avoid damage to internal components, enclosure and finish.
B. Store in a clean, dry environment. Maintain factory packaging and, if required,
provide an additional cover to protect enclosure in harsh environments.
PART2 - PRODUCTS
2.1 FUSES
A. All power distribution fuses shall be time-delay, high interrupting (200kAIC minimum)
and current limiting type, unless otherwise indicated. All fuses shall be of same
manufacturer and model.
1. Motor branch circuit fuses (0 — 600A): UL Class RK5 dual element, time delay
type shall be size for UL 508E "Type 2" coordination for the motor controller.
Coordinate fuse selection with motor starter overload relay heaters as required.
2. General purpose feeder fuses (0 — 600A): UL Class RK1 dual element, time
delay type shall be size per Drawings.
B. Control and instrumentation fuses shall of type and rating as recommended by
equipment manufacturer, suitable for fuse blocks or holders installation.
OVERCURRENT PROTECTION DEVICES
26 18 11-2
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2.2 MOLDED CASE CIRCUIT BREAKERS
A. General
1. Circuit breakers shall be constructed using glass reinforced insulating material.
Current carrying components shall be completely isolated from the handle and
the accessory mounting area.
2. Circuit breakers shall have an over center, trip free, toggle operating mechanism
which will provide quick-make, quick-break contact action. The circuit breaker
shall have common tripping of all poles.
3. The circuit breaker handle shall reside in a tripped position between ON and OFF
to provide local trip indication.
4. The maximum ampere rating and UL, IEC, or other certification standards with
applicable voltage systems and corresponding interrupting ratings shall be clearly
marked on face of circuit breaker after installation.
5. Circuit breakers shall have an RMS interrupting capacity not less than shown on
Drawings, or if not shown shall not be less than:
a. 25kA for 480V systems
b. 22kA for 240V (or less) systems
6. Each circuit breaker shall be equipped with a push-to-trip button, located on the
face of the circuit breaker to mechanically operate the circuit breaker tripping
mechanism for maintenance and testing purposes.
7. Circuit breakers shall be equipped with UL Listed electrical accessories as noted
on Drawing. Circuit breaker handle accessories shall provide provisions for
locking handle in the ON and OFF position.
8. All circuit breakers shall be UL Listed for reverse connection without restrictive
line and load markings and be suitable for mounting in any position.
9. Circuit breakers shall be constructed with factory installed mechanical lugs. All
circuit breakers shall be UL Listed to accept field installable/removable
mechanical type lugs. Lug body shall be bolted in place; snap in design not
acceptable. All lugs shall be UL Listed to accept solid (not larger than #8 AWG)
and/or stranded copper and aluminum conductors. Lugs shall be suitable for
90°C rated wire, sized according to the 750C temperature rating in the CEC.
10. All circuit breakers shall be capable of accepting bus connections.
B. Thermal-Magnetic Circuit Breakers
1. Circuit breakers shall have a permanent trip unit containing individual thermal
and magnetic trip elements in each pole.
OVERCURRENT PROTECTION DEVICES
26 18 11-3
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2. Thermal trip elements shall be factory preset and sealed. Circuit breakers shall
be true RMS sensing and thermally responsive to protect circuit conductor(s) in a
400C ambient temperature.
3. Circuit breaker frame sizes above 100 amperes shall have a single magnetic trip
adjustment located on the front of the circuit breaker.
4. Provide equipment ground fault protection where shown on Drawing with the
following features.
a. Ground fault sensing system shall be modified zero sequence sensing type
and not require any external power to trip the circuit breaker.
b. The ground fault sensing system shall be suitable for use on grounded
systems. The ground fault sensing system shall be suitable for use on three-
phase, three-wire circuits where the system neutral is grounded but not
carried through the system or on three-phase, four-wire systems.
c. Ground fault pickup current setting and time delay shall be field adjustable. A
switch shall be provided for setting ground fault pickup point. A means to seal
the pickup and delay adjustments shall be provided.
d. The ground fault sensing system shall include a ground fault memory circuit
to sum the time increments of intermittent arcing ground faults above the
pickup point.
e. A means of testing the ground fault system to meet the on-site testing
requirements of CEC 230.95 (C) shall be provided.
f. Local visual ground fault trip indication shall be provided.
g. The ground fault sensing system shall be provided with Zone Selective
Interlocking (ZSI) communication capabilities compatible with other thermal
magnetic circuit breakers equipped with ground fault sensing, electronic trip
circuit breakers with integral ground fault sensing and external ground fault
sensing systems as noted on Drawings.
C. Electronic Trip Circuit Breakers
1. Circuit breaker trip system shall be a microprocessor-based true RMS sensing
design with sensing accuracy through the thirteenth (13th) harmonic. Sensor
ampere ratings shall be as indicated on Drawings.
2. The integral trip system shall be independent of any external power source and
shall contain no less than industrial grade electronic components.
3. The ampere rating of the circuit breaker shall be determined by the combination
of an interchangeable rating plug, the sensor size and the long-time pickup
adjustment on the circuit breaker. The sensor size, rating plug and adjustment
positions shall be clearly marked on the face of the circuit breaker. Circuit
OVERCURRENT PROTECTION DEVICES
26 18 11-4
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
breakers shall be UL Listed to carry 80% (or 100% where noted on Drawings) of
their ampere rating continuously.
4. The following time/current response adjustments shall be provided. Each
adjustment shall have discrete settings and shall be independent of all other
adjustments.
a. Instantaneous Pickup
b. Long Time Pickup
c. Long Time Delay
d. Short Time Pickup
e. Short Time Delay
f. Ground Fault Pickup (when specified with ground fault protection)
g. Ground Fault Delay (when specified with ground fault protection)
5. A means to seal the trip unit adjustments in accordance with CEC 240.6 (B) shall
be provided.
6. Local visual trip indication for overload, short circuit and ground fault trip
occurrences shall be provided.
7. An ammeter to individually display all phase currents flowing through the circuit
breaker shall be provided. All current values shall be displayed in true RMS with
2% accuracy.
8. Long Time Pickup indication to signal when loading approaches or exceeds the
adjusted ampere rating of the circuit breaker shall be provided.
9. The trip system shall include a Long Time memory circuit to sum the time
increments of intermittent overcurrent conditions above the pickup point. Means
shall be provided to reset Long Time memory circuit during primary injection
testing.
10. An ammeter to individually display all phase currents flowing through the circuit
breaker shall be provided. Indication of inherent ground fault current flowing in
the system shall be provided on circuit breakers with integral ground fault
protection. All current values shall be displayed in true RMS with 2% accuracy.
11. Circuit breakers shall be equipped with back-up thermal and magnetic trip
system.
12. Equipment Ground Fault Protection shall be provided where noted on Drawings.
a. Circuit breakers shall be provided with integral equipment ground fault
protection for grounded systems. The circuit breaker shall be suitable for use
OVERCURRENT PROTECTION DEVICES
26 18 11-5
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
on three-phase, three-wire circuits where the system neutral is grounded but
not carried through the system or on three-phase, four-wire systems.
b. A separate neutral current transformer shall be provided for three-phase,
four-wire systems.
c. Ground fault sensing system shall be residual sensing type.
d. The trip system shall include a ground fault memory circuit to sum the time
increments of intermittent ground faults above the pickup point.
e. A means of testing the ground fault system to meet the on-site testing
requirements of CEC 230.95 (C) shall be provided.
f. Local visual trip indication for a ground fault trip occurrence shall be provided.
g. The ground fault sensing system shall be provided with Zone Selective
Interlocking (ZSI) communication capabilities compatible with other thermal
magnetic circuit breakers equipped with ground fault sensing, electronic trip
circuit breakers with integral ground fault sensing and external ground fault
sensing systems as noted on Drawings.
13. Circuit breaker trip system shall be equipped with an externally accessible test
port. Disassembly of the circuit breaker shall not be required for testing. Test set
shall be capable of verifying the operation of all trip functions with or without
tripping the circuit breaker.
PART 3 - EXECUTION
3.1 PREPARATION
A. Notify Engineer no later than 10 working days for adjustable circuit breaker settings
not shown within Drawings. Submit to Engineer the following information:
1. Panel, switchboard name/ID
2. Circuit breaker identifier (i.e., main circuit breaker, load served, etc.)
3. List of necessary settings (i.e., trip settings, time delays, etc.)
3.2 INSTALLATION
A. Install equipment and their accessories in to manufacturer's instructions, pertinent
Codes, and with recognized industry practices to insure device operates properly.
B. Tighten electrical connectors and terminals in accordance to manufacturer's
requirements. Where the manufacturer does not have published torque tightening
values, comply with the requirements of UL 468.
OVERCURRENT PROTECTION DEVICES
26 18 11-6
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3.3 FIELD QUALITY CONTROL
A. Check tightness of circuit breaker connections using a calibrated torque wrench or
torque screwdriver per manufacturer's written specifications.
B. Contractor to obtain the services of an independent testing company who shall
provide quality control and adjustments as well as tests for
1. Check each circuit breaker above 100A on a 225A frame for long-time and short-
time delay pickup and instantaneous pickup.
a. Instantaneous pickup current shall be determined by 4 cycles or less.
b. b. Perform timing test with 300% of breaker trip unit rated current.
c. Adjust unit if required, so that the tripping characteristics are within the limits
of the published time-current characteristic curves for that particular trip unit.
2. Test and calibrate ground fault protection trip and pickup time on 225A frame
breakers and larger.
C. Physically test key interlock systems to check for proper functionality.
D. Check and set where required all protective device settings in accordance with
approved coordination study settings and conduct ground fault acceptance tests.
3.4 ADJUSTING
A. Adjust all operating mechanisms for free mechanical movement per manufacturer's
specifications.
B. Adjust circuit breaker trip and time delay settings to values indicated as instructed by
Engineer.
1. Check each circuit breaker above 100A, long-time and short-time delay pickup
and instantaneous pickup. Instantaneous pickup current shall be determined by
4 cycles or less. Perform timing test with 300% of breaker trip unit rated current.
Adjust unit if required, so that the tripping characteristics are within the limits of
the published time-current characteristic curves for that particular trip unit.
2. Main circuit breaker ground fault setting shall be per CEC 230.95 (A) or as
directed by Engineer.
3.5 PROTECTION
A. When directed by Engineer provide physical means to "permanently fix" settings for
rotary and DIP type switches with a thin coat of clear lacquer.
OVERCURRENT PROTECTION DEVICES
26 18 11-7
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3.6 CLEANING
A. Remove marks, dirt and debris from installed equipment surfaces for "new like"
appearance.
END OF SECTION
OVERCURRENT PROTECTION DEVICES
26 18 11-8
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 26 27 26
WIRING DEVICES
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes
1. Provide all labor, materials and equipment necessary to complete the installation
required for the items specified under this Section, including but not limited to
wiring devices.
B. Related sections
1. Where items specified in other Division 26 sections conflict with the requirements
of this Section, the most stringent requirement shall govern.
a. 26 05 26 — Grounding and Bonding for Electrical Systems
2. The requirements of this Section apply to all Division 26 work, as applicable.
3. Consult all other sections, determine the extent and character of related work
and properly coordinate work specified herein with that specified elsewhere to
produce a complete installation.
1.2 REFERENCES
A. Comply with the latest edition of the following applicable specifications and standards
except as otherwise shown or specified:
1. Federal Specification
a. W-C-596; Connector, Electrical, Power, General Specification for
b. W-S-896; Switches, Toggle (Toggle and Lock), Flush Mounted (General
Specification)
2. NEMA—National Electrical Manufacturer's Association
a. WD 1; General Color Requirements for Wiring Devices
b. WD 6; Wiring Devices-Dimensional Requirements
3. UL -Underwriters Laboratories, Inc.
a. 20; General-Use Snap Switches
b. 498; Standard for Attachment Plugs and Receptacles
c. 943; Standard for Ground-Fault Circuit-Interrupters
WIRING DEVICES
26 27 26-1
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
d. 1449; Standard for Transient Voltage Surge Suppressors
1.3 SUBMITTALS
A. Submit manufacturer's data for materials specified within this Section in accordance
to Section 26 05 00.
1.4 QUALITY ASSURANCE
A. All materials, equipment and parts comprising the materials specified herein shall be
new and unused, bearing UL labels where applicable.
PART2 - PRODUCTS
2.1 SWITCHES
A. Wall switches
1. Specification grade, quiet, AC rated, mechanical, snap type with silver alloy
contacts, and shall comply with NEMA WD-1 and Fed. Spec W-S-896.
2. Rating shall be 20A at 120/277Vac, unless otherwise shown.
3. Handles shall be nylon; color shall be compatible with adjacent wall finish.
4. Manufacturers and types
a. Single pole, single throw
1) Cooper Wiring Devices #CS13120, Hubbell #CSB120, or equal.
b. Double pole, single throw
1) Cooper Wiring Devices #CSB220, Hubbell #CSB220, or equal.
c. Three way
1) Cooper Wiring Devices #CS13320, Hubbell #CSB320, or equal.
2.2 RECEPTACLES
A. Standards
1. Specification grade, NEMA 5-15R configuration grounding type, rated 15A at
125/250Vac that conform to NEMA WD-6 and Fed. Spec W-C-596.
2. At dedicated receptacle locations and as otherwise noted, use specification
grade, NEMA 5-20R configuration grounding type, rated 20A at 125/250Vac that
conform to NEMA WD-6 and when possible Fed. Spec W-C-596.
3. Specialty receptacles shall conform to NEMA WD-6 and UL standards as
applicable.
WIRING DEVICES
26 27 26-2
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
B. Color
1. General purpose receptacle face shall be nylon; color shall be compatible with
adjacent wall finish, unless otherwise indicated.
C. Receptacle types
1. General purpose single
a. Provide self-grounding back and side wired with binding head staked terminal
screw.
b. Use Cooper Wiring Devices #5261, Hubbell #5261, or equal for NEMA 5-
15R.
c. Use Cooper Wiring Devices #5361, Hubbell #5361, or equal for NEMA 5-
20R.
2. General purpose duplex
a. Provide self-grounding back and side wired with binding head staked terminal
screws and break-off strip for two circuit wiring.
b. Use Cooper Wiring Devices #5262, Hubbell #5262, or equal for NEMA 5-
15R.
c. Use Cooper Wiring Devices #5362, Hubbell #5362, or equal for NEMA 5-
20R.
3. Transient voltage surge suppressor (TVSS) duplex
a. Provide 20A, 125Vac receptacle consisting of NEMA 5-20R duplex device
with integral TVSS protection circuit.
b. Provide LED indicator to verify surge protection and ground, and audible
alarm to notify bad ground connection or surge protection expiration.
c. TVSS characteristics:
1) 400V clamping voltage.
2) 280J energy rating.
3) 150Vac RMS MOV rating
4) 18kA maximum surge current in all modes (L-N, L-G and N-G)
d. Use Cooper Wiring Devices #5362_S, no known equal.
4. Isolated ground
WIRING DEVICES
26 27 26-3
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
a. Provide receptacle specified within this Section with equipment grounding
contacts connected only to the green grounding screw terminal of the device
and with inherent electrical isolation from mounting strap.
5. Ground fault circuit interrupter (GFCI) duplex
a. Provide 20A, 125Vac receptacle consisting of NEMA 5-20R duplex device
with integral solid state sensing and signaling circuitry capable of detecting
and interrupting a maximum 5mA line-to-ground fault current in approximately
1/40th of a second per UL 943.
b. Provide visual device with trip indication, manual reset and test mechanisms
per UL 943.
c. Device shall be capable of point of use and multi-outlet protection.
d. Use Cooper Wiring Devices #XGF20, Hubbell #GF53, or equal.
6. Hospital grade and tamper resistant
a. Provide receptacle specified within this Section that conforms to UL 498
"Hospital Grade" requirements.
b. Tamper resistance receptacle shall have integral protection mechanism to
prevent accidental shock from foreign object contacting energized blades.
7. Special purpose
a. Provide specification grade devices with NEMA configuration, voltage,
ampacity, poles and ground provisions as noted on Drawings.
2.3 WALL PLATES
A. Interior locations
1. Finished Areas: 0.032" stainless steel, brushed or satin finish with required
number of openings for location.
2. Exposed Areas: galvanized, raised type.
B. Exterior: die-cast copper-free aluminum, gasketed, raintight cover UL listed for
exterior and wet locations while in use. Use Hubbell #WPBM (duplex), #WP26M
(GFCI) or equal.
C. Screws shall match plate.
D. Tamper resistance receptacles shall have exposed screws of tamper-resistant type.
E. Individual, gangable wall plates are not acceptable where two or more devices are
installed at one location.
WIRING DEVICES
26 27 26-4
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
PART 3 - EXECUTION
3.1 PREPARATION
A. Coordinate device heights with drawings and details.
B. Locate switches on latch side of door, unless otherwise indicated.
3.2 INSTALLATION
A. Mount and align device and wall plates level and plumb. Insure wall plates fit flat
against wall and tight against device without strain on plate.
B. Comply with manufacturer's instructions regarding termination of conductors to
wiring device.
C. Provide wall plates for all outlet boxes with devices.
D. Install blank wall plates on all outlet boxes in which no device is present or installed.
END OF SECTION
WIRING DEVICES
26 27 26-5
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 26 28 16
SAFETY SWITCHES AND INDIVIDUAL MOUNTED CIRCUIT BREAKERS
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes
1. Provide all labor, materials and equipment necessary to complete the installation
required for the items specified under this Section, including but not limited to
heavy duty fusible, non-fusible and double throw safety switches.
B. Related sections
1. Where items specified in other Division 26 sections conflict with the requirements
of this Section, the most stringent requirement shall govern.
a. 26 05 26 — Grounding and Bonding for Electrical Systems
b. 26 18 11 — Overcurrent Protection Devices
2. The requirements of this Section apply to all Division 26 work, as applicable.
3. Consult all other sections, determine the extent and character of related work
and properly coordinate work specified herein with that specified elsewhere to
produce a complete installation.
1.2 REFERENCES
A. Comply with the latest edition of the following applicable specifications and standards
except as otherwise shown or specified:
1. CCR—California Code of Regulations, Title 24
a. Part 3 -California Electrical Code(CEC); NFPA 70 National Electrical Code
(NEC) with California amendments
2. NEMA—National Electrical Manufacturer's Association
a. KS 1; Enclosed Switches
b. 250; Enclosures for Electrical Equipment
3. UL -Underwriters Laboratories, Inc.
a. 98; Enclosed and Dead Front Switches
b. 489; Molded-Case Circuit Breakers and Circuit Breaker Enclosures
SAFETY SWITCHES AND INDIVIDUAL MOUNTED CIRCUIT BREAKERS
26 28 16-1
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1.3 SUBMITTALS
A. Submit manufacturer's data for materials specified within this Section in accordance
to Section 26 05 00.
1.4 QUALITY ASSURANCE
A. All materials, equipment and parts comprising the materials specified herein shall be
new and unused, bearing UL labels where applicable.
1.5 DELIVERY, STORAGE AND HANDLING
A. Handle carefully to avoid damage to internal components, enclosure and finish.
B. Store in a clean, dry environment. Maintain factory packaging and, if required,
provide an additional cover to protect enclosure in harsh environments.
PART2 - PRODUCTS
2.1 MANUFACTURERS
A. Square D, Cutler Hammer or approved equal.
2.2 MATERIALS
A. Heavy-duty safety switches
1. Switch interior
a. All switches shall have switch blades which are visible when the switch is
OFF and the cover is open.
b. Lugs shall be front removable and UL Listed for 75°C conductors, aluminum
or copper.
c. 30A through 100A switches shall be equipped with factory or field installed
fuse pullers.
d. Switches required for Type 12, 12K or Type 4-4X-5 stainless steel
applications shall have all copper current carrying parts.
e. All current carrying parts shall be plated to resist corrosion.
f. Switches shall have removable arc suppressors to facilitate easy access to
line side lugs.
g. Switches shall have provisions for a field installable electrical interlock.
2. Switch mechanism
SAFETY SWITCHES AND INDIVIDUAL MOUNTED CIRCUIT BREAKERS
26 28 16-2
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
a. Switch operating mechanism shall be quick-make, quick-break such that,
during normal operation of the switch, the operation of the contacts shall not
be capable of being restrained by the operating handle after the closing or
opening action of the contacts has started.
b. The operating handle shall be an integral part of the box, not the cover.
c. Provisions for padlocking the switch in the OFF position with at least three
padlocks shall be provided.
d. The handle position shall travel at least 900 between OFF and ON positions
to clearly distinguish and indicate handle.
e. All switches shall have a dual cover interlock mechanism to prevent
unintentional opening of the switch cover when the switch is ON and prevent
turning the switch ON when the cover is open. The cover interlock
mechanism shall have an externally operated override but the override shall
not permanently disable the interlock mechanism. The tool used to override
the cover interlock mechanism shall not be required to enter the enclosure in
order to override the interlock.
3. Switch enclosures
a. All enclosures shall be NEMA 1 general purpose unless otherwise noted.
b. Switch covers shall be attached:
1) with welded pin-type hinges (Type 1, 12, 12K, 4-4X-5 stainless steel).
2) top hinged, attached with removable screws and securable in the open
position (Type 3R).
3) by molded hinges and type 316 stainless steel hinge pins (Type 4X
polyester).
4) by type 316 stainless steel bolts (Type 7/9).
c. The enclosure shall be finished with:
1) gray baked enamel paint which is electrodeposited on cleaned,
phosphate pre-treated steel (Type 1).
2) gray baked enamel paint which is electrodeposited on cleaned,
phosphate pre-treated galvannealed steel (Type 3R, 12, 12K).
3) a brush finish on type 304 stainless steel (Type 4-4X-5 stainless steel).
4) Gray baked enamel on copper free cast aluminum alloy (Type 7/9).
d. The enclosure shall have ON and OFF markings:
1) stamped into the cover (Type 1, 3R, 4-4X-5 stainless steel, 12, 12K).
SAFETY SWITCHES AND INDIVIDUAL MOUNTED CIRCUIT BREAKERS
26 28 16-3
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2) cast into the cover (Type 7/9).
3) inked on a adhesive label (Type 4X polyester).
e. The operating handle shall be provided with a dual colored, red/black position
indication.
f. All switches shall have provisions to accept up to three 3/8" hasp padlocks to
lock the operating handle in the OFF position.
4. Switch ratings
a. Switches shall be horsepower rated for ac and/or do as indicated on
Drawings.
b. The UL Listed short circuit current rating of the switches shall be:
1) 10,000 rms symmetrical amperes when used with or protected by Class H
or K fuses (30-600A).
2) 200,000 rms symmetrical amperes when used with or protected by Class
R or Class J fuses (30-600A switches employing appropriate fuse
rejection schemes).
3) 200,000 rms symmetrical amperes when used with or protected by Class
L fuses (800-1200A)
B. Double throw switches
1. Shall have the same characteristics as heavy-duty safety switches above for
switch interior, mechanism, enclosure and rating.
2. Additional switch operating mechanism characteristics shall be:
a. quick-make, quick-break for 60A through 200A, 2 pole and 3 pole devices.
b. Slow-make, slow-break for
1) 30A and greater than 200A, 2 pole and 3 pole devices.
2) 60A through 200A, 4 pole devices.
C. Individual Mounted Circuit Breakers
1. Circuit Breaker
a. Circuit breakers shall be of type, rating and poles shown on Drawings per
Section 26 18 11 —Overcurrent Protection Devices.
2. Enclosure
SAFETY SWITCHES AND INDIVIDUAL MOUNTED CIRCUIT BREAKERS
26 28 16-4
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
a. Enclosure shall be galvanized steel constructed in accordance with UL 50
requirements, and be NEMA 1, unless specifically shown or specified
otherwise.
PART 3 - EXECUTION
3.1 INSTALLATION
A. The equipment shall be installed per the manufacturer's recommendations.
B. Anchor safety switches to structural members and as shown on Drawings. Provide
additional support as required.
C. Mount safety switches level and plumb.
3.2 FIELD QUALITY CONTROL
A. Inspect complete installation prior to energizing for physical damage, proper
alignment, anchorage and grounding.
B. Check tightness of bolted connections per manufacturer's written specifications.
END OF SECTION
SAFETY SWITCHES AND INDIVIDUAL MOUNTED CIRCUIT BREAKERS
26 28 16-5
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 26 29 33
SOLID STATE REDUCED VOLTAGE CONTROLLER
PART 1 - GENERAL
1.1 SCOPE OF WORK
A. These specification requirements are for solid state reduced voltage motor controllers
herein referred to as soft starters or soft starts.
B. They are for use with NEMA design B, AC motors to reduce the current in-rush as well
as mechanical shocks that can result from starting or stopping a motor across the line.
1.2 QUALITY ASSURANCE
A. The electronic soft starter shall be listed by an independent testing laboratory in
accordance with UL 508 - Industrial Control Equipment.
B. The soft start shall carry the CE mark for indication of compliance to low voltage and
EMC directives in accordance with EN/IEC 60947-4-2.
C. The manufacturer shall be a certified ISO 9002 facility.
1.3 WARRANTY
A. An eighteen-month warranty shall be provided on materials and workmanship from date
of invoice.
PART2 - PRODUCTS
2.1 GENERAL DESCRIPTION
A. The soft starter shall be provided by the manufacturer factory mounted in an enclosure
rated as UL Type 3R for outdoor use.
1. Type 3R enclosures shall include a remote digital keypad for adjusting the soft
starter parameters either mounted on the door or with provisions to close the
enclosure door while the remote keypad is accessed externally.
2. Provisions shall be available for padlocking the enclosure door in the off position.
B. The enclosed product shall be provided complete with one of the following overcurrent
protective devices (OCPDs) for Type 1 short circuit protection:
1. Inverse-time circuit breaker disconnect means. Short circuit withstand rating shall
be 65 kA, @ 208, 230, 460 V.
C. The motor must be automatically protected from solid state component failure by one of
the following means:
SOLID STATE REDUCED VOLTAGE CONTROLLER
26 29 33-1
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1. Isolation contactor that opens when the motor is stopped or when the controller
detects a fault condition, including a shorted SCR condition.
D. The soft starter shall utilize at least two SCRs per phase to control the starting and
stopping of industry standard motors.
E. The soft starter shall be controlled by a microprocessor that continuously monitors the
current and controls the phasing of the SCRs. Analog control algorithms shall not be
allowed.
F. All soft starter power ratings shall utilize a common control board/module.
G. An internal shorting contactor shall be standard on soft starters in all enclosure
configurations. Protective features and deceleration control options integral to the soft
starter shall be available even when the shorting contactor is engaged.
H. The equipment shall be an Enclosed Altistart 22 Solid State Reduced Voltage
Combination Motor Controller by Square D / Schneider Electric or an approved equal.
2.2 MOTOR DATA
A. The soft starter shall be designed to operate a NEMA design B motor with a nameplate
rating as shown on the Drawings.
2.3 RATINGS
A. The soft start shall be designed to operate in an ambient temperature:
- UL Type 1 and Type 12 at 14 IF to 104 IF (-10 °C to 40 °C);
- UL Type 1, Type 12, and Type 3R at 14 IF to 122 OF (-10 °C to 50°C).
B. Storage temperature range shall be -25 °C to 70 °C (-13 OF to 158 OF).
C. Maximum relative humidity shall be 95%, non-condensing or dripping water, conforming
to IEC 60068-2-3.
D. The soft starter shall be designed to operate in altitudes up to 1000 m (3300 ft).
For higher altitudes, derate by 2.2% for each additional 100 m (330 ft) with a maximum
of 2000 m (6600 ft).
E. The soft starter shall be capable of operation between +10% /- 15% of nominal voltage
rating.
F. The soft start shall automatically adapt for operation at 50 or 60 Hz, with a frequency
tolerance of+/- 5%. By configuration, it shall be capable of operation at a supply line
frequency that can vary by +/- 20% during steady state operation.
G. The soft start shall be capable of supplying 350% of rated full load current for 40
seconds from a cold state, and 300% of rated full load current for 20 seconds, or 200%
of rated full load current for 40 seconds, with a load factor of 95% and 3 starts per hour.
SOLID STATE REDUCED VOLTAGE CONTROLLER
26 29 33-2
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
The SCRs shall have a minimum P.I.V. rating of 1800 Vac. Lower rated SCRs with
MOV protection are not acceptable.
H. A seismic qualification label shall be provided for all units to comply with the latest IBC
2000 and NFPA 5000 guidelines
2.4 ADJUSTMENTS AND CONFIGURATIONS
A. All programming/configuration devices, display units, and field control wiring terminals
shall be accessible on the front of the control module. Exposure to control circuit boards
or electrical power devices during routine adjustments is prohibited.
B. Digital indication shall provide, as a minimum, the following conditions:
1. Soft starter status - ready, starting/stopping, run.
2. Motor status - current.
3. Detected Fault status - Motor thermal overload, soft starter thermal fault, loss of line
or motor phase, line frequency, low line voltage, motor underload, maximum start
time exceeded, serial communication error, line phase reversal, motor overcurrent.
C. The soft starter must be preset to the following for adjustment-free operation in most
applications:
1. Current limitation to 300% of the motor full load current rating.
2. Class 10 overload protection.
3. Motor current preset per NEC/ NFPA 70 table 430.250 for standard hp motors.
D. A digital keypad shall be utilized configure the following operating parameters as
required:
1. Motor full load amperes adjustable from 40 to 110% of the soft starter's rating.
2. Current limitation on starting adjustable from 200 to 700% of the motor current
rating, not to exceed 350% of the soft starter rating.
3. Linear acceleration ramp adjustable from 1 to 60 seconds.
4. Maximum start time adjustable from 1 to 250 seconds.
5. Selection of freewheel or soft stop.
6. Linear deceleration ramp time adjustable from 1 to 60 seconds.
7. Threshold to change to freewheel from a controlled deceleration ramp to freewheel
stop: adjustable from 0 to 10% of the nominal motor torque.
8. Selection of Class 10, 20, or 30 motor thermal overload protection.
SOLID STATE REDUCED VOLTAGE CONTROLLER
26 29 33-3
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
E. A digital keypad shall be utilized to configure the following controller parameters as
required:
1. Assignment of soft starter inputs and output control terminals.
2. Activation of line phase reversal and phase loss protection.
3. Selection of motor thermal protection by overload class or PTC.
4. Return to factory settings.
F. Output relays shall provide the following status indications:
1. One Form C (N.O./N.C.) for indication of trip status.
2. One Form C (N.O./N.C.) for indication that the soft start is in acceleration, running
or deceleration state.
G. Additional inputs and outputs shall be available to provide the following status
indications:
1. Two assignable control inputs for the following functions: force to freewheel stop,
external fault input, disable serial link control, external motor overload reset or
general fault reset.
2. Two assignable logic-level signal outputs for the following functions: motor thermal
overload alarm, "motor powered" signal, motor overcurrent alarm, or motor
underload alarm.
H. Relay and 1/0 functions listed above must be isolated with respect to common.
2.5 PROTECTION
A. A microprocessor-based thermal protection system shall be included which
continuously calculates the temperature-rise of the motor and soft starter and provides:
1. A motor overload fault will stop the motor if the windings have exceeded 125% of
temperature-rise.
2. An electronic circuit with a time-constant adjustable to the motor's thermal cooling
time-constant ensuring the memorization of the thermal state even if power is
removed from the soft starter.
B. The soft starter shall provide line and motor phase loss, phase reversal, underload,
stall, and jam protection.
C. The integral protective features shall be active even when the shorting contactor is
used to bypass the SCRs during steady state operation.
SOLID STATE REDUCED VOLTAGE CONTROLLER
26 29 33-4
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2.6 CONTROL OPTIONS
A. The soft starter control circuit shall be fed from the line supply and be completely
independent of the power circuit and separate from the control logic.
B. The peripheral soft starter control circuitry shall be operated at 120 Vac 60 Hz from a
control power transformer included within the enclosure.
C. Operator devices shall be door mounted and shall be as shown on Drawings.
2.7 COMMUNICATIONS
A. The soft starter will have to include a multi-drop serial link for its direct connection to
Modbus.
B. The soft starter shall be able to be connected to Ethernet and other networks, with
connection to communication bus as an option.
C. The communication shall be able to provide access to the control, to the adjustment
and to the supervision of the soft starter.
2.8 SHORTING CONTACTOR
A. A microprocessor shall control the operation of the shorting contactor.
B. The shorting contactor shall close, shorting the SCRs after the acceleration ramp is
compete and motor current is below 130% of motor FLA, and open on a stop command
to allow a deceleration ramp.
C. Overload protection integral to the soft starter shall continue to protect the motor when
shorting is engaged.
D. The shorting contactor shall be contained within the soft starter frame.
PART 3 - EXECUTION
3.1 INSTALLATION
A. The soft start shall be installed per the manufacturer's specifications.
B. A standard wiring diagram shall be included for making the appropriate electrical
connections.
3.2 START UP OPTION
A. The services of a qualified manufacturer's service representative shall be available to
install, test, and start up all soft starts furnished under this specification.
END OF SECTION
SOLID STATE REDUCED VOLTAGE CONTROLLER
26 29 33-5
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 31 11 00
CLEARING AND GRUBBING
PART 1 GENERAL
1.1 WORK INCLUDED
A. The work of this section consists of clearing, grubbing, grinding, transporting,
removing and disposing of unsuitable material, trees, stumps, roots, vegetation
debris, and existing improvements, including curb, landscaping, fencing, and other
protruding obstructions within the clearing limits.
B. Protect trees, landscaping and shrubs that are not designated to be removed or near
construction site that may be harmed by construction activities.
1.2 RELATED WORK
A. Section 01 01 20 Protection of Underground Facilities & Monuments
B. Section 01 56 16 — Dust Control
C. Section 01 57 13 — Erosion Control
D. Section 01 57 23 —Storm Water Pollution Prevention Plan
E. Section 01 74 19 — Construction Waste Management and Disposal
F. Section 02 41 00 — Demolition
1.3 REGULATORY REQUIREMENTS
A. Obtain all required permits.
B. Dispose of removed materials in a legal manner at an approved disposal facility.
C. One hundred percent of trees, stumps, rocks and associated vegetation and soils
resulting from land clearing shall be reused or recycled.
1.4 REFERENCES
A. Section 15 — Existing Facilities, State Standard Specifications
B. Section 19 — Earthwork, State Standard Specifications
1.5 DEFINITION
A. Unsuitable Material: Unsuitable material is material determined to be:
1. Material containing trash, debris, oversized material or other foreign and
objectionable materials.
CLEARING AND GRUBBING
31 11 00-1
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/152ae04c-6d01-4370-9f11-
05376cde5102/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/31 11 00 Clearing and Grubbing.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2. Incapable of being compacted to Specified density using ordinary methods at
optimum moisture content.
3. Too wet to be properly compacted if circumstances prevent satisfactory in-
place drying prior to incorporation into the work.
4. Non-native material containing a significant amount of permeable materials,
such as sand or rock, that cannot be blended with other material and requires
to be off hauled.
5. Expansive clays that cannot be mixed or treated and requires to be off hauled.
6. Otherwise, unsuitable for planned use.
PART 2 PRODUCTS
2.1 NOT USED
PART 3 EXECUTION
3.1 CLEARING AND GRUBBING
A. Clear the specified areas by removing, above the natural ground surface, all existing
improvements including curbs, gutters, catch basins, storm drains, landscaping
fencing and utilities; vegetable growth such as trees, shrubs, logs, upturned stumps,
roots of down trees, brush, and similar material.
1. Trees of 4-inch diameter and larger shall not be removed without Owner's
authorization.
B. Grub the specified areas below the natural ground surface, except in embankment
areas where the grading plane is two feet or more above the natural ground, to a
depth necessary to remove all boulders, stumps, roots, buried logs, and other
objectionable material including rock and concrete. Remove and stock pile the top
4 inches of topsoil in any area which is to receive structural fill.
3.2 PRESERVATION
A. If indicated or required, preserve trees, plants, rock outcroppings, or other features
designated to remain. Protect trees and plants from damage; fell trees in a manner
which shall not injure standing trees, plants and improvements which are to be
preserved.
END SECTION
CLEARING AND GRUBBING
31 11 00-2
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/152ae04c-6d01-4370-9f11-
05376cde5102/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/31 11 00 Clearing and Grubbing.docx
COUNTY OF FRENSO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 31 23 17
TRENCHING, BACKFILLING AND COMPACTING
PART 1 GENERAL
1.1 WORK INCLUDED
A. This section includes material, testing, installation, and other requirements for trench
excavation, bedding, backfilling and compacting for underground pipelines and
utilities. Requirements in this section do not apply to underground landscape
irrigation pipes. The words pipe, utility, and pipelines are interchangeable in this
Section and apply to that which is being installed in the trench.
1.2 RELATED WORK
A. Section 01 33 00 — Submittal Procedures
B. Section 01 43 00 —Quality Control and Testing
C. Section 03 30 01 — Cast-in-Place Concrete
D. Section 31 11 00 — Clearing and Grubbing
E. Section 32 31 00 — Fencing
F. Division 33 - Utilities
G. Section 40 05 00 — Pipe and Fittings
H. Section 40 20 10 — Pipe Supports
1.3 REFERENCES
A. ASTM C136 — Standard Test Method for Sieve Analysis of Fine and Coarse
Aggregates.
B. ASTM D1557—Standard Test Methods for Laboratory Compaction Characteristics of
Soil Using Modified Effort (56,000 ft-Ibf/ft3 (2,700 kN-m/m3).
C. ASTM D1556— Density of Soil and Base Rock in Place by Sand-Cone Method.
D. ASTM D6938— Density of Soil and Base Rock in Place by Nuclear method.
E. ASTM D2937— Density of Soil In Place by Tube method
F. Cal/OSHA Construction Safety Orders, California Code of Regulations, Chapter 4,
Subchapter 4.
G. State Standard Specifications, Section 19— Earthwork
TRENCHING, BACKFILLING AND COMPACTING
31 23 17-1
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/80799b65-83b3-4e5c-9351-
c481af91ce73/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/31 23 17 Trenching Backfilling and Compacting.docx
COUNTY OF FRENSO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
H. State Standard Specifications, Section 26 —Aggregate Bases
I. ASTM D2321 Installation of Underground Thermoplastic Gravity Pipelines
J. AWWA Manual M23 PVC Pipe Design and Installation
K. AWWA Manual M55 PE Pipe Design and Installation
L. AWWA Manual M11 Steel Pipe: A Guide for Design and Installation
M. American Concrete Pipe Association Concrete Pipe & Box Culvert Installation Guide
N. Ductile Iron Pipe Research Association Installation Guide for Ductile Iron Pipe
O. PVC Pipe Association Installation Guide for Gasket-Joint PVC Pressure Pipe
P. National Resource Conservation Service (NRCS) Construction Specification 430
Irrigation Pipeline
Q. NRCS Construction Specification Plastic (PVC,PE) Pipe
R. U.S. Bureau of Reclamation Method for Prediction of Flexible Pipe Deflection M-25
S. U.S Department of Labor, 29 CFR, 1926, Subpart P
T. National Corrugated Steel Pipe Association (NCSPA) Corrugated Steel Pipe Design
Manual
U. NCSPA Installation Manual for Corrugated Steel Pipe and Structural Plate
V. Advanced Drainage Systems Corrugated Plastic Pipe Storm Installation Guide
1.4 SUBMITTALS
A. Submit plans as required for worker protection against caving ground in excavations.
Submittals shall be in accordance with Section 01 33 00 — Submittal Procedures.
B. Submit material classification and geotechnical test results on proposed imported fill.
1.5 SAMPLES
A. Submit samples under provisions of Section 01 43 00 — Quality Control and Testing.
1.6 PROTECTION
A. Prevent trench cave-in by sloping and/or shoring according to requirements of
Cal/OSHA, the U.S. Department of Labor, and the Contract Documents.
B. Notify Engineer of unexpected subsurface conditions.
C. Protect bottom of trench from frost.
TRENCHING, BACKFILLING AND COMPACTING
31 23 17-2
https://us-partner-i ntegrations.eg nyte.com/msoffice/wopi/files/80799b65-83b3-4e5c-9351-
c481af91ce73/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/31 23 17 Trenching Backfilling and Compacting.docx
COUNTY OF FRENSO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
D. When pipe laying is not in progress, close the open ends of pipe. Do not allow trench
water, animals or foreign material to enter the pipe.
1.7 QUALITY ASSURANCE
A. Compaction Testing:
1. All compaction testing shall be in accordance with Section 01 43 00 —
Quality Control and Testing.
1.8 CONTROL AND DIVERSION OF WATER
A. General —The Contractor shall furnish or procure all materials and labor required for
constructing and maintaining all necessary cofferdams, channels, flumes, drains,
sumps, and/or other temporary diversion and protective works and shall furnish,
install, maintain, and operate all necessary pumping and other equipment for removal
of water from the various parts of the work and for maintaining the trenches and other
parts of the work free from water. The Contractor shall at all times have on the project
sufficient pumping equipment for immediate use, including stand-by pumps for use in
case other pumps become inoperable.
B. Plan — Prior to beginning any work on the removal of water from trenches, the
Contractor shall submit for the Engineer's approval a water control plan showing the
proposed method for the removal of water from trenches and other parts of the work.
C. Dispose of the water in a manner that will prevent damage to the adjacent property
and in accordance with regulatory requirements.
D. Provide separate pipelines to drain trench water during construction.
E. Provide filters on devices to control and divert water to prevent the removal of fines
from the soil.
F. Repair any damage caused by the failure of any part of equipment to control and
divert water. Remove temporary equipment to control and divert water when no
longer needed for dewatering purposes.
G. Provision of equipment to control and divert water shall be considered part of the
project with no additional compensation allowed.
H. Unless otherwise specified in the Measurement and Payment section, any drain rock
required in the trench bottom to convey water or stabilize wet soil shall be included at
no extra cost to the Owner.
1.9 PROJECT CONDITIONS
A. Existing underground utilities may exist at this site. Contractor shall take all
necessary precautions to protect said utilities. Notify Engineer of any deviation in
utility location from that which is shown on the drawings.
B. Obtain all required permits and licenses before installing utilities and follow the rules
and requirements of authorities having jurisdiction.
TRENCHING, BACKFILLING AND COMPACTING
31 23 17-3
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/80799b65-83b3-4e5c-9351-
c481af91ce73/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/31 23 17 Trenching Backfilling and Compacting.docx
COUNTY OF FRENSO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
C. Arrange construction sequences to provide the shortest practical time that the
trenches will be open to avoid hazard to the public, and to reduce the possibility of
trench collapse.
1.10 DEFINITION
A. Percent Compaction: The ratio of the field-tested dry density of earthfill to the
maximum dry density determined in the laboratory according to the above-referenced
Laboratory compaction test method —expressed as a percentage
B. Unsuitable Material — Unsuitable material is material determined to be:
1. Material containing trash, debris, oversized material or other foreign and
objectionable materials.
C. Deflection is the decrease of the vertical diameter of the pipe (and corresponding
increase in horizontal diameter) due to load on the pipe. Deflection is expressed in
terms of percentage as follows: change in diameter/diameter x 100).
D. Ovality% = 2 x [(Dmax-Dmin)/(Dmax +Dmin)] x 100 where Dmax and Dmin are
maximum and minimum pipe diameters in any direction.
1.11 CLASSIFICATION AND CHARACTERIZATION OF EXCAVATED MATERIAL
A. The Contractor shall consider all trenched material as being unclassified.
1.12 HAND EXCAVATION
A. Hand excavation will be required within 12 inches of the existing water distribution
main identified in the drawings, if necessary.
PART 2 PRODUCTS
2.1 EXISTING GROUND AND BACKFILL
A. Existing Ground: In-situ soil or bedrock that the Contractor excavates for trenches.
The Contractor may use this excavated material as backfill if it meets backfill material
property requirements and/or if the Contractor processes it so that it meets those
requirements.
B. Backfill: Soil fill that the Contractor places and compacts in trenches over granular
backfill and aggregates and that meets material property requirements of the
geotechnical engineering report and the Contract Documents. Backfill may consist of
existing ground or imported earth material. The Engineer shall approve backfill
before it is imported to the site and placed.
2.2 AGGREGATES
A. Granular Backfill: material meeting the requirements of State Standard Specifications
Section 19-3.02C.
TRENCHING, BACKFILLING AND COMPACTING
31 23 17-4
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/80799b65-83b3-4e5c-9351-
c481af91ce73/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/31 23 17 Trenching Backfilling and Compacting.docx
COUNTY OF FRENSO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
B. Gravel: Natural rock; free of shale, clay, friable materials and debris; graded in
accordance with 11/2" x 3/4" aggregate grading in Section 90-1.02C, State Standard
Specifications.
C. Pea Gravel: Natural rock aggregate; washed, free of clay, shale, organic matter; No.
8 minimum to 3/8" maximum size per State Standard Specifications Section 90-
102C(4)(a).
D. Sand: Natural sand; free of friable or soluble materials, less than 2 percent organics
by dry weight, and graded in accordance with State Standard Specifications Section
90-1.02C(4)(c):
2.3 CONCRETE SLURRY
A. Concrete slurry mix shall be as specified in Section 03 30 00 - Cast-in-Place
Concrete.
2.4 MATERIALS FOR TRENCH BACKFILLING
A. Furnish required bedding, select backfill, and backfill materials shown on the Plans
and that meets requirements in this section depending on the trench type.
B. The Engineer shall approve all trench-backfill material prior to the Contractor's import
and placement.
C. Materials used in backfill, as shown in trench details, are defined as follows:
1. Bedding: Where trench bottoms expose bedrock and/or soil with hard
gravel/cobble particles that protrude up into the excavation, and when
trench subgrades consist of soft and unstable soil, then sand bedding is
required. Sand to be used shall meet the requirements listed above under
Aggregates.
2. Select Backfill: Select Backfill may be required as shown on the Plans.
Select backfill shall meet the material property requirements that follow:
a. Select backfill material shall have a sand equivalent of 30 per ASTM
D2419.
b. Plasticity index of less than 6
C. The following particle size distribution:
Sieve Size Percent Passing by Dry Weight
'/2 inch 100
No. 4 50-80
No. 200 10-25
3. Backfill: Soils that contain no rock larger than 3 inches at greatest dimension.
If expansive clays are present, such content shall not exceed one-third of the
material by volume and shall be well mixed with non-cohesive soils.
4. Gravel: Gravel shall meet the requirements listed above under Aggregates.
TRENCHING, BACKFILLING AND COMPACTING
31 23 17-5
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/80799b65-83b3-4e5c-9351-
c481af91ce73/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/31 23 17 Trenching Backfilling and Compacting.docx
COUNTY OF FRENSO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
5. Pea Gravel: Pea gravel shall meet the requirements listed above under
Aggregates
6. Sand: Sand shall meet the requirements listed above under Aggregates.
2.5 SAND-CEMENT SLURRY
A. Sand-cement slurry backfill shall be as specified in Section 03 30 00 — Cast-in-Place
Concrete.
2.6 WATER FOR FILL MOISTURE CONDITIONING AND COMPACTION
A. Water shall be free of organic materials injurious to the pipe coatings, have a pH of
7.0 to 9.3, maximum chloride concentration of 500 mg/l, and a maximum sulfate
concentration of 500 mg/I.
PART 3 EXECUTION
3.1 GENERAL
A. Excavation shall be by open cut except that short sections of a trench may be
tunneled if the utilities can be safely and properly installed and backfill can be
properly compacted in such tunnel sections.
3.2 INSPECTIONS
A. The contractor must verify that the engineer has approved stockpiled material for
reuse as backfill material (for each backfill zone for intended use).
B. The contractor shall verify that trenches that they will backfill are free of debris, snow,
ice, or water, and that ground surfaces that backfill will cover are not frozen.
3.3 PREPARATION
A. Identify required lines, levels, contours, and datum.
3.4 AC PAVEMENT AND CONCRETE REMOVAL
A. Cut bituminous and concrete pavements, regardless of the thickness, curbs, gutters
and sidewalks prior to excavation of trenches.
1. The contractor shall saw cut existing pavement at least one lateral foot
beyond (outside of) the trench edges or further out as shown on the Plans.
2. The contractor shall remove all pavement and aggregate within the saw
cuts.
3. AC pavement and concrete rubble shall not be used for trench backfill.
4. The contractor shall replace aggregate and pavement surfaces according to
Specification Section 32 12 16 Asphalt Concrete Paving.
TRENCHING, BACKFILLING AND COMPACTING
31 23 17-6
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/80799b65-83b3-4e5c-9351-
c481af91ce73/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/31 23 17 Trenching Backfilling and Compacting.docx
COUNTY OF FRENSO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3.5 TRENCH EXCAVATION
A. Excavate the trench to the lines and grades shown on the Plans with allowance for
pipe thickness, sheeting, shoring, and bedding.
B. Trenching Guidelines: Excavate the trench to the approximate level of the grade of
the utility line to be installed, using adequate trench width and side slopes to safely
accommodate worker access.
1. Rocky Trench Bottom: Where ledge rock, hard pan, boulders, or sharp-
edged materials are encountered, over excavate trenches at least 12 inches
below and beyond the planned excavation lines. The installed utility shall
have at least 12 inches of clearance from any rock protrusion.
2. Unstable Trench Bottom: Secure the Engineer's approval of over-excavation
depth and stabilization method. The Contractor must seek the Engineer's
approval of overexcavation bottoms and subgrades before the Contractor
backfills and places utility pipes/conduits.
3. Wet Trench Construction: use approved method of dewatering through
diversion, damming and pumping, well points, or underdrain systems.
Dispose removed fluidized materials as approved. Use bedding material to
build a suitable foundation to within 6 inches of finished utility grade, prior to
bedding with the specified material. Place and compact backfill as specified.
The Contractor must seek the Engineer's approval of overexcavation bottoms
and subgrades before the Contractor backfills and places utility
pipes/conduits.
C. Correct unauthorized excavation at no cost to Owner.
1. If the trench is excavated below the required grade, backfill over-excavations
with compacted engineered backfill as specified.
D. Trench widths shall be as shown on the Plans. If no details are shown, then the
maximum width in the pipe zone shall be 24 inches greater than the pipe outside
diameter.
E. Trench width at the top of the trench will not be limited except where width of
excavation would undercut adjacent structures and footings. In such case, width of
trench shall be such that there is at least two feet between the top edge of the trench
and the structure or footing.
F. Excavation shall not interfere with normal 45 degree bearing splay of foundations.
G. Hand trim for bell and spigot pipe joints.
H. During trench excavation, place the excavated material only within the working area.
Do not obstruct roadways or streets. Follow Caltrans guidelines for excavation safety
for conditions of surcharge from stockpiled material.
TRENCHING, BACKFILLING AND COMPACTING
31 23 17-7
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/80799b65-83b3-4e5c-9351-
c481af91ce73/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/31 23 17 Trenching Backfilling and Compacting.docx
COUNTY OF FRENSO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3.6 UNSUITABLE MATERIAL
A. Unsuitable material shall be excavated and disposed of in a lawful manner off the
project site, all disposal shall be approved by the Engineer prior to initiating the work.
B. Unsuitable material shall be excavated and deposited in the location designated on
the Plans.
3.7 CONTROL OF WATER
A. The Contractor shall keep trenches free from water, maintain and operate all
necessary pumping and other equipment for dewatering of excavations.
B. The dewatering operation shall be continuous, so that the excavated areas are kept
free from water during the construction.
C. Do not drain trench water through pipeline under construction but use separately
provided pipeline.
D. Repair any damage caused by the failure of any part of the protective works.
Remove temporary protective works when they are no longer needed for dewatering
purposes.
E. Use of any drain rock in the trench bottom to convey water or stabilize wet soil shall
only be done if approved by the Engineer.
3.8 TRENCH BACKFILLING
A. Support pipe during placement and compaction of bedding fill.
B. Backfilling and cleanup work shall be accomplished as sections of pipe or conduit are
tested and approved.
C. Compaction: The contractor shall choose means and methods for achieving
compaction. Generally, vibratory compactors tend to work better for sands and
gravels (non-cohesive soils) and mechanical tampers work better for sand and gravel
containing a significant portion of fine-grained materials, such as silt and clay
(cohesive soils).
D. Hand tamp around pipe or cable to protect the lines until adequate cushion is
attained. Puddling or water flooding for consolidation of backfill or compaction by
wheel rolling will not be permitted.
E. Bedding: Unless otherwise specified, compact the specified material to 95 percent of
maximum density to the finished utility grade.
F. Embedment: Fill by hand placement around the utility to just over half depth, and
compact in a manner to ensure against lateral or vertical displacement. Place select
backfill to 12 inches above the utility line by hand placement in not more than 6-inch
layers.
TRENCHING, BACKFILLING AND COMPACTING
31 23 17-8
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/80799b65-83b3-4e5c-9351-
c481af91ce73/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/31 23 17 Trenching Backfilling and Compacting.docx
COUNTY OF FRENSO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
G. Backfill: Soil backfill shall be placed and backfilled in lifts, with each lift compacted to
the project requirements prior to addition of the next layer. Unless otherwise
specified, place and compact the specified material as follows:
1. Vehicular Traffic Areas: Fill and compact in 8-inch maximum loose lifts as
follows:
a. From top of select backfill to two feet below top of road subgrade,
compact to 90 percent compaction.
b. From two feet below top of subgrade to top of subgrade, compact to
95 percent compaction.
2. Non-traffic Areas: Fill and compact in 8-inch maximum layers to 90 percent
compaction.
H. Employ a placement method that will not disturb or damage pipes or utilities.
I. Maintain moisture content of backfill materials to attain required compaction density.
J. Compact trench-backfill to the specified percent compaction. Compact by using
mechanical compaction or hand tamping. Do not use high impact hammer type
equipment except where the pipe manufacturer warrants in writing that such use will
not damage the pipe. Do not use water flooding or jetting for backfill compaction.
K. Compact material placed within 12 inches of the outer surface of the pipe by hand
tamping only.
1. Carefully place the material around the pipe so that the pipe barrel is
completely supported and that no voids or uncompacted areas are left
beneath the pipe.
2. Use particular care in placing material on the underside of the pipe to
prevent lateral movement during subsequent backfilling.
L. After pipe has been bedded, place pipe zone material simultaneously on both sides of
the pipe, in maximum 8-inch lifts, keeping the level of backfill the same on each side.
M. Do not use any axle-driven or tractor-drawn compaction equipment within 5 feet of
building walls, foundations, and other structures.
N. Do not permit free fall of the material until at least two feet of cover is provided over
the top of the pipe. Do not drop sharp, heavy pieces of material directly onto the pipe
or on the surface of compacted backfill around the pipe. Do not operate heavy
equipment over the pipe until at least 3 feet of backfill has been placed and
compacted over the pipe.
O. Remove surplus backfill materials from site.
P. Leave stockpile areas completely free of excess fill materials.
TRENCHING, BACKFILLING AND COMPACTING
31 23 17-9
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/80799b65-83b3-4e5c-9351-
c481af91ce73/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/31 23 17 Trenching Backfilling and Compacting.docx
COUNTY OF FRENSO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3.9 TESTING FREQUECY
A. Backfill Compaction:
Pipeline Trenches: At least 1 test per lift per every 200 feet of trench backfill placed or
every 500 cubic yards placed, whichever is more frequent.
A greater frequency of testing may be required at the start of work or when new
materials, crews, or equipment are introduced to the site. A lesser frequency can be
utilized if approved by the Engineer and the Owner's Representative.
B. Laboratory Index Testing:
In addition, at least one set of index tests shall be performed for each distinct material
type used as compacted fill at the site.
Additional tests may be performed, as directed by the Owner's Representative,
whenever deviations in material properties or quality of workmanship are suspected.
3.10 TOLERANCES
A. Top Surface of trench backfill: ±0.1 foot.
3.11 SAND CEMENT SLURRY, CONCRETE ENCASEMENT AND THRUST BLOCKS
A. Place in accordance with the Contract drawings.
3.12 PIPE DEFLECTION AND OVALITY CONTROL
A. Pipe installation and backfill process shall be done in a manner that does not overly
deflect pipe or make it overly oval in any direction so that deflection or ovality limits in
pipe specifications or installation guidelines are exceeded. The following table has
common deflection and ovality limits for flexible pipes but pipe specifications and
installation guidelines shall govern over this table. Owner has the option to hire a
third-party testing firm to conduct pipe mandrel testing to verify the pipe installation is
within the following requirements or as stated in the individual pipe specification
sections.
Pipe Type Deflection and Ovality Limit
PVC Pressure, Sewer, or Gravity Pipe 7.5%
Steel with Flexible Coating 5%
Cement Mortar Lined Steel with flexible 3%
coating
Cement Mortar Coated Steel 2%
Cement Mortar Lined and Coated Steel 2%
TRENCHING, BACKFILLING AND COMPACTING
31 23 17-10
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/80799b65-83b3-4e5c-9351-
c481af91ce73/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/31 23 17 Trenching Backfilling and Compacting.docx
COUNTY OF FRENSO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
END SECTION
TRENCHING, BACKFILLING AND COMPACTING
31 23 17-11
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/80799b65-83b3-4e5c-9351-
c481af91ce73/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/31 23 17 Trenching Backfilling and Compacting.docx
COUNTY OF FRENSO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
This Page is Intentionally Left Blank
TRENCHING, BACKFILLING AND COMPACTING
31 23 17-12
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/80799b65-83b3-4e5c-9351-
c481af91ce73/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/31 23 17 Trenching Backfilling and Compacting.docx
COUNTY OF FRESNO
RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 31 23 35
DISPOSAL OF MATERIALS
PART 1 GENERAL
1.1 WORK INCLUDED
A. Disposal of unsuitable material, concrete, asphalt concrete, rubbish, and other
debris, as described below.
1.2 SUBMITTALS
A. Submittals shall be in accordance with Section 01 33 00 - Submittal Procedures.
1.3 GENERAL
A. The Contractor shall be responsible for the cleanup and disposal of waste materials
and rubbish. The disposal of waste materials and rubbish shall be in accordance
with applicable Federal, State, and local laws and regulations, and with the
requirements of this paragraph. Should a conflict exist in the requirements for
cleanup and disposal of waste materials, the most stringent requirement shall apply.
B. The Contractor shall keep records of the types and amounts of waste materials
produced, and of the disposal of all waste materials on or off the jobsite.
C. The cost of disposing of waste materials other than unsuitable materials shall be
included in the prices bid in the schedule for other items of work.
PART 2 PRODUCTS
Not Used
PART 3 EXECUTION
3.1 DISPOSAL OF EXCAVATED MATERIAL
A. All unsuitable material that is hauled off-site shall be properly disposed.
3.2 DISPOSAL OF CONCRETE AND A.C. SURFACING
A. All concrete and pavement removed from the project site shall be disposed of at a
site obtained by the Contractor and approved by the Owner's Representative. No
recyclable material shall be disposed of at any landfill. All disposable recyclable
materials shall be disposed in a manner that facilitates recycling. Payment for
disposal, including all costs of hauling, shall be as specified in the Technical
Specifications or Explanation of Bid Items. The Contractor shall report quantities of
disposed material in a manner that enables the Owner to utilize diverted quantities
as diversion credits pursuant to California Integrated Waste Management Act of
1989 (Public Resources Code Sections 40000 et seq.)
DISPOSAL OF MATERIALS
31 23 35-1
https://us-partner-i ntegrations.eg nyte.com/msoffice/wopi/files/e96dd956-cOa6-460d-bb4e-
54218546272d/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/31 23 35 Disposal of Materials.docx
COUNTY OF FRESNO
RAISIN CITY GROUNDWATER WELL PROJECT
3.3 DISPOSAL OF OTHER DEBRIS
A. All oil cake, wood debris, structure demolition, vegetation and any other debris
removed from the project site shall be legally disposed of at a site(s) obtained by
the Contractor with prior written permission of the Owner's Representative.
Contractor shall identify the proposed Disposal Site(s) at the pre-construction
conference. Such Disposal Site(s) shall be a properly licensed and permitted facility
pursuant to state and local regulations for purposes of accepting delivery of the
respective materials. No recyclable material shall be disposed of at any landfill. All
disposable recyclable materials shall be disposed in a manner that facilitates
recycling. In addition to the following, a certificate of compliance stating disposal
location and manner of disposal of recyclable materials shall be submitted to the
Owner's Representative.
1. Disposal of combustible materials shall be by removal from the construction
area. Disposal of combustible materials by burning will not be permitted.
Disposal of waste materials by burying will not be permitted.
2. Waste materials shall be disposed of or recycled at a State approved disposal
or recycle facility. The Contractor shall make any necessary arrangements
with private parties, and State and county officials pertinent to locations and
regulations of such disposal or recycle facilities and shall pay any fees or
charges required for such disposition.
3.4 CONTRACTOR'S DISPOSAL SITES
A. Contractor shall make arrangements for disposing of the materials at the Disposal
Site(s) and pay all costs involved. Arrangements shall include, but not be limited to,
obtaining written authorization from the property owner of the Disposal Site(s) and
before disposing of any material off the project site, Contractor shall furnish to the
Owner's Representative the authorization or a certified copy thereof together with a
written release from the property owner absolving the Owner from any and all
responsibility in connection with the disposal of material on the property of the
Disposal Site(s). Before any material is disposed of on the Disposal Site(s), the
Contractor shall obtain written permission from the Owner's Representative to
dispose of the material at the location designated in the authorization.
B. It is expressly understood and agreed that the Owner assumes no responsibility to
the Contractor whatsoever by the granting of such permission and Contractor shall
assume all risks in connection with the use of the Disposal Site(s). The Contractor
is cautioned to make such independent investigation and examination as the
Contractor deems necessary to be satisfied as to the quantity and types of materials
which may be disposed of on the Disposal Site(s) and the status of any permits or
licenses in connection therewith.
C. Within 24 hours of removing the respective material from the project site for disposal,
Contractor shall provide Owner's Representative with a certified copy of the weight
slip from the Disposal Site obtained by Contractor upon delivery of such debris, and
a certified statement from Contractor identifying the material constituting the debris
and that it was disposed of at the Disposal Site (identifying the and name of the
owner) in accordance with all laws and applicable regulations promulgated by
Federal, State, regional, or local administrative and regulatory agencies.
DISPOSAL OF MATERIALS
31 23 35-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/e 96d d 956-cOa 6-46Od-bb4e-
54218546272d/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/31 23 35 Disposal of Materials.docx
COUNTY OF FRESNO
RAISIN CITY GROUNDWATER WELL PROJECT
3.5 DISPOSAL OF HAZARDOUS WASTE AND MATERIALS
A. Materials or wastes, defined as hazardous by 40 CFR 261.3, or by other Federal,
State, or local laws or regulations, used by the Contractor or discovered in work or
storage areas, shall be disposed of in accordance with these specifications and
applicable Federal, State, and local laws and regulations. Unknown waste materials
that may be hazardous shall be tested, and the test results shall be submitted to the
Owner's Representative for review.
B. Waste materials known or found to be hazardous shall be disposed of in approved
treatment or disposal facilities. Hazardous wastes shall be recycled whenever
possible. A copy of all hazardous waste manifest shall be sent to the Owner's
Representative.
C. Waste materials discovered at the construction site shall immediately be reported to
the Owner's Representative. If the waste may be hazardous, the Owner's
Representative may order delays in the time of performance or changes in the work,
or both. If such delays or changes are ordered, an equitable adjustment will be
made in the contract in accordance with the applicable clauses of the contract.
D. If necessary, the Contractor will be required to conduct an environmental site
assessment at the following Contractor use locations:
1. All hazardous waste accumulation areas;
2. All hazardous material and petroleum dispensing and storage areas where
the aggregate storage of hazardous materials or petroleum at the site is or
has been over 110 gallons.
3. This site assessment shall be performed by a qualified environmental
consultant or equivalent and shall document through appropriate analytical
sampling that the site is free of the effects of contamination (i.e., contaminant
concentrations less than State action cleanup levels).
3.6 CLEANUP
A. The Contractor shall keep work and storage areas free from accumulations of waste
materials and rubbish, and before completing the work, shall remove all plant
facilities, buildings, including concrete footings and slabs, rubbish, unused
materials, concrete forms, and other like materials, which are not a part of the
permanent work.
B. Upon completion of the work, and following removal of construction facilities and
required cleanup,work areas shall be regraded and left in a neat manner conforming
to the natural appearance of the landscape.
END SECTION
DISPOSAL OF MATERIALS
31 23 35-3
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/e 96d d 956-cOa 6-46Od-bb4e-
54218546272d/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/31 23 35 Disposal of Materials.docx
COUNTY OF FRESNO
RAISIN CITY GROUNDWATER WELL PROJECT
This Page is Intentionally Left Blank
DISPOSAL OF MATERIALS
31 23 35-4
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/e 96d d 956-cOa 6-46Od-bb4e-
54218546272d/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/31 23 35 Disposal of Materials.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 32 31 00
FENCING
PART 1 GENERAL
1.1 WORK INCLUDED
A. Provide all labor, materials and equipment and perform all operations necessary to
complete chain link fencing as specified, shown on the Drawings, or as directed.
B. Furnish and Install Right of Way fencing as shown on the Plans.
C. Install salvaged chain fence as indicated on the Plans
1.2 RELATED WORK
A. Section 03 33 00 — Cast-in-Place Concrete
1.3 REFERENCES
A. Section 80 — Fences, State Standard Specifications
1.4 SUBMITTALS
A. Submittals shall be in accordance with the Standard General Conditions and the
Supplementary conditions.
PART 2 PRODUCTS
A. Chain Link shall conform to State Standard Specifications Section 80-3.02
B. Fence lines adjacent to residences shall be furnished with brown ultraviolet resistant
PVC privacy slats conforming with State Standard Specifications Section 80-3.02E.
C. Right of Way fence shall conform to State Standard Specifications Section 80-3.
PART 3 EXECUTION
3.1 FENCES
A. Installation shall be in accordance with State Standard Specifications, Section 80,
and with State Standard Plans Drawing A85, A85A and as indicated on the Plans.
B. Relocation and installation of other fencing materials shall be in accordance with the
plans and standard construction practices.
END SECTION
FENCING
3231 00-1
https://us-partner-i ntegrations.eg nyte.com/msoffice/wopi/files/22ga2O35-f00f-4d69-add0-
1ba78396fbe4/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/32 31 00 Fencing.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
This Page is Intentionally Left Blank
FENCING
3231 00-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/22ga2O35-f00f-4d 69-add 0-
1ba78396fbe4/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/32 31 00 Fencing.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 33 05 26
UTILITY LINE MARKING
PART 1 GENERAL
1.1 WORK INCLUDED
A. The work of this section consists of furnishing and installing utility line marking tape
in the trench above newly constructed utility lines.
1.2 SUBMITTALS
A. Samples: 24-inch strips of tape and two markers.
B. Certification that the materials used in the tape fabrication meet the requirements of
this section.
C. Installation procedure if the cable is installed by plowing.
PART 2 PRODUCTS
2.1 MARKING TAPE
A. Capable of being inductively detected electronically.
B. Construction: Metallic foil laminated between two layers of impervious plastic film
not less than 3 inches wide. Total thickness of tape shall not be less than 0.005
inch (5 mil), ±10 percent manufacturing tolerances.
1. Film: Inert plastic. Each film layer shall be not less than 0.001 inch (1.0 mil)
thick.
2. Foil: Not less than 0.001 inch (1.0 mil) thick.
3. Adhesive: Compatible with foil and film.
C. Imprint: 3/4-inch or larger bold black letters.
D. Legend: Identify buried utility line tape with imprint such as "Caution: Water Main
Below". Repeat identification at approximately 24 inch intervals.
E. Background Color: APWA color code and as specified in the following table.
Color Utility
Safety Precaution Blue Water System, Irrigation
UTILITY LINE MARKING
33 05 26-1
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/e67888a7-3fcf-4e81-b020-
e0176c5b0706/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/33 05 26 Utility Line Marking.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
F. Manufacturer: Lineguard, Inc., Wheaton, Illinois; Reef Industries, Inc., Houston,
Texas; Thor Enterprises, Inc., Sun Prairie, Wisconsin; or Engineer-approved
equivalent.
2.2 SURFACE MARKERS
A. All markers shall have an identifying letter either cast or routed into marker. The
Contractor has the option of any of the following. However, only one type shall be
used on any one project:
B. Cast-In-Place Concrete.
1. Concrete: As specified in Section 03 33 00— Cast in Place Concrete.
2. Reinforcement: One No. 5 bar in the centre of the marker.
C. Precast Concrete: Commercially fabricated concrete marker meeting design
dimensions and concrete reinforcing requirements.
D. Timber Posts: Any softwood lumber species meeting PS 20-70. Grade No. 1 or
better, free of heart center, S4S as shown. Pressure treat timber posts for soil
contact with waterborne preservative in accordance with AWPA C2-90.
2.3 TRACER WIRE
A. Minimum: No.10, solid, 12 AWG copper wire with Type TW insulation. Join so as to
form a mechanically and electrically continuous line throughout the length of the
marked pipe.
PART 3 EXECUTION
3.1 MARKING TAPE
A. Install tape in backfill directly over each buried utility line as shown on the detailed
drawings.
B. Unless otherwise shown, tape shall be installed a minimum 1.5 feet below finish
grade. However, in no case shall tape be placed closer than two feet above the top
of the pipe.
C. Where utilities are buried in a common trench, identify each line by a separate
warning tape. Bury tapes side by side directly over the applicable line.
3.2 TRACER WIRE
A. Wherever PVC or Polyethylene pipe is installed in the ground, a tracer wire shall be
installed. Conductors shall be spliced in accordance with Division 26, Electrical.
1. Tracer wire shall be brought to the surface at all gate and butterfly valves, air
valves, blow-offs, Fire Hydrants, Water Services, and other pipeline
appurtenances
UTILITY LINE MARKING
33 05 26-2
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/e67888a7-3fcf-4e81-b020-
e0176c5b0706/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/33 05 26 Utility Line Marking.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
B. Tracer Wire: Attachment of the wire to the pipe shall be made with plastic tie-wraps
or other approved method.
C. Contractor shall conduct a satisfactory continuity test prior to Owner acceptance.
3.3 SURFACE MARKERS
A. In addition to marking tape, install surface markers at all changes in horizontal
direction and at intervals not exceeding 400 feet.
B. Tracer wire shall be wrapped around cast iron valve boxes; while ensuring wire
conductors are making contact with valve box.
1. Tracer wires shall be tied together to a No. 5 rebar cast in a concrete utility
line marker and terminate above grade. Allow sufficient slack in tracer wire
along pipe to allow for pipe shrinkage and expansion.
END SECTION
UTILITY LINE MARKING
33 05 26-3
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/e67888a7-3fcf-4e81-b020-
e0176c5b0706/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/33 05 26 Utility Line Marking.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
This Page is Intentionally Left Blank
UTILITY LINE MARKING
33 05 26-4
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/e67888a7-3fcf-4e81-b020-
e0176c5b0706/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/33 05 26 Utility Line Marking.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 33 13 00
DISINFECTION OF WATER DISTRIBUTION SYSTEM
PART 1 GENERAL
1.1 WORK INCLUDED
A. Disinfection of all new potable piping, components, and appurtenances.
B. This shall include disinfection of all potable water piping, well, hydropneumatic tank,
finished water storage tank, and pumps.
C. New facilities shall be kept isolated from the active distribution system using a
backflow, double check valve device per ANSI/AWWA C651 - Disinfecting Water
Mains.
D. Before allowing water from the municipal supply system to enter the new potable
water system, all its components shall be cleaned and disinfected.
E. Test and report results. Cost of all testing shall be borne by the Contractor.
F. Connect new system and existing water distribution mains, after all required test are
satisfactory and approved by the Engineer.
1.2 RELATED WORK
A. Section 40 05 00 — Pipe and Fittings
1.3 REFERENCE
A. ANSI/AWWA C651 — Disinfecting Water Mains
B. ANSI/AWWA C652 — Disinfection of Water Storage Facilities
C. ANSI/AWWA C654 — Disinfection of Wells
1.4 SUBMITTALS
A. Submit five copies of each compliance report to Engineer. Reports shall include the
following information:
1. Disinfection report; accurately record:
a. Type and form of disinfectant used.
b. Date and time of disinfectant injection start and time of completion.
C. Test locations.
d. Initial and 24-hour disinfectant residuals in parts per million (ppm) for
each location tested.
DISINFECTION OF WATER DISTRIBUTION SYSTEM
33 13 00-1
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/c 10c0482-a4d0-4921b-a31b4-
9f292eb232471WOPIServiceld To EGNYTE—PLUS/WOPIUserldl 89.ppeng.egnyte.com/33 13 00 Disinfection of Water Distribution System.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
e. Date and time of flushing start and completion.
f. Disinfectant residual after flushing in ppm for each location tested.
g. Persons present during the disinfection operation.
2. Bacteriological report; accurately record:
a. Date issued, project name, and testing laboratory name, address, and
telephone number.
b. Time and date of water sample collection.
C. Name of person collecting samples.
d. Test locations.
e. Initial and 24-hour disinfectant residuals in ppm for each location
tested.
f. Coliform bacteria test results for each location tested.
g. Certification that water conforms, or fails to conform, to bacterial
standards of the California State Water Resources Control Board.
h. Bacteriologist's signature.
B. Submittals shall be in accordance with Section 01 33 00 — Submittal Procedures.
1.5 QUALITY ASSURANCE
A. Testing laboratory certified with the State of California for examination of drinking
water.
1. Testing laboratory shall be selected by the Contractor and approved by the
Owner.
2. All samples shall be gathered and tested by said Laboratory.
3. Contractor shall instruct the testing laboratory to provide the test results to
the Engineer immediately upon results and a copy of the written report sent
directly to the Engineer.
PART 2 PRODUCTS
2.1 CHLORINE
A. All disinfectant chemicals shall be certified to ANSI/NSF Standard 60
B. Chlorine-bearing compounds:
DISINFECTION OF WATER DISTRIBUTION SYSTEM
33 13 00-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/c 10c0482-a4d0-4921b-a31b4-
9f292eb232471WOPIServiceld To EGNYTEPLUS/WOPIUserldl 89.ppeng.egnyte.com/33 13 00 Disinfection of Water Distribution System.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1. Calcium hypochlorite (comparable to commercial products known for example
as HTH, Perchloron, and Pittchlor, sold for swimming pool chlorination).
2. Sodium hypochlorite (liquid bleach, sodium hypochlorite in powder or tablet
form for pool chlorination).
PART 3 EXECUTION
3.1 PREPARATION
A. Verify that system has been cleaned, inspected, and pressure tested.
B. If a chlorine-bearing compound is to be used, the calcium hypochlorite or sodium
hypochlorite shall be prepared as a water mixture before introduction into the
potable water piping system. The powder shall first be made into a paste and then
thinned to approximately a 1- percent chlorine solution (10,000 ppm). The
preparation of 1- percent chlorine stock solution requires the following proportions
of powder to water:
Amount of Quantity of
Product Compound Water (Gals)
High-test Calcium
Hypochlorite (65 to 70 percent CI) 1 lb. 7.50
Sodium Hypochlorite liquid
(5.25 percent CI) 1 gal. 4.25
3.2 APPLICATION
A. Provide and attach equipment required to execute work of this Section. This may
include:
1. A solution-feed chlorination device.
2. A device to regulate rate of flow and provide effective diffusion of the gas into
the water within the pipe being tested. Chlorinating devices for feeding
solutions of the chlorine gas or the gas itself into the water shall provide means
for preventing the backflow of water into the chlorine cylinder.
B. Preliminary Flushing: Before disinfection, the system with outlets open shall be
flushed thoroughly with water. Flushing shall be done after the pressure test has
been made. Flushing shall develop a velocity in pipes of at least 2.5 feet per second
(fps).
C. Point of Application: The preferred point of application of the chlorinating agent is
at the beginning of the pipeline extension of any valved section, and through a
corporation stop inserted by the Contractor (except in new distribution systems) in
the top of the newly laid pipe. The water injector for delivering the chlorine-bearing
DISINFECTION OF WATER DISTRIBUTION SYSTEM
33 13 00-3
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/c 10c0482-a4d0-4921b-a31b4-
9f292eb232471WOPIServiceld To EGNYTEPLUS/WOPIUserldl 89.ppeng.egnyte.com/33 13 00 Disinfection of Water Distribution System.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
water into the pipe shall be supplied from a tap on the pressure side of the gate
valve controlling the flow into the pipeline extension.
D. Retention Period: Treated water shall be retained for at least 24 hours.
E. Chlorinating Valves and Hydrants: In the process of chlorinating newly laid pipe, all
valves or other appurtenances shall be operated while the pipeline is filled with the
chlorinating agent.
F. Chlorinating water services: Water meters and services lines can be sprayed or
swabbed with chlorine per AWWA C651, Section 4.11.3.1.
G. Circulate and flush repeatedly until specified cleanliness is achieved. Before being
placed in service, all new mains and repaired portions of, or extensions to, existing
mains shall be chlorinated so that a chlorine residual of not less than 25 mg/I free
available chlorine remains in the water after 24 hours standing in the pipe.
H. Disposal of flushed chlorinated water shall be at the responsibility of the Contractor.
If Contractor chooses to flush water in the local storm drain system, water shall be
dechlorinated as described in AWWA C655.
3.3 TESTS
A. Samples shall be tested in accordance with ANSI/AWWA C651 for water mains,
C652 for bolted steel storage tanks and hydropneumatic tanks, and C654 for wells.
B. Test shall be taken no more than 10 days prior to the system being placed into
service.
C. If disinfection fails to produce satisfactory test results, the new pipes and facilities
may be re-flushed and retested. If samples taken after re-flushing also fail to
produce satisfactory results, sections represented by those results shall again be
disinfected and retested. The cost of any retests, including time for the Engineer,
shall be borne by the Contractor at no additional cost to the project.
END SECTION
DISINFECTION OF WATER DISTRIBUTION SYSTEM
33 13 00-4
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/c 10c0482-a4d0-4921b-a31b4-
9f292eb232471WOPIServiceld To EGNYTE—PLUS/WOPIUserldl 89.ppeng.egnyte.com/33 13 00 Disinfection of Water Distribution System.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 33 21 00
WATER WELL DRILLING
PART 1 GENERAL
1.1 WORK INCLUDED
A. The work consists of constructing one (1) new well. The work on the well will consist
initially of drilling a pilot hole to a depth of about 700 feet using the reverse circulation
method of drilling and collecting zone specific water samples, as described in these
specifications. If upon completion of the pilot hole and associated test results,
completion of a production well is authorized, the work will additionally consist of
reaming the pilot hole to the final bore hole diameter by the reverse circulation
method of drilling, and constructing and developing a production well.
B. The pilot hole will be used to obtain depth zone specific water samples for water
quality analysis purposes as described in the specifications.
C. The production well is expected to be about 700 feet deep and to be perforated over
200 to 250 feet of the total depth. However, the exact depth and interval of
perforation will be based on the results of the pilot hole drilling and testing.
D. Upon completion of construction of the well, the Contractor shall develop and pump
test the well as described in these Specifications. Contractor shall supply equipment
and labor including variable speed equipment for pump testing. If completion to a
production well is not authorized, Contractor shall properly abandon the pilot hole.
1.2 SUBMITTALS
A. The Contractor shall submit a Mud Program for Engineer's review prior to beginning
work on the well.
B. The Contractor shall prepare a final written report containing, as a minimum, the
following information for the pilot hole and, if authorized, the production well:
1. For the pilot hole: drillers log, electric log, deviation log (geophysical
logging to be performed by a logging subcontractor approved by the
Engineer and paid for by Contractor), and sieve analysis for up to eight
(8) drill cutting samples.
2. For the production well: well log submitted to State showing casing
diameter and wall thickness, lengths and location of casing installed,
type of perforation and aperture size, perforated intervals, bore hole
diameter, cemented conductor casing, gradation of gravel envelope
and location of cement seal.
WATER WELL DRILLING
3321 00-1
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/d 5ed 164c-eeae-427e-b85d-
061e96a38bb3/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/33 21 00 Water Well Drilling.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3. Construction records showing quantity of gravel initially installed,
quantity of gravel added during development operations, development
time, and all other pertinent information.
4. Development and test records showing production rate, static water
level, pumping water level, drawdown, production of sand, and all
other pertinent information concerning development by pumping.
5. Manufacturer's or suppliers standard literature and certification that the
following materials for the production well comply with this
specification:
a. Well casing
b. Perforated well casing
c. Gravel
d. Cement Grout
1.3 STANDARDS AND PERMITS
A. The well shall be constructed in accordance with the Fresno County Water Well
Ordinance, the California Water Well Standards (California DWR Bulletins 74-81 and
74-90), the AWWA Standard A100-06 for Water Wells, and as described in these
Specifications. The Contractor shall obtain, and pay for, a well drilling permit from
Fresno County, and shall report the results of the drilling to the California Department
of Water Resources.
1.4 EXPERIENCE AND LICENSE
A. Pilot hole and production well shall be drilled by a qualified well driller with experience
in construction of public water supply wells.
B. The Contractor shall have at least 5 years experience in drilling public water supply
wells to a depth of at least 700 feet using the drilling, construction, development, and
test pumping methods as specified. The Contractor shall submit to the Owner and
Engineer three references for whom reverse rotary drilling of public supply wells, as
described in these Specifications and to at least these depths, was performed and
for whom water samples were collected from the pilot holes as specified herein. In
listing these references, the Contractor shall give the name of the person or firm for
whom the work was performed, the address and telephone number at which that
person or firm can be contacted, and a description of the work performed.
C. Well driller must possess a C-57 Well Drillers License, valid in the State of California.
1.5 ORDER OF WORK
A. Upon completion of the pilot hole, Contractor shall furnish copies of the drilling log,
electric log (e-log), deviation log, and suitable bagged drill cutting samples for review
by the Engineer.
WATER WELL DRILLING
3321 00-2
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/d 5ed 164c-eeae-427e-b85d-
061e96a38bb3/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/33 21 00 Water Well Drilling.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
B. Engineer shall be allowed up to thirty (30) calendar days from completion of zone
specific water sampling to review the pilot hole data and to determine if the
production well is to be built and prepare the final well design.
C. The Contractor shall fill the remainder of the pilot hole with gravel or native material
after completing depth zone sampling.
D. Construction of a production well shall not proceed until Engineer has made final
recommendation of construction details.
E. Upon completion of the production well, development and pump test, Contractor shall
furnish a copy of the pump test data to the Engineer.
1.6 WORK TO BE PERFORMED BY THE CONTRACTOR
A. All drilling, casing, sealing, developing, test pumping, and other work incidental to
the well shall be performed by the Contractor. The Contractor shall drill the pilot hole
by the reverse rotary method and, as authorized, the production well using the
reverse rotary method and shall provide all necessary equipment for development
and test pumping of the wells. Contractor shall provide temporary pump equipment
for test pumping.
B. The Contractor will prepare and maintain access to the work area as well as provide
sufficient room for the efficient operation of his equipment. Contractor shall provide
temporary fencing to enclose the work area and all stored equipment. The Contractor
will be held as having examined the drilling site and access roads in order to acquaint
himself with local conditions, as no allowance will be made after the bid has been
accepted for any errors or omissions made by the Contractor due to site conditions.
C. The Contractor shall diligently pursue all work to completion. Upon completion of the
well, the Contractor shall level the drill site, and remove all materials incidental to the
drilling operations.
D. The Contractor shall, at his own expense, furnish all equipment, material (including
lost circulation materials), supplies, and personnel necessary to perform the work
(including, but not limited to, drilling rig, water truck, a crew comprised of experienced
drillers, and helpers).
E. The Contractor shall pay any federal, local, or state taxes assessed or levied on
account thereof, in accordance with the practices generally acceptable for the nature
of work to be performed under this Contract.
F. The entire cost of furnishing, transporting, unloading, hauling, handling, sorting, and
caring for all equipment, materials, tools, and supplies, and of removing same from
the site of the work as hereinafter specified, shall be included in prices bid in the
proposal for the work for which the materials are required. The drilling shall be done
with well drilling equipment of proper type and size and in good working condition so
that the work can be performed without interruption arising from defective or improper
equipment. All materials that will become a part of the completed work shall be new.
WATER WELL DRILLING
3321 00-3
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/d 5ed 164c-eeae-427e-b85d-
061e96a38bb3/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/33 21 00 Water Well Drilling.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
All equipment, materials, tools, and supplies not a part of the completed well shall
remain the property of the Contractor and shall be removed from the site upon
completion of the work. All materials to be stored shall be stored at the drilling site
within a fenced enclosure.
G. Contractor shall be responsible for disposing of all excess material and debris
produced by construction activities.
1.7 SECURITY
A. The Contractor is responsible for all site safety and security. The actual work area,
including the mud pit and drilling rig, shall be secured by the Contractor during the
entire duration of the construction. Contractor may elect to install the new permanent
fence per plans at the beginning of the project to secure the site or utilize temporary
fencing. If permanent fencing is used, the contractor will be required to replace
section of fences that may be damaged during construction. If Contractor elects to
use temporary fencing instead of permanent fence, the Contractor shall install a
temporary 6-feet high chain link fence during entire duration of construction
operations. If installed, the fence shall be constructed and maintained in good
condition throughout the course of the work so as to exclude unauthorized persons
and animals from the well site. The fenced area shall be posted with "NO
TRESPASSING"signs visible from all angles of approach. Installation of a temporary
fence is at the Contractor's option and shall be included, if determined necessary by
the Contractor, in the Bid Schedule submitted and no additional compensation for
site security will be made after the bid has been submitted.
B. The Contractor shall provide, at all times during the duration of the Contract, suitable
means of protecting the borehole and well casing from the entrance of foreign
objects.
1.8 NOTIFICATION
A. The Contractor shall give notice to the Engineer of specific operations as follows:
1. At least seventy-two (72) hours advance notice of start of drilling
operations at the well site.
2. At least eight (8) hours notice of geophysical logging.
3. At least six (6) hours advance notice of start of "depth zone airlifting"
from the pilot hole at each depth interval.
4. At least twenty-four (24) hours advance notice of installation of casing
(including conductor), gravel, and annular seal.
5. At least twenty-four (24) hours advance notice of commencement of
development of the completed production well.
6. At least twelve (12) hours advance notice of the pump test.
7. At least twenty-four (24) hours advance notice of video survey and
casing alignment test.
WATER WELL DRILLING
3321 00-4
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/d 5ed 164c-eeae-427e-b85d-
061e96a38bb3/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/33 21 00 Water Well Drilling.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
B. Upon completion of the pilot hole and completion of zone specific water sampling,
the Owner shall have up to thirty (30) calendar days to review the results of the
geologic and a-logs, and to obtain and review the results of the sieve analyses and
the results of the water quality testing, whereafter the Owner shall instruct the
Contractor whether to proceed with a production well or abandon the pilot hole. If a
production well is built, the exact casing schedule, slot size, gravel packed interval,
and gravel gradation will be provided by the Engineer.
1.9 WELL ABANDONMENT
A. In the event the Contractor shall abandon a hole or well because of loss of tools or
other causes which are his responsibility, or if the well fails to conform to these
Specifications and the Contractor is unable to correct the condition at his own
expense or negotiate a mutually-acceptable cost reduction for deviations from the
Plans and Specifications, it shall be considered an abandoned hole, and the
Contractor shall immediately start a new well at a nearby location designated by the
Engineer. The Contractor may salvage as much undamaged materials from the
initial well as possible to be used in the new well. The Contractor shall destroy the
old hole (at Contractor's expense) by filling with sand-cement grout completely from
bottom to top and in conformance with regulations of the Fresno County Water Well
Ordinance. Contractor shall notify Fresno County Health Department and arrange
for Health Department inspector to witness sealing.
PART 2 PRODUCTS
2.1 CONDUCTOR CASING
A. Conductor casing shall be manufactured in accordance with the latest edition of
ASTM A252, Grade 2 and the following conditions:
1. The diameter shall be 30 inches (nominal), and the wall thickness shall
be 0.375 inches.
2. The casing sections shall be factory assembled in not less than 20-
foot lengths.
2.2 WELL CASING
A. Well casing shall be new, in "straight from the factory" condition and shall be
manufactured in accordance with the latest edition of ASTM A53, Grade B, with the
following conditions:
1. The casing will be 12 inches (nominal) diameter. The wall thickness
shall be a minimum of 0.3125 inches.
2. Casing used in the well shall be of uniform outside diameter and wall
thickness and shall be factory assembled in not less than 40-foot
lengths. The exact depth of the production well and location of the
perforated sections shall be specified by the Engineer after all results
from the zone sampling have been received and evaluated.
WATER WELL DRILLING
3321 00-5
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/d 5ed 164c-eeae-427e-b85d-
061e96a38bb3/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/33 21 00 Water Well Drilling.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3. For field assembly by welding, ends of sections shall be furnished with
collars. The collars shall be of the same thickness and have the same
chemical and physical properties as the corresponding casing section,
shall be 5 inches in width, shall be rolled to fit the outside diameter,
and shall be welded to the casing section. The inside edge of the
collars and the outside edge of the adjacent casing length shall be
ground or sufficiently scarred to remove sharp edges or burrs. Section
ends shall be machined flat, perpendicular to the axis of the casing,
and shall not vary more than 0.010 inches at any point from a true point
at right angles to the axis of the casing. Diametrical clearance between
casing O.D. and collar I.D. shall be 1/16 inch ± 1/32 inch.
4. Alternatively, the casing sections may be provided with machined
beveled joints and butt welded. The welding rod shall be of equal or
better A.S.M.E. rating than that of the parent metal. Full penetration,
double pass welds shall be used on each joint. An alignment clamp
must be used and care taken to ensure the casing sections are
properly aligned.
5. If collared pipe is used, three 3/8-inch x 1-inch alignment holes shall
be provided in each collar to ensure proper matching of the sections.
All of these holes shall be completely filled by welding when the casing
is installed.
2.3 PERFORATED WELL CASING
A. Vertical mill slot perforated well casing shall be manufactured in accordance with the
aforementioned casing requirements. Casing of 12 inches (nominal) diameter will
be used, and wall thickness shall be a minimum of 0.3125-inch. The openings in the
perforated casing shall be machine made vertical to the axis of the casing. For
bidding purposes, assume 48-Row perforated casing with a perforation size of 0.060-
inch. Information obtained from the pilot hole will be used to determine the size of
the openings, depths of the well, and lengths of blank and perforated casing.
Perforated well casing shall be of identical inside diameter and wall thickness as the
blank casing.
2.4 COMPRESSION SECTIONS
A. Compression sections of well casing shall be manufactured in accordance with the
aforementioned casing requirements. Casing of 12 inches (nominal) diameter will
be used, and wall thickness shall match the specified casing requirements. The
compression section may be of either a single style or double style configuration.
The shell (outer) casing diameter shall be two inches larger than the parent casing.
The shell casing shall reduce to the parent casing size at the lower end (single style
type) and be connected to the parent casing as specified in the aforementioned
casing requirements. The parent casing shall be able to telescope freely within the
casing length of the outer shell casing. Integral beveled steel rings shall be welded
to the parent casing and shell casing acting as stops and stabilizers. The casing
stabilizers on the parent casing shall include elastomeric seals to seat against the
ring stops on the shell casing. The compression sections shall have an overall length
of 20 feet and allow 10 feet of movement.
WATER WELL DRILLING
3321 00-6
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/d 5ed 164c-eeae-427e-b85d-
061e96a38bb3/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/33 21 00 Water Well Drilling.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2.5 GRAVEL
A. The gravel shall be composed of sound, durable,well-rounded, naturally stream worn
particles, containing no silt, clay, organic matter, or deleterious materials. No
crushed rock will be accepted. Information obtained from the pilot hole will be used
to determine the required gravel size. For bidding purposes, assume SRI Supreme
6x12 Gravel Pack gravel is to be used.
2.6 NEAT CEMENT OR SAND CEMENT GROUT
A. Sand cement grout shall be composed of not more than two parts by weight of sand
and one part of Portland Type II cement to 4.5 to 6.5 gallons of clean water per sack
of cement.
2.7 DRILLING FLUID
A. Water alone shall be employed as a drilling fluid in the pilot hole as well as in the
production well unless prior approval is given by the Engineer.
B. The Contractor shall submit a Mud Program to the Engineer for review.
C. The Contractor shall dispose of surplus drilling fluid in a manner acceptable to the
Owner and Engineer. Contractor is responsible for making the necessary
arrangement with a property owner to dispose of mud, cuttings and development
water. County has contacted the property owner immediately south of the school
grounds (APN 03518044) and they are willing to cooperate with County and
Contractor. Refer to section 5-1.20B(4) of the special provisions for contact
information and necessary documentation.
D. The Owner will allow use of water from the onsite storage tank. Refer to specification
01 51 36.
2.8 VENT PIPE AND GRAVEL CHUTE
A. In accordance with the Plans and as described below, the following items shall be
installed.
1. A 2-inch Schedule 40 steel vent pipe shall be welded to the well casing
as shown on the Plans. The upper end of the vent pipe shall be
threaded and provided with a screened, inverted vent.
2. A 3-inch Schedule 40 steel gravel fill pipe shall be installed as shown
on the Plans. The upper end of the pipe shall be threaded and
provided with a cap as shown on the Plans. The cap shall be marked
with the termination depth of the pipe.
WATER WELL DRILLING
3321 00-7
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/d 5ed 164c-eeae-427e-b85d-
061e96a38bb3/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/33 21 00 Water Well Drilling.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
PART 3 EXECUTION
3.1 COMMUNICATIONS WITH CONSTRUCTION SUPERVISOR
A. A fluent English-speaking supervisor shall be on-site at all times work is occurring on
the work site.
3.2 HOURS OF OPERATION
A. Drilling operations may proceed continuously, 24 hours per day. When work is
expected to occur between the hours of 7 pm and 7 am the Contractor shall notify all
residents within 500 feet of the impending construction activity.
B. Opening of the borehole to final diameter and installation of casing and gravel shall
proceed continuously until complete.
3.3 INSTALLING CONDUCTOR CASING
A. A 30-inch conductor casing shall be installed to a depth of at least 50 feet below
natural grade and include an extension at least 6-inches above the ground. If an
adequate clay layer is not present at that depth, the depth shall be increased as
directed by the Engineer. The conductor casing shall be set in a hole not less than
36 inches in diameter. It shall be securely anchored at the ground surface to prevent
falling.
B. Care shall be taken to install the conductor casing plumb. Centralizers shall be
welded to the conductor casing at intervals not to exceed 20 feet to center the casing
in the bore. The centralizers shall be constructed of 3/8-inch-thick by 2-inch-wide
steel strips so shaped as to form a guide approximately 2.5 inches from the casing
well.
C. Each strip shall provide at least 1-foot length of bearing surface at the bore interface.
A minimum of three strips shall be provided at each circumferential location for
centering the casing. Centralizer strips shall be located on the same vertical
alignment to minimize interference with placing the sealing material as specified.
D. After the conductor casing has been installed, the annular space between the
conductor casing and the bore hole shall be sealed with cement grout. The cement
grout shall be placed by pressure grouting with the use of a tremie pipe. The cement
grout shall be placed through the tremie pipe, and the pipe shall be gradually
withdrawn as the cement rises in the annulus. The quantity of cement grout placed
in the annulus shall not be less than the computed volume of the annulus. A quantity
less than the computed value will be judged as an indication of voids, and measures
shall be taken by the Contractor to eliminate the apparent voids. Upon completion of
cementing, cement shall be visible above the surface of the ground outside the
conductor casing. After cementing operations are completed, the cement shall be left
undisturbed for a period of not less than 24 hours. Contractor shall notify Fresno
County Health Department prior to placing the grout seal.
WATER WELL DRILLING
3321 00-8
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/d 5ed 164c-eeae-427e-b85d-
061e96a38bb3/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/33 21 00 Water Well Drilling.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3.4 METHOD OF DRILLING
A. The pilot hole and the production well, as authorized, shall be drilled by the reverse
rotary method of drilling.
3.5 MUD PIT DESIGN
A. Mud pits shall be above ground dual-pits, with the ability to isolate each pit
compartment from the other during depth zone development and shall be of sufficient
size and configuration to ensure adequate removal of cuttings from fluid before
returning into the borehole.
3.6 PILOT HOLE DRILLING
A. The standard reverse rotary method will be used to drill the pilot hole to an anticipated
depth of about 700 feet. The exact depth to which the pilot hole shall be drilled will
be determined by the Engineer. The Contractor shall be responsible for keeping the
hole open to the total depth of the hole. The hole will be a minimum of fifteen inches
in diameter. The purpose of the pilot hole is to allow collection of drill cuttings and
geophysical logging of the hole upon completion to the total depth. In addition, the
pilot hole will be used to obtain depth zone specific water samples for water quality
testing.
B. Samples of drill cuttings from the bottom of the conductor casing to total depth shall
be collected at changes of strata or at 10-foot depth intervals, whichever is less, and
placed in separate bags or containers. These samples shall be plainly marked with
the depth. One set of samples shall be collected and marked.
C. The Engineer shall select up to eight cutting samples for sieve analysis to allow final
design of slot size and gravel gradation. Contractor shall be responsible for having
the sieve analysis performed, at the Contractor's expense.
D. Electric and Deviation logs will be run in the pilot hole. The Contractor will be
responsible for retaining the Engineer approved logging subcontractor, at the
Contractor's expense, to perform the geophysical logging. Contractor shall remain
at the site during logging and cooperate with the subcontractor in running the logging
tools in the hole. Results of the deviation log must indicate the pilot hole does not
deviate more than six inches per 100 feet in any portion of the completed borehole.
All work shall conform to the specifications of the Owner, the County of Fresno, the
State of California Standard Specifications, and local and State permits and
ordinances for drilling of pilot holes and wells.
3.7 DEPTH ZONE SPECIFIC WATER SAMPLING
A. After completion of pilot hole drilling and logging, the Contractor will perform depth
zone specific water sampling. Upon notification by the Engineer to perform such
sampling, the Contractor will prepare a formation testing tool to sample formation
water from selected depths. The tool will consist of approved diameter pipe that
contains a perforated section on the lower end of the casing, with a plate welded to
WATER WELL DRILLING
3321 00-9
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/d 5ed 164c-eeae-427e-b85d-
061e96a38bb3/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/33 21 00 Water Well Drilling.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
the bottom of the section. The contractor shall have sufficient segments of perforated
section of the tool such that the available length of perforations are approximately
10-feet, 20-feet, 30-feet, and 40-feet. The tool will be connected to approved
diameter drill pipe to allow air-lifting a minimum flow of water of 200 gpm against a
head of 300-feet.
B. Engineer, upon review of drill cuttings and geophysical log, shall determine zones to
be sampled and location of bentonite seals. Prior to placing the drill pipe and testing
tool at the lowest desired depth, a 10-foot seal shall be placed in the hole. Then with
the drill pipe and testing tool set at the desired depth, a sufficient amount of selected
gravel will be placed in the hole to fill to a depth as specified for each zone. In order
to facilitate sampling, the gravel pack material for sampling should be selected to
screen out the finest formation encountered and to be compatible with the 1/1 6-inch
sampling tool slot. Then 5-feet of fine sand will be placed atop the gravel followed
by 10-feet of bentonite placed on the sand. The gravel, sand and bentonite shall be
placed with a tremie pipe.
C. After the bentonite seal has set, the well should be air-lifted at a rate of 200 gpm, if
possible, for at least 6 hours and until the turbidity substantially decreases. A
submersible pump shall then be installed and pumped at a rate of at least 70 gpm
for at least six hours. The time to be recorded shall commence when the equipment
is installed in the well and is placed in operation and shall end when the pumping is
stopped. When the sampling at that zone is completed the string of tools shall be
raised to the next zone to be tested. The testing tool shall be tripped out of the hole
and cleaned between zone setups as necessary. Seals, sand, and gravel shall be
placed as in the first zone tested. It is anticipated that up to three (3)formation tests
will be conducted in the pilot hole, although the Engineer may modify this number.
After the last sample is collected, the remainder of the hole shall be filled with gravel.
Engineer shall be allowed thirty (30) calendar days to review the pilot hole data.
D. Full payment for formation testing shall be provided as specified and no additional
payment will be made. The Contractor will not be paid for formation testing hours
required as a result of negligence on his part.
E. Engineer and Owner will be responsible for collecting water samples and for water
quality testing expenses.
3.8 PILOT HOLE ABANDONMENT
A. If upon completion of the pilot hole, and associated test results, the Owner decides
not to proceed with a production well, the Contractor shall destroy the pilot hole by
filling with sand-cement grout to top and in conformance with the specifications of
the Owner, the County of Fresno, the State of California Standard Specifications,
and local and State permits and ordinances for abandonment of test wells.
WATER WELL DRILLING
3321 00-10
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/d 5ed 164c-eeae-427e-b85d-
061e96a38bb3/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/33 21 00 Water Well Drilling.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3.9 REAMING HOLE AND INSTALLING BLANK AND PERFORATED WELL
CASINGS
A. The pilot hole shall be reamed to a final minimum diameter of 24-inches from the
bottom of the conductor casing to a depth of up to 700 feet. Contractor shall not
begin the drilling operation until all casing and gravel is on-site. The final drilling
operation shall be continuous (non-stop) through the entire length of bore to be
developed into the completed well unless permitted or specified otherwise by Owner
in writing. The exact depth of reaming shall be determined by the Engineer after the
pilot hole is completed and all information interpreted. Perforated casing will be
required as shown on the Plans or as modified by the Engineer after all results from
the zone sampling have been received and evaluated.
B. Prior to installing the casing, clean water shall be circulated in the bore hole to
remove the drilling fluid and any cuttings caked to the side of the drilled hole.
C. Upon completion of reaming the borehole to the final diameter, and after clean water
has been circulated in the hole to remove drilling fluid and caked cuttings, a caliper
log shall be run by a subcontractor approved by the Engineer.
D. Casing installation shall be by methods that will ensure no damage to blank casing,
perforated casing, or the hole. The casing shall be suspended above the bottom of
the hole to ensure that it will not be supported from the bottom.
E. Except when drilling is in progress, casing is being installed, or gravel is being placed,
the top of the well shall be kept securely capped, both day and night, to effectively
prevent tampering or entrance. Upon completion of well casing installation, placing
of gravel envelope, and development and testing of well, a steel top plate shall be
installed on the top of the well casing. The plate shall be welded around the full
circumference.
F. Centralizers shall be welded to the casing at intervals not to exceed 80 feet to center
the casing in the bore. Centralizers shall also be installed at 5 feet from top of and
bottom of the casing. The centralizers shall be welded at both points which contact
the casing. Centralizers shall be constructed of 3/8-inch-thick steel strips at least 2
inches wide so shaped as to form a guide approximately 2 1/2 inches from the casing
well. Each strip shall provide at least 1-foot length of bearing surface at the bore
interface. At least three strips shall be provided at each centralizer location.
Centralizer strips shall be placed on the same vertical alignment to minimize
interference with placing of gravel or sealing material.
G. 10 feet of blank casing shall be installed at the bottom of the well. The bottom of the
casing or screen is to have a 5/16-inch minimum thickness rounded steel cap welded
to casing.
H. The welder required for final assembly of well casings and screen shall be qualified
in accordance with the latest revision of the section titled "WELDING
PROCEDURES" of the ASME Boiler Construction Code or by the AWS Standard
Qualifications Procedure.
WATER WELL DRILLING
3321 00-11
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/d 5ed 164c-eeae-427e-b85d-
061e96a38bb3/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/33 21 00 Water Well Drilling.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
I. The casing shall be lowered in the well with the collar facing upward. The plain end
of the following length shall be inserted in the collar. True contact of the two joints
must be verified by observation through the inspection windows. Spot welds shall
be placed through the three windows to hold the contact position. A filet type weld
shall be made covering the top edge of the collar continuously for the entire
circumference. Two welding passes shall be applied to 5/16 inch and thicker wall
material. The inspection windows on all casing sections shall be seal welded to
assure a leak-proof connection.
3.10 FURNISHING AND INSTALLING GRAVEL ENVELOPE
A. The gravel shall be placed using double hopper and tremie pipe equipment. The
rate at which gravel is allowed to drop from the upper hopper into the lower hopper,
where water is added, shall result in a free-flowing water/gravel mix. The
water/gravel mix shall be pumped into the tremie pipe from the lower hopper.
Placement shall start with the tremie pipe near the bottom of the hole. The tremie
pipe shall be withdrawn from the well at such a rate that the bottom of the tremie pipe
is within a few feet of the top of the gravel pack. From time to time during the gravel
packing operation, the flow of gravel shall be interrupted, the tremie pipe allowed to
empty of gravel, and the top of the gravel located by "sounding" with the tremie pipe
or other device.
B. Prior to placing the gravel in the well, a granular hypochlorite or similar disinfectant
shall be added to the gravel at the rate of at least 1/2 pound per cubic yard of gravel,
based on 70% chlorine content. If a lower strength hypochlorite, or other chlorine
product is used, the quantity shall be adjusted accordingly.
C. The quantity of gravel placed in the annulus of the well shall not be less than the
computed volume of the annulus. A quantity less than the computed value will be
judged as an indication of voids, and measures shall be taken by the Contractor to
eliminate the apparent voids. Significant differences between the estimated and final
volume of gravel installed may be grounds for rejection of the well.
D. Prior to placing the annular seal, the Contractor shall dry swab (no airlifting) across
all perforated casing. The dry swabbing operations shall commence at the bottom
of the lowest perforated section and work upward in short screen intervals of not
more than 20 feet to the top of the uppermost perforated casing section. The swab
shall be repeatedly hoisted at each increment.
E. The Contractor shall tag the top of the gravel envelope after dry swabbing operations
and add gravel (by the method as specified above) to bring the level back up to the
depth specified by the Engineer, if required.
3.11 INSTALLING CEMENT ANNULAR SEAL
A. A cement grout seal shall be installed in the annular space above the gravel pack
between the wall of the bore hole and the well casing and shall be a minimum of 3
inches thick. The cement grout shall be sand-cement. The well casing shall be filled
with water during placement of the grout seal. The Contractor may install the cement
WATER WELL DRILLING
3321 00-12
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/d 5ed 164c-eeae-427e-b85d-
061e96a38bb3/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/33 21 00 Water Well Drilling.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
grout in lifts to prevent casing collapse, if deemed necessary by the Contractor.
Contractor shall notify Fresno County Health Department prior to placing the grout.
B. The bottom five feet of the sealed section shall consist of five feet of bentonite. The
bentonite product used shall be approved by the Engineer prior to placement and
shall be placed using a tremie pipe.
C. The cement grout shall be placed by pressure grouting with the use of a tremie pipe.
Grout placement shall start with the tremie pipe at the bottom of the area to be
grouted. The cement grout shall be placed through the tremie pipe, and the pipe
shall be gradually withdrawn as the cement rises in the annulus. The quantity of
cement grout placed in the annulus shall not be less than the computed volume of
the annulus. A quantity less than the computed value will be judged as an indication
of voids, and measures shall be taken by the Contractor to eliminate the apparent
voids.
D. Significant differences between the estimated and final volume of the cement seal
may be grounds for rejection of the well.
E. The cement seal will extend from the ground surface to a depth as shown on the
Plans, or as indicated by Engineer after all results from the zone sampling have been
received and evaluated.
F. Each cement seal shall be allowed to set for 24 hours prior to further operations.
3.12 PRELIMINARY DEVELOPMENT
A. Preliminary well development will begin by airlifting open-ended at the bottom of the
well until the heaviest fluids are removed.
B. Swabbing and airlifting shall then be used for preliminary development. The
swabbing and airlifting operations shall commence at the bottom of the lowest
perforated casing section and work upwards in short screen intervals of no more than
20 feet. The swab shall be repeatedly hoisted at each increment. Upon reaching
the top of the uppermost perforated section the airlift swabbing shall begin again at
the bottom of the well and proceed upward, in similar manner, to the top of the
perforations again.
C. Preliminary well development will conclude by airlifting open-ended at the bottom of
the well to remove any heavy fluids and fill.
D. During preliminary development the Contractor shall monitor the level of gravel in the
gravel fill pipe and add material as necessary.
E. The well shall then be developed by pumping and surging with a test pump. The
pumping equipment shall be clean and in good operating condition upon delivery to
the site. Within not more than seven (7) days after completion of preliminary
development, the Contractor shall commence well development by pumping and
surging.
WATER WELL DRILLING
3321 00-13
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/d 5ed 164c-eeae-427e-b85d-
061e96a38bb3/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/33 21 00 Water Well Drilling.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3.13 DEVELOPMENT BY PUMPING
A. The Contractor shall install, operate, and remove a pump for developing the well.
The pump shall have a capacity in excess of 750 gpm against a total head of 500
feet measured at the discharge head. The prime mover shall be a variable speed
type. Up to 600 feet of column pipe, tube and shaft shall be provided with the
development pump. The development pump setting will be determined by the
Engineer after well construction. Pump development shall be performed in
conformance with these specifications and in consultation with the Engineer.
B. Contractor is responsible for containing and disposal of initial development water.
Contractor is responsible for making the necessary arrangement with a property
owner to dispose of development water. County has contacted the property owner
immediately south of the school grounds (APN 03518044) and they are willing to
cooperate with County and Contractor. Refer to section 5-1.20B(4) of the special
provisions for contact information and necessary documentation.
C. The Contractor shall install discharge piping from the pumping unit of sufficient size
and length to conduct water to the point of disposal together with a totalizing flow
meter that will accurately measure the flow rate. Discharge piping as required shall
be provided by the Contractor. The Contractor shall provide a manometer to check
the accuracy of the totalizing flow meter. The totalizing meter shall be accurate within
plus or minus 5% of the flow rate indicated by the manometer. If the totalizing meter
is not within this tolerance it will be recalibrated or replaced until it does operate within
this tolerance. Gauges, valves, meter, manometer, access tubes, and other
equipment required shall be installed prior to start of pump development. The
Contractor shall cooperate with the Engineer who will be present periodically during
the well development.
D. The initial pumping rate shall be restricted (100 gpm) and as the water clears shall
be gradually increased in 50 gpm steps until the maximum rate is reached.
Development shall continue at each step rate for a minimum of one hour. At intervals
of approximately 10 to 15 minutes, the pump shall be stopped and the water in the
pump column shall be allowed to surge back through the pump bowls and through
the perforated area.
E. Development records shall be maintained on at least a 1/2-hour interval showing
pumping rate, pumping level, and sand production. Development shall continue until
the following conditions are met:
1. The specific capacity (gpm per foot of drawdown) no longer increases
with time.
2. Sand production is no greater than five (5) ppm within 10 minutes after
commencement of pumping at the capacity of the well. Failure to meet
this requirement may be sufficient cause for rejection of the well.
F. The Contractor shall be responsible for disposing of all development and test water.
Water, including mud, sand and debris pumped from the well during developing and
testing shall be disposed of by the Contractor in such a manner as not to damage or
WATER WELL DRILLING
3321 00-14
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/d 5ed 164c-eeae-427e-b85d-
061e96a38bb3/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/33 21 00 Water Well Drilling.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
interfere with other work. The disposal and discharge sites shall be approved by the
Owner. Contractor is responsible for making the necessary arrangement with a
property owner to dispose of mud, cuttings and development water. County has
contacted the property owner immediately south of the school grounds (APN
03518044) and they are willing to cooperate with County and Contractor. Refer to
section 5-1.20B(4) of the special provisions for contact information and necessary
documentation.
G. Development pumping and surging (not including pump test) is expected to be
completed within 40 hours of total pumping time.
H. The Contractor may submit alternate development methods in writing for approval
by the Engineer. However, the submittal must be prior to commencement of the
production well drilling operation.
3.14 TESTING FOR YIELD AND DRAWDOWN
A. Following development of the well, the Contractor shall perform a complete pumping
test of the well including step rate and recovery tests. The Contractor shall cooperate
with the Engineer who will be present during the test pumping procedure. The actual
test pumping rates will be furnished by the Engineer upon completion of well
development. Well shall remain idle for at least 12 hours overnight prior to
commencement of test, and static or non-pumping level shall be determined prior to
the pump test.
B. The pumping equipment shall be of the variable speed type and shall be the same
equipment as used during the well development procedure. Gauges, valves, meter,
manometer, access tubes, and other equipment required shall be installed prior to
beginning the pump test procedure.
C. The pump shall be operated continuously for a period of 12 hours at the rates
selected by the Engineer. The pumped water shall be disposed of in a manner similar
to the development water.
D. During the test, the discharge of the pump shall be measured with an accurate
totalizing meter supplied by the Contractor and approved by the Engineer.
Additionally, the Contractor will provide a manometer to allow a check of the accuracy
of the totalizing flow meter. The totalizing flow meter shall be accurate within plus or
minus 5% of the flow rate indicated by the manometer. The pump discharge shall
be maintained during the test within plus or minus five (5) percent of the desired
pumping rate by means of a gate valve. Prior to the start of the test, the pump shall
be adjusted to each of the prescribed pumping rates to determine the appropriate
motor speeds (rpm) and discharge valve positions to facilitate rapid adjustment of
the pump at the commencement of testing.
E. Upon completion of the pump test the well shall remain undisturbed for a period of at
least 12 hours to allow water recovery rates to be measured. After the pump is
removed, all sand and debris shall be removed from the bottom of the well.
WATER WELL DRILLING
3321 00-15
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/d 5ed 164c-eeae-427e-b85d-
061eMa38bb31WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/33 21 00 Water Well Drilling.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3.15 COMPLETED WELL WATER SAMPLES
A. Water samples will be collected during the pump test. The Contractor shall
cooperate with the Engineer who will collect the samples. Owner will be responsible
for water quality testing expenses.
3.16 PLUMBNESS AND ALIGNMENT
A. The Contractor shall test well for plumbness and alignment by lowering a 40-foot long
"dummy" or cage into the well to the bottom. The outer diameter of the dummy shall
be not more than one-inch smaller than the inside diameter of the well casing. The
dummy shall consist of a rigid spindle with 3-rings, each 12 inches wide and spaced
top-middle-bottom. The central member of the dummy shall be sufficiently rigid to
maintain the concentric alignment of the 3 rings.
B. Should the dummy fail to move freely throughout the length of the well, the well shall
be subject to rejection by the Owner.
C. The Contractor shall guarantee that the well, when completed, shall be sufficiently
straight and plumb to permit the free installation and operation of a deep well turbine
pump normally used in similarly sized casings with the pump bowls set at 600 feet.
3.17 VIDEO SURVEY
A. A color video survey of the entire length of the casing will be performed to verify
casing integrity, location of perforations, and effectiveness of development. The
video survey equipment shall have side scan capability. A DVD with the video log
shall be submitted to Engineer for review prior to casing closure. If further well
cleaning is necessary, Contractor shall do so at his own expense and also pay for an
additional video survey after the well is cleaned.
3.18 CASING CLOSURE
A. Upon completion of work on the well, the production well shall be capped by welding
a 1/4-inch steel plate over the top of the well casing.
3.19 CLEANUP
A. Site shall be returned to essentially original condition upon completion of work. All
temporary fencing shall be removed.
END SECTION
WATER WELL DRILLING
3321 00-16
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/d 5ed 164c-eeae-427e-b85d-
061e96a38bb3/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_128.ppeng.egnyte.com/33 21 00 Water Well Drilling.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 40 05 00
PIPE AND FITTINGS
PART 1 GENERAL
1.1 WORK INCLUDED
A. Furnish, install, and test all water, utility, pipe, fittings, and appurtenances as
indicated and as specified.
1.2 RELATED WORK
A. Section 03 30 00 - Cast-In-Place Concrete
B. Section 09 90 00 - Painting and Coating
C. Section 31 23 17 —Trenching, Backfilling, and Compacting
D. Section 40 05 23 —Valves and Appurtenances
E. Section 40 20 10 — Pipe Supports
1.3 REFERENCES
A. California Plumbing Code
B. American Water Works Association Standards
1.4 SUBMITTAL REQUIREMENTS
A. Submittals shall be in accordance with the Standard General Conditions and the
Supplementary conditions.
B. Submit manufacturer's catalog data. Show manufacturer's model number.
C. Submit dimensions including wall thickness and materials of construction by
reference standard and grade. Submit information on interior and exterior coatings
as applicable.
1.5 QUALITY ASSURANCE
A. All work performed under this section shall meet all recommendations and
requirements of AWWA, California Plumbing Code, NFPA 24, ASTM D2774, and all
other applicable national, state, local, standards and regulations.
1.6 MATERIALS
A. All materials in contact with potable water shall be certified to ANSI/NSF Standard
61.
PIPE AND FITTINGS
40 05 00-1
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/8cb3fb3O-195c-4d 71-ae98-
4c5e2d1aa47e/W0PIService1d_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 00 Pipe&Fittings.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
PART 2 PRODUCTS
2.1 DUCTILE IRON PIPE
A. General: Ductile iron pipe shall conform to ANSI A21.51 (AWWA C151) and shall
be Class 52 unless shown otherwise. Pipe for grooved or flanged joints shall be no
less than Class 53.
B. Joints:
1. Buried pipe and pipe fittings shall have push-on joints or mechanical joints
conforming to AWWA C111. Flanged joints, sleeve-type mechanical
couplings, and grooved-type couplings shall be used when shown.
2. For push-on joints, shape of pipe ends shall conform to ANSI A21.11 (AWWA
C111). Gaskets and lubricant for pipe and fittings shall conform to ANSI
A21.11 (AWWA C111).
3. For mechanical joints, dimensional and material requirements for pipe ends,
glands, bolts, nuts, and gaskets shall conform to ANSI A 21.11 (AWWA
C111). Pipe smaller than 4 inches shall have screwed or grooved joints
4. For flanged joints, ends of pipe shall be provided with flanges conforming to
ANSI A21.15(AWWA C115), and to ANSI B16.5 for 150 lb. class. Bolts, nuts,
and gaskets for flanged connections shall conform to ANSI B18.2.1. For
grooved joints, groove specifications shall conform to ANSI/AWWA C606.
C. Fittings: Fittings with push-on, mechanical joint, grooved joints and flanged ends
shall conform to ANSI A21.53 (AWWA C153). Fittings shall have pressure rating of
350 psi for Y-24" and 250 psi rating for 30"-48" pipe. Fittings shall have cement-
mortar lining equivalent to that of the pipe lining.
D. Coating and Lining: Pipe shall be bituminous seal-coated and cement-mortar lined.
The lining shall conform to AWWA C104.
E. All buried ductile iron pipe shall be encased in an 8-mil lining of polyethylene,
installed per AWWA C105.
2.2 STEEL PIPE
A. General: Steel pipe 12-inches in diameter and smaller shall conform to the
requirements of the "Specifications for Black and Hot-Dipped Zinc-Plated
(Galvanized)Welded and Seamless Steel Pipe for Ordinary Uses (ASTM A53), and
shall be "Standard Weight" Steel Pipe larger than 12 inches in diameter shall be
ASTM Al39, AWWA C200, wall thickness not less than 0.18 inches.
B. Joints: Pipe 4-inches in diameter and larger shall be flanged or shall have grooved
ends for Victaulic-type couplings. Where shown on the Plans, the pipe shall be
flanged or plain end for flanged coupling adapters. Flanges shall be standard 150
psi flanges meeting the requirements of ANSI B16.1. Flanges shall be furnished with
flat faces. Pipe smaller than 4 inches shall have screwed or grooved joints unless
shown otherwise on the Plans.
PIPE AND FITTINGS
40 05 00-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/8cb3fb3O-195c-4d 71-ae98-
4c5e2d1aa47e/W0PIService1d_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 00 Pipe&Fittings.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
C. Fittings: All fittings shall be flanged cast or ductile iron, screwed malleable iron, or
Victaulic-type fittings. The Contractor may substitute Victaulic-type fittings for
flanged fittings or screwed fittings unless the particular joint requires a specific end
for compatibility with a valve or special fitting. All Victaulic-type fittings shall be of
strength equal to the pipes with lining and coatings equivalent to that specified for
the pipe.
D. Unless otherwise specified or noted in the Plans, all steel pipe 2-1/2 inch and smaller
shall be Hot-Dipped galvanized, and pipes larger than 2-1/2 inch shall be black steel
with epoxy or lining with minimum 10 mil dry thickness. Exterior surfaces of all pipe
shall be shop primed. Finish coatings shall be as specified in Section 09 90 00 -
Painting.
2.3 POLYVINYL CHLORIDE WATER PIPE(PVC)
A. General: PVC pipe shall conform to AWWA C900, unless otherwise specified.
B. The pipe shall be minimum PR 235 (DR 18) unless shown otherwise. Each length
of pipe shall be marked with the manufacturer's name, nominal size, pressure
classification, and date of manufacture.
C. Joints: Joints shall be push-on type couplings or integral socket bell PVC pipe
unless otherwise shown with rubber gaskets conforming to ASTM D3139 and ASTM
F477. Integral socket bells of PVC pipe or separate couplings shall meet the same
strength requirements as that of the pipe. All component parts of each joint including
gaskets and coupling shall be clearly marked for use with the pipe for which they
are intended.
D. Fittings: Fittings shall be of ductile iron conforming to ANSI A21.10 (AWWA C 153)
for mechanical joints. Dimensional and material requirements for pipe ends, glands,
bolts, nuts, and gaskets shall conform to ANSI A 21.11 (AWWA C111).
2.4 GROOVED COUPLINGS
A. Groove dimensions shall conform to AWWA C606.
B. Grooved couplings for ductile iron shall be Victaulic Style 31;
C. Flexible grooved couplings for steel pipe shall be Victaulic Style 77 or equal; rigid
grooved couplings for steel pipe shall be Victaulic Style 07 or equal. Couplings shall
be rigid unless otherwise noted on the drawings.
D. Grooved - Flanged adapters shall be Victaulic Style 341 for ductile iron pipe and
Style 741 for steel pipe or equal.
E. Grooved coupling for high density polyethylene pipe shall be Victaulic Style 995 or
997 or equal.
2.5 FLANGED JOINTS
A. Flange shall conform to ANSI B16.5, Class 150.
PIPE AND FITTINGS
40 05 00-3
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/8cb3fb3O-195c-4d 71-ae98-
4c5e2d1aa47e/W0PIService1d_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 00 Pipe&Fittings.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
B. All steel hardware installed underground shall be coated with a rust preventative,
wrapped with 8 mil polyethylene sheeting, and secured with PVC tape.
C. Gaskets shall be meet the pressure requirements of the adjoining flanges and shall
conform to AWWA C-207. Gaskets for flat faced flanges shall be 1/8-inch thick.
D. Gaskets for metallic pipe and non-potable 150 psi or less services shall be acrylic or
aramid fiber bound with nitrile; Garlock Blue-Gard 3000 or equal. EPDM rubber
gaskets, Garlock 98206 or equal, are also acceptable.
E. Gaskets for metallic pipe and potable water service shall be NSF/ANSI-61 certified
EPDM rubber, Garlock 98206 or equal.
F. Gaskets for non-metallic flat faced flanges shall be constructed of a
fluoroelastomeric material with a hardness of 70 durometer designed specifically for
lower seating stress. Gaskets shall be certified to NSF/ANSI-61 for potable water
service. Gaskets shall be Garlock Style XP or equal.
2.6 TRACER WIRE
A. Install No. 10 solid-core copper tracer wire.
2.7 CONCRETE FOR THRUST BLOCKS
A. As specified in Section 03 30 00 — Cast-In-Place Concrete. Thrust blocks shall be
used only where specifically permitted on the drawings or with pre-approval from the
Engineer.
2.8 JOINT RESTRAINT COUPLINGS
A. Mechanical joint restraint coupling shall be of the type that utilizes the follower gland,
and shall consist of several individual lug bolts with gripping mechanism that
prevents the joints from pulling apart. Glands shall be ductile iron conforming to
ASTM A536, and dimensions shall be compatible to be used with standard
mechanical joint fittings for ductile rim pipe. The mechanical restraintjoint shall have
a minimum working pressure rating equal to that of the pipe with a safety factor of
not less than 2. Restrained joints shall have twist off nuts to insure proper installation
of restraining grip mechanism. Mechanical joint restrained coupling shall be EBAA,
Iron, Inc. MEGALUG; with Mega-Bond coating; or approved equal. Coating of
gland follower body shall be electrostatically applied and heat cured polyester
based powder. Wedge assemblies and bolts shall be coated with heat cured
fluoropolymer coatings. Restraints shall be designed for the specific type of
pipe to be restrained.
B. Restrained joint fittings shall meet Uni-B-13 for PVC and be FM and UL approved
through 12-inch for both ductile iron and PVC.
C. Restrained joint fittings for high density polyethylene pipe shall be Victaulic 995 or
997 style coupling.
PIPE AND FITTINGS
40 05 00-4
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/8cb3fb3O-195c-4d 71-ae98-
4c5e2d1aa47e/W0PIService1d_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 00 Pipe&Fittings.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2.9 FASTENERS
A. All fasteners shall include washers under both bolt head and nut unless the use of
washers is incompatible with the fitting design.
B. Unless otherwise noted, all bolts, tie rods, and T-bolts used to secure flanges,
fittings, and couplings located underground or submerged in liquid shall be Type
304 or 316 stainless steel per ASTM A320 or ASTM A193. Nuts shall be 304 or 316
stainless steel per ASTM A194 and washers shall be ASTM F436 Type 3.
C. Unless otherwise noted, all bolts, tie rods, and T-bolts used to secure flanges,
fittings, and couplings located indoors, above grade, and in vaults shall be carbon
steel conforming to ASTM A307, Grade B with ASTM A563, Grade A nuts and ASTM
F436 washers. Bolts, nuts, and washers shall be hot dipped galvanized in
accordance with ASTM F2329. Stainless steel meeting the requirements of
Paragraph B shall also be acceptable.
PART 3 EXECUTION
3.1 HANDLING AND DISTRIBUTION OF MATERIALS
A. Delivery: Handle pipe carefully to ensure delivery at the project site in sound,
undamaged condition. Contractor shall replace damaged pipe at no additional
expense to the Owner.
B. Storage: Do not store materials directly on the ground. Adequately support piping
to prevent warping. Use protective covers where pipe may be damaged by direct
sunlight.
C. No more than one week's supply of material shall be distributed in advance of pipe
laying operations, unless otherwise approved or required.
D. Before laying, pipe shall be inspected for cracked, broken, or defective pieces. Such
pieces shall be rejected. Pipe shall be carefully lowered into the trench to prevent
damage. All dirt or other foreign matter shall be removed from inside the pipe before
lowering into the trench.
3.2 COATING
A. Unless otherwise indicated in Part 2, all pipe and fittings shall be coated in
accordance with specification 09 90 00.
3.3 INSTALLATION OF BURIED PRESSURE PIPING
A. General: Pipe, fittings, and appurtenances shall be installed in accordance with the
manufacturer's instructions and in accordance with the following references as
appropriate:
1. Ductile Iron Pipe - AWWA C600
2. Polyvinyl Chloride Pipe and HDPE pipe - AWWA C605
PIPE AND FITTINGS
40 05 00-5
https://us-partner-i ntegrations.eg nyte.com/msoffice/wopi/files/8cb3fb30-195c-4d 71-ae98-
4c5e2d1aa47e/WOPI Serviceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 00 Pipe&Fittings.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3. Steel Pipe —AWWA C604
B. Handling: The pipe shall be protected to prevent entrance of foreign materials
during laying operations. When laying is not in progress, open pipe ends shall be
protected with a watertight plug or other approved means to exclude water or foreign
material.
C. Alignment:
1. Mains shall be installed to the grades and elevations indicated and shall have
a minimum cover of 30-inches from the top of the pipe to existing ground or
paved surface unless otherwise indicated.
2. The allowable angle of deflection at any joint shall not exceed the amount
recommended by the pipe manufacturer for the particular pipe size used.
Deviation of any pipe section from the line and grade indicated shall not
exceed 1/2-inch.
D. Joints:
1. Pipe shall be assembled and joined in accordance with the manufacturer's
published instructions for the type of pipe and joint used. All portions of the
joints shall be thoroughly cleaned before the sections of pipe are assembled.
The ends of each pipe shall abut against the next pipe section in such a
manner that there shall be no unevenness of any kind along the bottom half
of the interior of the pipe. Where mechanical joints are used, the pipe shall
be marked in such a manner that it can be determined after installation that
the pipe is properly seated.
2. Where flexible couplings are used as expansion joints, the ends of the pipes
shall be separated 1-inch to allow for expansion. The welded seam at the
end of each coupled steel pipe shall be ground smooth for approximately 12-
inches. Couplings shall be centered on pipe ends. Runs of pipe containing
flexible couplings shall be properly blocked, anchored or tied to the structure
to prevent joints from separating.
3. Mechanical restrained joints shall be installed in accordance with joint
manufacturer's instructions and recommendation.
E. Installation of Marker Tape: Install tape in backfill directly over each pipeline, 24
inches over top of pipe, unless shown otherwise on the Plans. Where utilities are
buried in a common trench, identify each line by a separate marker tape. Place
tapes directly over the applicable line.
3.4 THRUST BLOCKS OR MECHANICAL RESTRAINED JOINTS
A. Thrust blocks shall be used only where specifically allowed on the drawings or with
prior approval by the Engineer.
B. When it is necessary to restrain push-on joints adjacent to restrained fittings, a
harness restraint device shall be used. All harnesses shall have a pressure rating
PIPE AND FITTINGS
40 05 00-6
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/8cb3fb3O-195c-4d 71-ae98-
4c5e2d1aa47e/W0PIService1d_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 00 Pipe&Fittings.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
equal to that of the pipe on which it is used. Harness assemblies including tie bolts
conform to ASTM A536.
3.5 INSTALLATION OF EXPOSED PIPING
A. General - Pipe shall be installed as specified, as indicated on the Plans or, in the
absence of detail piping arrangement, in a manner acceptable to the Engineer.
B. Pipe shall be cut from measurements taken at the site and not from the Plans. All
necessary provisions shall be taken in laying out piping to provide throughout for
expansion and contraction. Piping shall not obstruct openings or passageways.
Pipes shall be held free of contact with building construction so as not to transmit
noise resulting from expansion.
C. The inside of all pipe, valves, and fittings shall be smooth, clean, and free from
blisters, loose mill scale, sand, dirt, and other foreign matter when erected. The
interior of all lines shall be thoroughly cleaned, to the satisfaction of the Engineer,
before being placed in service.
D. Stuffing box leakage from water sealed pumps shall be contained and not allowed
to into storm drains.
E. Taps for pressure gauge connections on piping and equipment shall be provided
with a nipple and a ball type shutoff valve. Drilling and tapping of pipe walls for
installation of pressure gauges or switches will not be permitted.
F. A union shall be provided within 2 feet of each end of threaded end valves unless
there are other connections that facilitate easy removal of the valve. Unions shall
also be provided in piping at locations adjacent to devices or equipment that may
require removal in the future and at locations required by the Plans or other sections
of the Specifications.
G. Provide unions on exposed piping and tubing 3-inches and smaller as follows:
1. At every change in direction (horizontal and vertical).
2. Downstream of valves, 6 to 12 inches.
3. As shown on plans.
H. In all piping except air piping, insulating fittings shall be provided to prevent contact
of dissimilar metals.
I. Pipe Joints - Pipe joints shall be carefully and neatly made in accordance with the
requirements that follow.
1. Threaded - Pipe threads shall conform to ANSI/ASME B1.20.1, NPT, and
shall be full and cleanly cut with sharp dies. Not more than three threads at
each pipe connection shall remain exposed after installation. Ends of pipe
shall be reamed, after threading and before assembly, to remove all burrs.
PIPE AND FITTINGS
40 05 00-7
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/8cb3fb3O-195c-4d 71-ae98-
4c5e2d1aa47e/W0PIService1d_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 00 Pipe&Fittings.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
Threaded joints in plastic piping shall be made up with Teflon thread tape
applied to all male threads. Threaded joints in stainless steel piping shall be
made up with Teflon thread sealer and Teflon thread tape applied to all male
threads. At the option of the Contractor, threaded joints in other piping may
be made up with Teflon thread tape, thread sealer, or a suitable joint
compound. Thread tape and joint compound or sealers shall not be used in
threaded joints that are to be seal welded.
Threaded joints in steel piping for chlorine service shall be made up with
Teflon thread tape or paste applied to all male threads.
2. Compression - Ends of tubing shall be cut square and all burrs shall be
removed. The tubing end shall be fully inserted into the compression fitting
and the nut shall be tightened not less than 1-1/4 turns and not more than 1-
1/2 turns past finger tight, or as recommended by the fitting manufacturer, to
produce a leak tight, torque-free connection.
3. Flared - Ends of annealed copper tubing shall be cut square and all burrs
shall be removed prior to flaring. Ends shall be uniformly flared without
scratches or grooves. Fittings shall be tightened as required to produce leak
tight connections.
4. Soldered and Brazed - Where solder fittings are specified for lines smaller
than 2 inches, joints may be soldered or brazed at the option of the
Contractor. Joints in 2 inch and larger copper tubing shall be brazed.
5. Flanged - Flange bolts shall be tightened sufficiently to slightly compress the
gasket and effect a seal, but not so tight as to fracture or distort the flanges.
A plain washer shall be installed under the head and nut of bolts connecting
plastic pipe flanges. Anti-seize thread lubricant shall be applied to the
threaded portion of all stainless steel bolts during assembly. Connecting
flanges shall have similar facings, i.e., flat or raised face.
6. Welded - Welding shall conform to the specifications and recommendations
contained in the "Code for Pressure Piping", ANSI B31.1.
7. Grooved Couplings - Grooves for grooved couplings shall be cut with a
specially designed grooving tool. Grooves cut in steel pipe shall conform to
flexible grooving dimensions as set forth in AWWA C606 and shall be clean
and sharp without burrs or check marks.
3.6 ACCEPTANCE TESTS FOR BURIED PRESSURE PIPING
A. General
1. All testing and inspection shall be performed after final backfill and
compaction operations are complete. If the Contractor so desires, he may
pretest the lines at his own expense, but final testing must be performed after
compaction requirements have been approved.
PIPE AND FITTINGS
40 05 00-8
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/8cb3fb3O-195c-4d 71-ae98-
4c5e2d1aa47e/W0PIService1d_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 00 Pipe&Fittings.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
B. In general, tests shall be conducted in accordance with AWWA C600 and C651
except as otherwise herein specified.
C. All newly installed sections of buried pressure piping shall be pressure and leakage
tested as described herein.
1. For buried pressure pipelines, tests shall be made on two or more valved
sections not to exceed 2,500 feet in length. The Contractor shall furnish all
necessary equipment, material and labor required.
2. Tests shall be made after the trench has been backfilled and compacted, but
not until at least 5 days have elapsed since any thrust blocks in the section
have been poured.
3. The pipe shall be slowly filled with water and ensuring all air expelled from
section being tested. The line shall stand full of water for at least twenty-four
hours prior to testing to allow all air to escape. A test pressure equal to 1.5
times the design pressure, of the pipe measured at the point of lowest
elevation pressure, or 100 psi, whichever is greater, shall be applied.
4. The test pressure in the line shall be maintained for a period of 2 hours. Test
pressure shall be maintained within 5 psi during the test period. Conduct a
leakage test concurrently with the pressure test. Leakage is defined as the
volume of water that must be supplied into the newly laid pipeline to maintain
pressure within +/- 5 psi of the test pressure after it is filled and purged of air.
The water required to maintain test pressure shall be measured by means of
a graduated barrel, drum, or similar device at the pump suction or through a
meter.
Allowable leakage at the specified test pressure shall not exceed the amounts
allowed by AWWA C600, L = SD-y P
148,000
Where:
L = Allowable fluid loss, in gallon per hour.
S = Length of pipe tested, in feet.
D = Nominal diameter of the pipe, in inches.
P = Average test pressure during the hydrostatic test, in pounds per square inch
(psi).
Hydrostatic testing allowance per 1,000 ft. of pipeline in gph.
PSI 4" 6" 8" 101, 12" 14" 16" 18" 20" 24"
PIPE AND FITTINGS
40 05 00-9
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/8cb3fb3O-195c-4d 71-ae98-
4c5e2d1aa47e/W0PIService1d_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 00 Pipe&Fittings.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
200 0.38 0.57 0.76 0.96 1.15 1.34 1.53 1.72 1.91 2.29
175 0.36 0.54 0.72 0.89 1.07 1.25 1.43 1.61 1.79 2.15
150 0.33 0.50 0.66 0.83 0.99 1.16 1.32 1.49 1.66 1.99
125 0.30 0.45 0.60 0.76 0.91 1.06 1.21 1.36 1.51 1.81
100 0.27 0.41 0.54 0.68 0.81 0.95 1.08 1.22 1.35 1.62
5. Should testing disclose any visible leaks or leakage greater than that allowed,
the defective joints or pipe shall be located, repaired, and re-tested until
satisfactory. The cost of any retests, including time for the Engineer, shall be
borne by the Contractor at no additional cost to the project.
3.7 ACCEPTANCE TEST FOR EXPOSED PIPING
A. Pipe to be Tested - All new installed piping sections shall be pressure and leakage
tested as specified herein.
B. Pressure Testing - After the section of line to be tested has been filled with water or
other test media, the test pressure shall be applied and maintained without
interruption for 2 hours plus any additional time required for the Engineer to examine
all piping undergoing the test and for the Contractor to locate all defective joints and
materials.
1. Test medium shall be potable water for potable water piping; all other piping
may be tested using plant water subject to Engineer's approval.
2. Pipe system shall be tested at 1-1/2 times the operating pressure, or 100 psi,
whichever is greater, using the appropriate test fluid medium.
3. All piping shall be tight and free from leaks. All pipe, fittings, valves, pipe
joints, and other materials that are found to be defective shall be removed
and repaired or replaced with new and acceptable material, and the affected
portion of the piping be retested until satisfactory. The cost of any retests,
including time for the Engineer, shall be borne by the Contractor at no
additional cost to the project.
Compressed air or gas under pressure shall not be used to test plastic piping unless
specifically recommended by the pipe manufacturer.
Leakage may be determined by loss of pressure, soap solution, chemical indicator,
or other positive and accurate method acceptable to the Engineer. All fixtures,
devices, or other accessories which are to be connected to the lines and which
would be damaged if subjected to the specified test pressure shall be disconnected
and ends of the branch lines plugged or capped as required during the testing
procedures.
PIPE AND FITTINGS
40 05 00-10
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/8cb3fb3O-195c-4d 71-ae98-
4c5e2d1aa47e/W0PIService1d_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 00 Pipe&Fittings.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
END SECTION
PIPE AND FITTINGS
40 05 00-11
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/8cb3fb3O-195c-4d 71-ae98-
4c5e2d1aa47e/W0PIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 00 Pipe&Fittings.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
This Page is Intentionally Left Blank
PIPE AND FITTINGS
40 05 00-12
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/8cb3fb3O-195c-4d 71-ae98-
4c5e2d1aa47e/W0PIService1d_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 00 Pipe&Fittings.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 40 05 23
VALVES AND APPURTENANCES
PART 1 GENERAL
1.1 WORK INCLUDED
A. This section includes materials, testing, and installation of manually operated
valves and check valves.
1.2 RELATED WORK
A. Section 05 05 20 — Bolts, Washers, Anchors, and Eyebolts
B. Section 09 90 00 — Painting and Coating
C. Section 09 97 57 — Polyethylene Tape Pipe Coating
D. Section 09 97 61 — Fusion-Bonded Epoxy Linings and Coatings
1.3 REFERENCES
A. American Society for Testing and Materials (ASTM)
B. American Water Works Association (AWWA)
1.4 SUBMITTALS
A. Submittals shall be in accordance with Section 01 33 00 — Submittal Procedures.
B. Submit manufacturer's catalog data and detail construction sheets showing all
valve parts. Describe each part by material of construction, specification (such as
AISI, ASTM, SAE, or CDA), and grade or type.
C. Show valve dimensions including laying lengths. Show port sizes. Show
dimensions and orientation of valve actuators, as installed on the valves. Show
location of internal stops for gear actuators. State differential pressure and fluid
velocity used to size actuators. For worm-gear actuators, state the radius of the
gear sector in contact with the worm and state the handwheel diameter.
D. Show valve linings and coatings. Submit manufacturer's catalog data and
descriptive literature.
E. Submit six copies of a report verifying that the valve interior linings and exterior
coatings have been tested for holidays and lining thickness. Describe test results
and repair procedures for each valve. Do not ship valves to project site until the
reports have been returned by the Owner's Representative and marked
"Resubmittal not required."
VALVES AND APPURTENANCES
40 05 23-1
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bdc 11905-faa6-4e6a-b284-
761f74dc511a/W0PlService1d TPEGNYTE PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 23 Valves and Appurtenances.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
PART 2 PRODUCTS
2.1 GENERAL
A. Valves are identified in the drawings by size, category and type number. For
example, a callout in the drawings of 6" Type-1 butterfly valve refers to Type-1
valve in the butterfly valve category in these specifications, which is a Class 125
rubber seated butterfly valve.
B. All valves installed in potable water applications shall conform to California AB
1953 no-lead regulations and ANSI/NSF Standard 61.
C. Install valves complete with operating handwheels or levers, chainwheels,
extension stems, floor stands, gear actuators, operating nuts, chains, and
wrenches required for operation.
D. Valves shall have the name of the manufacturer and the size of the valve cast or
molded onto the valve body or bonnet or shown on a permanently attached plate.
2.2 VALVE ACTUATORS
A. Provide lever or wrench actuators for exposed valves 6 inches and smaller. For
larger valves, provide handwheels.
B. Where manually operated valves (size 4 inches and larger) are installed with their
centerlines more than 6 feet 9 inches above the floor, provide chainwheel and
guide actuators.
C. Provide 2-inch AWWA operating nuts for buried and submerged valves.
D. Design gear actuators assuming that the differential pressure across the plug,
gate, or disc is equal to the test pressure of the connecting piping and assuming a
fluid velocity of 16 fps for valves in liquid service and 80 fps for valves in air or gas
service and a line fluid temperature range of 33°F to 1250F unless otherwise
required in the detailed valve specifications. Size actuators using a minimum
safety factor of 1.5 for valves in open/close service and 2.0 in modulating service.
E. Gear actuators shall be enclosed, oil lubricated, with seals provided on shafts to
prevent entry of dirt and water into the actuator. Gear actuators for valves located
above ground or in vaults and structures shall have handwheels. The actuators for
valves in exposed service shall contain a dial indicating the position of the valve
disc or plug. Gear actuators for buried or submerged valves shall have 2-inch-
square AWWA operating nuts.
F. For buried or submerged service or valves installed in buried vaults, provide
watertight shaft seals and watertight valve and actuator cover gaskets. Provide
totally enclosed actuators designed for buried or submerged service.
G. Traveling nut and worm and gear actuators shall be of the totally enclosed design
so proportioned as to permit operation of the valve under full differential pressure
rating of the valve with a maximum pull of 40 pounds on the handwheel or crank.
Provide stop limiting devices in the actuators in the open and closed positions.
VALVES AND APPURTENANCES
40 05 23-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bdc 11905-faa6-4e6a-b284-
761f74dc511a/W0PlService1d TPEGNYTE PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 23 Valves and Appurtenances.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
Actuators shall be of the self-locking type to prevent the disc or plug from creeping.
Design actuator components between the input and the stop-limiting devices to
withstand without damage a pull of 200 pounds for handwheel or chainwheel
actuators and an input torque of 300 foot-pounds for operating nuts when
operating against the stop.
H. Handwheel diameters for traveling nut actuators shall not exceed 8 inches for
valves 12 inches and smaller and shall not exceed 12 inches for valves 20 inches
and smaller.
I. Design actuators on buried valves to produce the required torque on the operating
nut with a maximum input of 150 foot-pounds.
J. Valve actuators, handwheels, or levers shall open by turning counterclockwise.
2.3 CAST IRON VALVE BOXES AND RISERS
A. Valve boxes shall be Christy G5 with Christy Iron Covers or equal unless
otherwise shown on the Drawings.
B. Risers shall be 8-inch nominal diameter PVC pipe conforming to AWWA C900.
2.4 INDICATOR POSTS
A. Indicator posts for buried gate valves in fire protection service shall be UL listed,
FM approved for use on valves of sizes 4 through 12 inches. Provide a target or
sign visible through a window on both sides of the post that indicates the open or
shut position of the gate valve. Working parts shall be fully enclosed for weather
protection. Body shall be cast or ductile iron. Provide post extension if trench is
deeper than can be served by manufacturer's standard post. Coat buried portion of
indicator posts per Section 09 90 00, System No. 21. Products: Nibco NIP-1,
Stockham Figure G-951, or equal.
2.5 EXTENSION STEMS FOR BURIED AND SUBMERGED VALVE ACTUATORS
A. Where the depth of the valve is such that its centerline is more than 4 feet below
grade, provide operating extension stems to bring the operating nut to a point 6
inches below the surface of the ground and/or box cover. Where the valve is
submerged, provide operating extension stems to bring the operating nut to 6
inches above the water surface. Extension stems shall be Type 316 stainless
steel, solid core, and shall be complete with 2-inch-square operating nut. The
connections of the extension stems to the operating nuts and to the valves shall
withstand without damage a pull of 300 foot-pounds.
B. Extension stem diameters shall be as tabulated below:
VALVES AND APPURTENANCES
40 05 23-3
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bdc 11905-faa6-4e6a-b284-
761f74dc511a/W0PlService1d TPEGNYTE PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 23 Valves and Appurtenances.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
Minimum Extension
Valve Size Stem Diameter
(inches) (inches)
2 3/4
3, 4 7/8
6 1
8 1 1/8
10, 12 1 1/4
14 1 3/8
16, 18 1 1/2
20, 24, 30, 36 1 3/4
42, 48, 54 2
2.6 FLOOR STANDS, EXTENSION STEMS, AND EXTENSION STEM SUPPORT
BRACKETS
A. When required by the installations, provide floor stands and extension stems for
operation of valves. Floor stands shall be of the nonrising stem, indicating type,
complete with steel extension stems, couplings, handwheels, stem guide brackets,
and special yoke attachments as required by the valves and recommended and
supplied by the stand manufacturer. Floor stands shall be cast-iron base type:
Clow, Figure F-5515; Bingham and Taylor; Stockham; or equal. Handwheels shall
turn counterclockwise to open the valves.
B. Provide Type 316 stainless steel anchor bolts.
C. Provide steel extension stems for valves in exposed service. Provide Type 316
stainless steel stems for valves in submerged service.
D. Provide adjustable stem guide brackets for extension stems. The bracket shall
allow valve stems to be set over a range of 2 to 36 inches from walls. Provide
bushings drilled to accept up to 2-inch-diameter stems. Base, arm, and clamp shall
be ductile iron. Coat ductile iron components with fusion-bonded epoxy per
Section 09 90 00. Bushing shall be bronze (ASTM B584, Alloy C86400 or
C83600). Bolts, nuts, screws, and washers (including wall anchor bolts) shall be
Type 316 stainless steel. Provide slots in the bracket to accept 3/4-inch bolts for
mounting the bracket to the wall. Products: Trumbull Industries, Inc., Adjustable
Stem Guide or equal.
2.7 CHAINWHEELS AND GUIDES
A. Chainwheels and guides shall be Clow Figure F-5680, DeZurik Series W or LWG,
Stockham, or equal. Chainwheels and guides shall be galvanized iron or steel.
Chains shall extend to within 4 feet of the operating floor. Chains shall be
galvanized steel.
VALVES AND APPURTENANCES
40 05 23-4
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bdc 11905-faa6-4e6a-b284-
761f74dc511a/W0PlService1d TPEGNYTE PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 23 Valves and Appurtenances.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2.8 BOLTS AND NUTS FOR FLANGED VALVES
A. Bolts and nuts for flanged valves shall be as described in Section 40 05 00.
2.9 GASKETS FOR FLANGES
A. Gaskets for flanged end valves shall be as described in Section 40 05 00.
2.10 PAINTING AND COATING
A. Coat metal valves located above ground or in vaults and structures the same as
the adjacent piping. If the adjacent piping is not coated, then coat valves per
Section 09 90 00. Apply the specified prime coat at the place of manufacture.
Apply intermediate and finish coats in field.
B. Coat buried metal valves at the place of manufacture per Section 09 90 00,
System No. 7.
C. Coat submerged metal valves, stem guides, extension stems, and bonnets at the
place of manufacture per Section 09 90 00, System No. 1.
D. Line the interior metal parts of metal valves 4 inches and larger, excluding seating
areas and bronze and stainless-steel pieces. Lining shall be epoxy similar to
Section 09 90 00, System No. 1. Apply lining at the place of manufacture.
E. Alternatively, line and coat valves with fusion-bonded epoxy per Specification 09
9000.
F. Coat floor stands per Section 09 90 00.
G. Test the valve interior linings and exterior coatings at the factory with a low-voltage
(22.5 to 80 volts, with approximately 80,000-ohm resistance) holiday detector,
using a sponge saturated with a 0.5% sodium chloride solution. The lining shall be
holiday free.
H. Measure the thickness of the valve interior linings per Section 09 90 00. Repair
areas having insufficient film thickness per Section 09 90 00
2.11 PACKING, O-RINGS AND GASKETS
A. Unless otherwise stated in the detailed valve specifications, packing, O-rings, and
gaskets shall be one of the following nonasbestos materials:
1. Teflon.
2. Kevlar aramid fiber.
3. Gaskets for metallic pipe and non-potable 150 psi or less services shall be
acrylic or aramid fiber bound with nitrile; Garlock Blue-Gard 3000 or equal.
EPDM rubber gaskets, Garlock 98206 or equal, are also acceptable.
4. Buna-N (nitrile).
VALVES AND APPURTENANCES
40 05 23-5
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bdc 11905-faa6-4e6a-b284-
761f74dc511a/W0PlService1d TPEGNYTE PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 23 Valves and Appurtenances.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2.12 RUBBER SEATS
A. Rubber seats shall be made of a rubber compound that is resistant to free chlorine
and monochloramine concentrations up to 10 mg/L in the fluid conveyed.
2.13 VALVES
A. Gate Valves:
1. Type 5—Ductile-Iron Resilient Wedge Gate Valves 4 Through 36 Inches
(AWWA C515):
Valves shall comply with AWWA C515 and the following. Valves shall be of
the bolted-bonnet type with nonrising stems. Valve stems shall be Type 304
or 316 stainless steel or cast, forged, or rolled bronze. Provide operating nut
for buried valves. Provide handwheel for exposed valves. Stem nuts shall
be made of solid bronze. Bronze for internal working parts, including stems,
shall not contain more than 2% aluminum or more than 7% zinc. Bronze
shall conform to ASTM B62 or ASTM B584 (Alloy C83600), except the stem
bronze shall have a minimum tensile strength of 60,000 psi, a minimum
yield strength of 30,000 psi, and a minimum of 10% elongation in 2 inches
(ASTM B584 or B763, Alloy C87600 or C99500). Body bolts shall be Type
316 stainless steel. End connections for exposed valves shall be flanged.
End connections for buried valves shall be mechanical joint type.
Provide reduction thrust bearings above the stem collar. Stuffing boxes shall
be 0-ring seal type with two rings located in stem above thrust collar. Each
valve shall have a smooth unobstructed waterway free from any sediment
pockets.
Valves shall be lined and coated at the place of manufacture with either
fusion-bonded epoxy or heat-cured liquid epoxy. Minimum epoxy thickness
shall be 8 mils.
Manufacturers: Clow, AVK, American Flow Control, Waterous, Kennedy, or
equal.
B. Ball Valves:
1. Type 2—Full Port Threaded Bronze Ball Valves 2 Inches and Smaller (Low
Lead):
Ball valves, 2 inches and smaller, for water service shall have a pressure
rating of at least 600 psi WOG at a temperature of 100°F. Provide full port
ball and body design. Valves shall comply with MSS SP-110. Materials of
construction shall be as follows:
VALVES AND APPURTENANCES
40 05 23-6
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bdc 11905-faa6-4e6a-b284-
761f74dc511a/W0PlService1d TPEGNYTE PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 23 Valves and Appurtenances.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
Component Material Specification
Body Bronze ASTM B584, Alloy C89836
Ball Bronze ASTM B584, Alloy C89836 or
Alloy C27450, chromium plated
Ball retainer Bronze ASTM B584, Alloy C89836 or
ASTM B371, Alloy C69430
Stem Bronze Alloy C27450
Seats Reinforced Teflon —
Bronze alloys having a maximum lead content of 0.25%, a maximum zinc
content of 7.0%, and a minimum copper content of 80% may be substituted
for the bronze alloys specified above. Valves shall have threaded ends
(ASME B1.20.1), nonblowout stems, and have plastic-coated lever
actuators.
Valves shall be Apollo 77CLF Series or equal.
2. Type 6—True Union CPVC Ball Valves:
Ball valves, 2 inches and smaller, for chemical or water service shall be
Schedule 80 full bore design, true union type. Where used in potable water
service, the valve shall be ANSI/NSF-61 certified. Valves shall be
constructed from CPVC Type IV, ASTM D1784 Cell Classification 23447
and rated for a pressure of 150 psi at a temperature of 1050F and 235 psi at
a temperature of 73°F. All 0-rings shall be EPDM or FKM as required for
the compatibility with the chemical service and seats shall be constructed of
PTFE. All valve components shall be replaceable. Valves for sodium
hypochlorite and hydrogen peroxide service shall include vented balls.
Valves shall be manufactured by Spears Manufacturing, Asahi, Plast-O-
Matic, Harrington or equal.
3. Type 7—True Union PVC Ball Valves:
Ball valves, 3 inches and smaller, for chemical or water service shall be
Schedule 80 full bore design, true union type. Where used in potable water
service, the valve shall be ANSI NSF-61 certified. Valves shall be
constructed from PVC Type I, ASTM D1784 Cell Classification 12454 and
rated for a pressure of 150 psi at a temperature of 1050F and 235 psi at a
temperature of 73°F. All 0-rings shall be EPDM or FKM as required for the
compatibility with the chemical service and seats shall be constructed of
PTFE. All valve components shall be replaceable. Valves for sodium
hypochlorite and hydrogen peroxide service shall include vented balls.
Valves shall be manufactured by Spears Manufacturing, Asahi, Plast-O-
Matic, Harrington or equal.
C. Globe Valves, Angle Valves, Hose Valves, Hose Bibbs, and Fire Hydrants:
1. Type 1—Bronze Globe Valves 2 Inches and Smaller:
VALVES AND APPURTENANCES
40 05 23-7
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bdc 11905-faa6-4e6a-b284-
761f74dc511a/W0PlService1d TPEGNYTE PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 23 Valves and Appurtenances.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
Globe valves, 2 inches and smaller, shall be all bronze (ASTM B62 or
ASTM B584, Alloy C83600) with screwed ends, union bonnet, inside screw,
rising stem, and composition or PTFE disc. Valves shall have a pressure
rating of at least 300 psi at a temperature of 150°F. Stem shall be bronze:
ASTM B371 (Alloy C69400), ASTM B99 (Alloy C65100), or ASTM B584
(Alloy C87600). Valves shall be Crane No. 7TF, Walworth Figure 3095,
Stockham B-22T, or equal.
2. Type 2—Bronze Angle Hose Valves (1 1/2 and 2 1/2 inches):
Angle-type hose valves of sizes 1 1/2 and 2 1/2 inches shall be brass or
bronze (ASTM B62 or ASTM B584, Alloy C83600) body with rising or
nonrising stem, composition disc, and bronze or malleable iron handwheel.
Stem shall be bronze, ASTM B62, ASTM B584 (Alloy C83600), or ASTM
B198 (Alloy C87600). Valves shall have a cold-water service pressure rating
of at least 150 psi. Provide cap and chain with valve. Threads on the valve
outlet shall be American National Standard fire hose coupling screw thread.
Valves shall be Powell Figure 151 with Figure 527 nipple adapter, Crane
17TF with hose nipple adapter, or equal.
3. Type 3—Brass or Bronze Angle Hose Valves 1 1/2 and 2 1/2 Inches (UL
Listed):
Angle-type hose valves of sizes 1 1/2 and 2 1/2 inches shall be UL
approved complying with UL 668, cast or forged brass or bronze, with
handwheel. Inlet threads shall be female NPT. Outlet hose threads shall be
male national standard fire hose (MNST). Minimum pressure rating shall be
300 psi. Provide caps with chains for the outlet. Products: Fire Protection
Products, Inc. Series 07, National Fire Equipment, Guardian Fire Equipment
Model 5000, NIBCO T-331-HC, American Fire Hose and Cabinet Series
400, or equal.
4. Type 4—Bronze Hose Bibbs:
Hose bibbs of size 1/2 inch, 3/4 inch, and 1 inch shall be all bronze (ASTM
B62 or ASTM B584, Alloy C83600) with rising or nonrising stem,
composition disc, bronze or malleable iron handwheel, and bronze stem
(ASTM B99, Alloy C65100; ASTM B371, Alloy C69400; or ASTM B584,
Alloy C87600). Packing shall be Teflon or graphite. Valves shall have a
pressure rating of at least 125 psi for cold-water service. Threads on valve
outlet shall be American National Standard fire hose coupling screw thread
(ASME B1.20.7). Provide atmospheric vacuum breaker conforming to ASSE
Standard 1011 and IAPMO code.
D. Check Valves:
1. Type 4—Cast-Iron Swing Check Valves 3 Inches and Larger, Class 125:
Swing check valves, 3 inches and larger, shall be iron body, bronze
mounted complying with AWWA C508 with the following materials of
construction.
VALVES AND APPURTENANCES
40 05 23-8
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bdc 11905-faa6-4e6a-b284-
761f74dc511a/W0PlService1d TPEGNYTE PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 23 Valves and Appurtenances.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
Description Material Specification
Disc or clapper seat ring Bronze or brass ASTM B62 or B584
and valve body seat ring (Alloy C84400 or
C87600)
Body and cap (bonnet) Cast iron ASTM A126, Class B
Disc and hinge or arm Bronze ASTM B62 or ASTM
(valves 4 inches and B584 (Alloy C84400)
smaller)
Disc and hinge or arm Cast iron or ASTM A126, Class B;
(valves larger than 4 bronze ASTM B62.
inches)
Hinge pin Stainless steel Type 303, 304, or
410 stainless
Cover bolts and nuts Stainless steel ASTM A193, Grade
B8M; ASTM A194,
Grade 8M
Internal fasteners and Bronze or Type
accessories 304 or 316
stainless steel
Bronze or brass components in contact with water shall comply with the
following requirements:
Constituent Content
Zinc 7% maximum
Aluminum 2% maximum
Lead 0.25% (potable use)
Copper + Nickel + Silicon 83% minimum
Ends shall be flanged, Class 125, ASME B16.1. Minimum valve working
pressure shall be 150 psi. Provide check valves with outside lever.
The shop drawing submittal shall include a detail showing how the hinge pin
extends through the valve body. Show packing gland, hinge pin gland, cap,
and other pieces utilized.
Valves shall be M&H Style Clow or equal.
2. Type 7—Cast-Iron Ball Check Valves, 3 Through 14 Inches, Class 125:
Valve shall consist of a body with a sinking-type hollow steel ball and
flanged access port. Design shall be such that the fluid flow forces the ball
into a receiving cavity in the valve. When the fluid flow stops, the ball shall
fall out of the cavity into a rubber seat in the body to shut off flow. Valve
shall be suitable for vertical upward or horizontal flow conditions. Body
material shall be cast iron (ASTM A48 or A126) with 15-mil fusion bonded
VALVES AND APPURTENANCES
40 05 23-9
https://us-partner-integrations.eg nyte.com/msoffice/wopi/files/bdc 11905-faa6-4e6a-b284-
761f74dc511a/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 23 Valves and Appurtenances.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
epoxy lining and coating per AWWA C550. Provide nitrile coating on ball.
Provide Type 316 stainless steel fasteners. Flanges shall be Class 125 per
ASME B16.1. Products: Flygt Corporation ball check valve, Flomatic
Corporation Model 408, or equal.
3. Type 8—Slanting Disc Check Valves With Controlled Opening and Closing,
Class 125:
Slanting disc check valves of sizes 6 through 60 inches shall have materials
of construction as described below:
Component Material Specification
Body Cast or ductile iron ASTM A126, Class B or
ASTM A536, Grade 65-45-
12
Seat ring and disc Bronze See paragraph below
ring
Pivot pins Stainless steel ASTM A582, Type 303 or
304
Bushings Stainless steel ASTM A269, Type 304 or
316
Oil reservoirs Stainless steel AISI Type 316
Bronze shall have the following chemical characteristics:
Constituent Content
Zinc 7% maximum
Aluminum 2% maximum
Lead 0.25% (potable use)
Copper + Nickel + Silicon 83% minimum
Ends shall be flanged, ASME B16.1, Class 125. The body shall be of two-
piece construction, bolted at the center to hold the seat at angle of 55
degrees. The area throughout the valve body shall equal the full pipe area.
Provide top-mounted hydraulic dashpot to control valve opening and
closing. Dashpot shall have a control valve to adjust the speed of the
opening and closing cycles. Time spreads shall be adjustable 5 to 30
seconds. Provide oil-filled dashpots to operate the opening and closing
arrangement. The reservoir for the opening cycle shall contain pressurized
air and shall have a 3-inch pressure gauge and pneumatic fill valve.
Provide oil-fitted bottom buffer to control valve closing (adjustable one to
five seconds) over the last 10% of the closing range.
VALVES AND APPURTENANCES
40 05 23-10
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bdc 11905-faa6-4e6a-b284-
761f74dc511a/W0PlService1d TPEGNYTE PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 23 Valves and Appurtenances.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
Valve shall be APCO Series 800, Val-Matic Series 9600 or 9800 or equal.
4. Type 9—Rubber Flapper Swing Check Valves (3 Through 24 Inches):
Valves shall consist of body, flapper, and bolted cover. Operating pressure
shall be at least 175 psi at a temperature of 212°F. Valve seat shall be set
at an angle of 35 to 45 degrees to the centerline of the pipe. Ends shall be
flanged, ASME B16.1, Class 125. Body and cover shall be cast iron (ASTM
A48, Class 30, or ASTM A126, Class B). Flapper shall consist of a steel
disk insert and a steel bar hinge bonded to the metal pieces. Provide O-ring
seal bonded onto the disk. Lining shall have a hardness of 50 to 60
durometer, Shore A. Cover bolts shall be Type 316 stainless steel.
Products: APCO Series 100R, Val-Matic Series 500, or equal.
5. Type 10—Duckbill-Shaped Check Valves, 1 Through 54 Inches, Class 125:
Valve shall consist of a contoured rubber body with a duckbill sleeve-type
exit. The body entrance shall be round, with a connecting Class 125 ASME
B16.1 rubber flange to match the connecting pipe.. Provide synthetic fabric
reinforcement. Provide stainless steel backing rings on the rubber body
flanges. The valve shall open at a differential pressure of 2 inches of water
column and shall close under a no-flow condition. Minimum body pressure
rating shall be 50 psi. Maximum backpressure: 10 psi. Products: Red Valve
Company "Tideflex" Model 35 or equal.
6. Type 11—Silent Check Valve 3 Inches and Larger:
Silent check valves, 3 inches and larger, shall be bronze mounted globe
style. The seat and plug shall be hand replaceable in the field. Provide
resilient seat. Flow area through valve shall be equal to or greater than the
cross sectional area of the equivalent pipe size. Valve plug shall be center
guided with a through integral shaft and spring loaded for silent shutoff
operation. Ends shall be flanged Materials of construction shall be as
follows:
Component Material Specification
Body Cast Iron ASTM A48, Class 30, or
ASTM A126, Class B
Ductile Iron ASTM A536, Grade 60-45-
10
Plug and seal Bronze ASTM B62 or B584 (Alloys
C83600 or C87600)
Spring Stainless steel Type 316 stainless
Valve shall be APCO Series 600 or equal.
7. Type 12 — CPVC Ball Check Valves
VALVES AND APPURTENANCES
40 05 23-11
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bdc 11905-faa6-4e6a-b284-
761f74dc511a/W0PlService1d TPEGNYTE PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 23 Valves and Appurtenances.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
Valve bodies and balls shall be fabricated with chlorinated polyvinyl chloride
(CPVC), or polyvinylidene fluoride (PVDF), as recommended by the
manufacturer for the service indicated. Valves shall include unions with
socket connections. Seals shall have Viton 0-rings and valve design shall
minimize possibility of the balls sticking or chattering. Valves shall be
suitable for a maximum working non-shock pressure of 150 psi at 73
degrees F. Valves shall be manufactured by Spears Manufacturing, Asahi,
Plast-O-Matic, Harrington or equal.
8. Type 13 — PVC Ball Check Valves
Valve bodies and balls shall be fabricated with polyvinyl chloride (PVC), or
polyvinylidene fluoride (PVDF), as recommended by the manufacturer for
the service indicated. Valves shall include unions with socket connections.
Seals shall have Viton O-rings and valve design shall minimize possibility of
the balls sticking or chattering. Valves shall be suitable for a maximum
working non-shock pressure of 150 psi at 73 degrees F. Valves shall be
manufactured by Spears Manufacturing, Asahi, Plast-O-Matic, Harrington or
equal.
E. Solenoid Valves:
1. Design and construct solenoid valves such that they can be used in both
horizontal and vertical piping.
2. Type 1—Metallic Solenoid Valves 1 1/2 Inches and Smaller:
Solenoid valves of sizes 1/4 through 1 1/2 inches for water and air service
shall have forged brass (Alloy C23000) or bronze (ASTM B62) bodies with
Teflon main seats. Internal plunger, core tube, plunger spring, and cage
assembly shall be stainless steel (Types 302, 304, or 305). Valve actuators
shall be 120-volt a-c. Seals shall be Teflon. Valves shall have a maximum
operating pressure and a maximum differential pressure of 125 psi. Valves
shall be ASCO "Redhat" ,Parker Hannifin "Skinner" or equal.
PART 3
PART 3 EXECUTION
3.1 VALVE SHIPMENT AND STORAGE
A. Provide flanged openings with metal closures at least 3/16-inch thick, with
elastomer gaskets and at least four full-diameter bolts. Install closures at the place
of valve manufacture prior to shipping. For studded openings, use all the nuts
needed for the intended service to secure closures. Alternatively, ship flanged
valves 3 inches and smaller in separate sealed cartons or boxes.
B. Provide threaded openings with steel caps or solid-shank steel plugs. Do not use
nonmetallic (such as plastic) plugs or caps. Install caps or plugs at the place of
VALVES AND APPURTENANCES
40 05 23-12
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bdc 11905-faa6-4e6a-b284-
761f74dc511a/W0PlService1d TPEGNYTE PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 23 Valves and Appurtenances.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
valve manufacture prior to shipping. Alternatively, ship valves having threaded
openings or end connections in separate sealed cartons or boxes.
C. Store resilient seated valves in sealed polyethylene plastic enclosures with a
minimum of one package of desiccant inside. Store resilient seated valves in the
open or unseated position. Valves with adjustable packing glands shall have the
packing gland loosened prior to storage. Inspect valves at least once per week,
replace desiccant if required and repair damaged storage enclosures. Do not store
valves with resilient seats near electric motors or other electrical equipment.
D. Inspect valves on receipt for damage in shipment and conformance with quantity
and description on the shipping notice and order. Unload valves carefully to the
ground without dropping. Use forklifts or slings under skids. Do not lift valves with
slings or chain around operating shaft, actuator, or through waterway. Lift valves
with eyebolts or rods through flange holes or chain hooks at ends of valve parts.
E. Protect the valve and actuators from weather and the accumulation of dirt, rocks,
and debris. Do not expose rubber seats to sunlight or ozone for more than 30
days. Also, see the manufacturer's specific storage instructions.
F. Make sure flange faces, joint sealing surfaces, body seats, and disc seats are
clean. Check the bolting attaching the actuator to the valve for loosening in transit
and handling. If loose, tighten firmly. Open and close valves having manual or
power actuators to make sure the valve operates properly and that stops or limit
switches are correctly set so that the valve seats fully. Close valve before
installing.
3.2 FACTORY PRESSURE TESTING
A. Hydrostatically test the valve pressure-containing parts at the factory per the valve
specification or per the referenced standard. If no testing requirement is otherwise
specified or described in the referenced standards, then test with water for 30
minutes minimum at a pressure of 1.5 times the rated pressure but not less than
20 psig. Test shall show zero leakage. If leaks are observed, repair the valve and
retest. If dismantling is necessary to correct valve deficiencies, then provide an
additional operational test and verify that the valve components function.
3.3 INSTALLING VALVES - GENERAL
A. Remove covers over flanged openings and plugs from threaded openings, after
valves have been placed at the point to which the valves will be connected to the
adjacent piping. Do not remove valves from storage cartons or boxes until they are
ready to be installed.
B. Handle valves carefully when positioning, avoiding contact or impact with other
equipment, vault or building walls, or trench walls.
C. Clean valve interiors and adjacent piping of foreign material prior to making up
valve to pipe joint connection. Prepare pipe ends and install valves in accordance
with the pipe manufacturer's instructions for the joint used. Do not deflect pipe-
valve joint. Do not use a valve as a jack to pull pipe into alignment. The installation
VALVES AND APPURTENANCES
40 05 23-13
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bdc 11905-faa6-4e6a-b284-
761f74dc511a/W0PlService1d TPEGNYTE PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 23 Valves and Appurtenances.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
procedure shall not result in bending of the valve/pipe connection with pipe
loading.
D. Make sure valve ends and seats are clean. Check exposed bolting for loosening in
transit and handling and tighten to manufacturer's recommendations. Open and
close the valve to make sure it operates properly and that stops or limit switches
are correctly set so that the vane, ball, gate, needle, diaphragm, disc, plug, or
other seating element seats fully. Close the valve before installing. Check coatings
for damage and repair. Handle valves carefully when positioning, avoiding contact
or impact with other equipment or structures
E. Prior to assembly, coat threaded portions of stainless steel bolts and nuts with
lubricant.
3.4 INSTALLING EXPOSED VALVES
A. Unless otherwise indicated in the drawings, install valves in horizontal runs of pipe
having centerline elevations 4 feet 6 inches or less above the floor with their
operating stems vertical. Install valves in horizontal runs of pipe having centerline
elevations between 4 feet 6 inches and 6 feet 9 inches above the floor with their
operating stems horizontal.
B. Install valves on vertical runs of pipe that are next to walls with their stems
horizontal, away from the wall. Valves on vertical runs of pipe that are not located
next to walls shall be installed with their stems horizontal, oriented to facilitate
valve operation.
3.5 INSTALLING BURIED VALVES
A. Connect the valve, coat the flanges and place and compact the backfill to the
height of the valve stem.
B. Place block pads under the riser pipe to maintain the valve box vertical during
backfilling and repaving and to prevent the riser pipe from contacting the valve
bonnet.
C. Secure the riser pipe with backfill and compact. Install the valve box and pour the
concrete collar. In pavement areas pour the collar to 2 inches below the finished
pavement grade to allow asphalt concrete to be placed over the collar. In non-
paved areas, place the collar to the top of the valve box.
3.6 FIELD COATING BURIED VALVES
A. Coat flanges of buried valves and the flanges of the adjacent piping, and the bolts
and nuts of flanges and mechanical joints, per Section 09 90 00, System No. 07.
3.7 ASSEMBLING JOINTS
A. Bolt holes of flanged valves shall straddle the horizontal and vertical centerlines of
the pipe run to which the valves are attached. Clean flanges by wire brushing
before installing flanged valves. Clean flange bolts and nuts by wire brushing,
lubricate threads with oil and graphite, and tighten nuts uniformly and
VALVES AND APPURTENANCES
40 05 23-14
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bdc 11905-faa6-4e6a-b284-
761f74dc511a/W0PlService1d TPEGNYTE PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 23 Valves and Appurtenances.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
progressively. If flanges leak under pressure testing, loosen or remove the nuts
and bolts, reseat or replace the gasket, reinstall or retighten the bolts and nuts,
and retest the joints. Joints shall be watertight.
B. Clean threaded joints by wire brushing or swabbing. Apply Teflon joint compound
or Teflon tape to pipe threads before installing threaded valves. Joints shall be
watertight.
3.8 INSTALLING EXTENSION STEM GUIDE BRACKETS
A. Install at 6 to 8-foot centers. Provide at least two support brackets for stems longer
than 10 feet, with one support near the bottom of the stem and one near the top.
3.9 MOUNTING GEAR ACTUATORS
A. The valve manufacturer shall select and mount the gear actuator and accessories
on each valve and stroke the valve from fully open to fully closed prior to shipment.
3.10 FIELD INSTALLATION OF GEAR ACTUATOR
A. Provide the actuator manufacturer's recommended lubricating oil in each actuator
before commencing the field testing.
3.11 VALVE FIELD TESTING
A. Test valves for leakage at the same time that the connecting pipelines are
hydrostatically tested. See Section 40 05 00 for pressure testing requirements.
Protect or isolate any parts of valves, actuators, or control and instrumentation
systems whose pressure rating is less than the pressure test. Valves shall show
zero leakage. Repair or replace any leaking valves and retest.
B. Operate manual valves through three full cycles of opening and closing. Valves
shall operate from full open to full close without sticking or binding. Do not backfill
buried valves until after verifying that valves operate from full open to full closed. If
valves stick or bind, or do not operate from full open to full closed, repair or replace
the valve and repeat the tests.
C. Gear actuators shall operate valves from full open to full close through three cycles
without binding or sticking. The pull required to operate handwheel- or chainwheel-
operated valves shall not exceed 40 pounds. The torque required to operate
valves having 2-inch AWWA nuts shall not exceed 150 ft-lbs. If actuators stick or
bind or if pulling forces and torques exceed the values stated previously, repair or
replace the actuators and repeat the tests. Operators shall be fully lubricated in
accordance with the manufacturer's recommendations prior to operating.
END SECTION
VALVES AND APPURTENANCES
40 05 23-15
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bdc 11905-faa6-4e6a-b284-
761f74dc511a/W0PlService1d TPEGNYTE PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 23 Valves and Appurtenances.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
This Page is Intentionally Left Blank
VALVES AND APPURTENANCES
40 05 23-16
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/bdc 11905-faa6-4e6a-b284-
761f74dc511a/W0PlService1d TPEGNYTE PLUS/WOPIUserld_189.ppeng.egnyte.com/40 05 23 Valves and Appurtenances.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 40 20 10
PIPE SUPPORTS
PART 1 GENERAL
1.1 WORK INCLUDED
A. All pipe hangers, brackets, supports and accessories for newly installed piping as
specified and indicated in the Contract Documents.
B. All labor, materials, equipment and incidentals necessary and required for their
completion.
C. Concrete and fabricated steel supports shall be as indicated or specified in other
sections or, in the absence of such requirements, as permitted by the Engineer.
1.2 RELATED WORK
A. Section 03 30 00 — Cast-in-Place Concrete
B. Section 09 90 00 — Paintings and Coatings
C. Section 40 05 00 — Pipe and Fittings
D. Section 40 05 23 —Valves and Appurtenances
1.3 REFERENCES
A. Seismic design requirements in applicable codes and regulations.
1.4 QUALITY ASSURANCE
A. Except as modified or supplemented herein, all pipe supports shall comply with the
applicable provisions of ANSI/MSS SP-58 AND MSS SP-69.
B. In certain locations, pipe supports, anchors, and expansion joints have been
indicated on the drawings, but no attempt has been made to indicate every pipe
support, anchor, and expansion joint. It shall be the Contractor's responsibility to
provide a complete system of pipe supports, to provide expansion joints, and to
anchor all piping, in accordance with the requirements set forth herein. Additional
pipe supports may be required adjacent to expansion joints, couplings, or valves.
1.5 SUBMITTALS
A. Submittals shall be in accordance with Section 01 33 00 — Submittal Procedures.
B. Data shall include a listing of the intended use and general location of each item
submitted.
PIPE SUPPORTS
40 20 10-1
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/c5ebl bd1-36cf-4e34-bf55-
98ff15c607f1/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 20 10 Pipe Supports.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1.6 DELIVERY, STORAGE AND HANDLING
A. All pipe support materials shall be packaged as necessary to ensure delivery in
satisfactory condition.
PART 2 PRODUCTS
2.1 MATERIALS
A. Unless otherwise specified or indicated on the drawings, pipe supports shall be
fabricated of manufacturer's standard materials and provided with manufacturer's
standard finish.
B. Pipe support types and application shall comply with Schedule I in paragraph 3.2.
2.2 PERFORMANCE AND DESIGN REQUIREMENTS
A. Design Criteria
1. Pipe supports shall be manufactured for the size and type of pipe to which
they are applied. Strap hangers will not be acceptable. Threaded rods shall
have sufficient threading to permit the maximum adjustment available in the
support item.
2. All piping shall be rigidly supported and anchored so that there is no
movement or visible sagging between supports.
3. Anchorage shall be as shown on the bid documents.
2.3 DIMENSIONS
A. Unless closer spacing is indicated on the drawings, the maximum spacing for pipe
supports and expansion joints shall be as scheduled in Schedule II at the end of this
section.
2.4 STRUCTURAL DESIGN
A. Design loads for inserts, brackets, clamps, and other support items shall not exceed
the manufacturer's recommended loads.
PART 3 EXECUTION
3.1 INSTALLATION
A. Approved anchors shall be used to fasten supports to concrete or masonry. Unless
otherwise indicated on the drawings or permitted by the Engineer, piping shall be
supported so that the closest distance from pipe wall or insulation covering is at least
1-1/2 inches from the face of walls and at least 3 inches below ceilings.
PIPE SUPPORTS
40 20 10-2
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/c5ebl bd1-36cf-4e34-bf55-
98ff15c607f1/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 20 10 Pipe Supports.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
B. Contact between dissimilar metals, including contact between stainless steel and
carbon steel, shall be prevented. Those portions of pipe supports which contact
dissimilar metals shall be rubber or vinyl coated.
3.2 SCHEDULES
A. SCHEDULE I: Pipe Support Types and Application Schedule:
Description or Location MSS SP-69 Other
(Note 1)
Floor Supports, steel or cast iron:
prefabricated channels --- 12 ga galv., 1-5/8" x 1-5/8", with
suitable brackets and pipe clamps.
B. SCHEDULE II: Spacing Schedule
1. Distance between supports shall not be more than that recommended by the
pipe manufacturer.
2. Distance between supports shall not be more than that shown on the
drawings.
3. Additional supports shall be added as required to prevent visible bowing of
pipe.
4. In addition to the spacing requirements listed above, the distance between
supports shall not be more than listed in the following schedule.
Pipe Support Max Run Without
Max Expansion Joint, Expansion Joint Type of
Type of Pipe Spacing, ft Loop. or Bend, ft Max Spacing, ft Expansion Joint
Ductile Iron, 4" and 15 80 80 Note 1
larger
Steel for all services:
1-1/2 to 4 10 30 100 Note 1
inch
Notes:
PIPE SUPPORTS
40 20 10-3
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/c5ebl bd1-36cf-4e34-bf55-
98ff15c607f1/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 20 10 Pipe Supports.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1. Expansion joint not required in straight run of pipe if overall length does not exceed the
maximum run specified in schedule.
END SECTION
PIPE SUPPORTS
40 20 10-4
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/c5ebl bd1-36cf-4e34-bf55-
98ff15c607f1/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 20 10 Pipe Supports.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 40 50 00
INSTRUMENTATION AND CONTROLS — GENERAL PROVISIONS
PART 1 - GENERAL
1.1 SCOPE OF WORK
A. The Contractor shall procure the services of a single Process Control System
Supplier (PCSS) and a single Pressure Filter System Supplier (PFSS) to furnish and
install all materials, equipment, labor and services, except for those services and
materials specifically noted, required to achieve a fully integrated and operational
system as specified herein and in other Specification Sections listed below.
B. Requirements specified in this Section apply to all equipment specified in the above
sections, unless otherwise specified. The work shall include furnishing, installing and
testing the equipment and materials detailed in the following Sections:
1. 40 50 00 Instrumentation and Controls (I&C) - General Provisions
2. 40 50 01 Testing
3. 4051 10 Computer System Hardware
4. 4051 20 PLC Hardware and Software
5. 4051 30 HMI System Software
6. 4051 50 Control Panels and Panel Mounted Equipment
7. 4051 70 SCADA Radio Communication Equipment
8. 2624 19 Motor Control Centers
C. Auxiliary and accessory devices necessary for system operation or performance,
such as transducers, relays, signal amplifiers, intrinsic safety barriers, signal
isolators, software, and drivers to interface with existing equipment or equipment
provided by others under other Sections of these specifications, shall be included
whether they are shown on the Drawings or not.
D. Substitutions on functions or type of equipment specified shall not be acceptable
unless specifically noted. In order to confirm compatibility between all equipment,
coordinate all interface requirements with mechanical and electrical systems and
furnish any signal isolation devices that might be required.
E. Equipment shall be fabricated, assembled, installed and placed in operating
condition in full conformity with the project Specifications, Drawings, engineering
data, instructions, and recommendations of the equipment manufacturer as
approved by the Engineer.
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-1
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
F. To facilitate the Owner's future operation and maintenance, similar products (e.g.,
differential pressure transmitters, SCADA 1/0 cards) shall be supplied from the same
manufacturer.
G. All equipment and installations shall satisfy applicable Federal, State and local
codes.
H. Use the equipment, instrument, and loop numbering scheme that has been
developed and shown on the Drawings and specifications in the development of the
submittals. Do not deviate from or modify said numbering scheme without the
Engineer's approval.
1. The work of this project includes, but is not necessarily limited to the following:
1.2 RELATED WORK
A. Process Flow Diagrams (PFD) are included in the Drawings.
B. Control System Architecture Block Diagram is included in the Drawings.
C. Specific control system and instrumentation materials and requirements are included
in related Sections of Division 40.
D. Instrumentation and Controls conduit systems are specified in Section 26 05 33.
1.3 SUBMITTALS
A. General submittal requirements include:
1. Refer to Division 01 for general submittal requirements.
2. Other Division 40 Sections may have additional submittal requirements.
3. Shop drawings shall be submitted as detailed herein. Shop drawings shall
demonstrate that the equipment and services to be furnished comply with the
provisions of these specifications and shall provide a complete record of the
equipment as manufactured and delivered.
4. Submittals shall be complete; giving equipment specifications, details of
connections, wiring, ranges, installation requirements, and specific dimensions.
Submittals consisting of only general sales literature shall not be acceptable.
5. Submittals shall be bound in separate three-ring binders, with an index and
sectional dividers, with all drawings reduced to a maximum size of 11-inch by 17-
inch, then folded to 8.5 inch by 11 inch for inclusion within the binder. Maximum
binder size shall be 3 inches.
6. The submittal drawings' title block shall include, as a minimum, the PCSS
registered business name and address, Owner and project name, drawing name,
revision level, and personnel responsible for the content of the drawing.
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-2
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
7. Incomplete or partial submittals not complying with the submittal arrangements
outlined in this Section will be returned without review.
8. Separate submittals shall be made as follows:
a. Project Plan, Deviation List and Schedule Submittal
b. Application Development System Submittal
c. Coordination Meetings Agenda
d. 1/0 List Submittal
e. Field Instrument Submittal
f. Hardware Submittal and Software Packages Submittal
g. Panel Layout Drawings and Wiring Diagram Submittal
h. Testing Plans Submittal
i. Training Plan Submittal
1) Preliminary Training Plan Submittal
2) Final Training Plan Submittal
j. Spares, Expendables, and Test Equipment Submittal
k. Final System Documentation
B. Project Plan, Deviation List, and Schedule Submittal
1. Submit a Project Plan within 21 calendar days from Notice to Proceed date. The
Project Plan shall, as a minimum, contain the following:
a. Overview of the proposed control system in clear text format describing the
PCSS understanding of the project work, preliminary system architecture
drawing, interfaces to other systems, schedule, startup, and coordination.
b. Approach to work in clearly written format describing how the PCSS intends
to execute the work. A discussion of switchover, startup, replacement of
existing equipment with new, and other tasks as required by these
specifications shall be included as applicable.
c. Preliminary HMI software, PLC software, and PLC hardware submittal
information, including version numbers, solely to determine compliance with
the requirements of the Contract Documents prior to development of system
programming. Review and approval of software and hardware systems as
part of this Project Plan stage shall not relieve the PCSS of meeting all the
functional and performance requirements of the system as specified herein.
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-3
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
Substitution of manufacturer or model of these systems after the submittal is
approved is not allowed without Engineer approval.
d. Project personnel and organization including the PCSS project manager,
project engineer, and lead project technicians. Include resumes of each key
individual and specify in writing their commitment to this project.
e. Preliminary coordination meeting agendas as specified herein.
f. Preliminary testing plan
g. Preliminary training plan
h. Sample formats of the shop drawings to be submitted and in conformance
with the requirements of the Specifications. At a minimum include samples of
panel fabrication drawings, loop, 1/0 wiring diagrams, and graphical display
presentations.
2. Exceptions to the Specifications or Drawings shall be clearly defined in a
separate Deviation List. The Deviation List shall consist of a paragraph by
paragraph review of the Specifications indicating acceptance or any proposed
deviations, the reason for exception, the exact nature of the exception and the
proposed substitution so that an evaluation may be made by the Engineer. The
acceptability of any device or methodology submitted as an "or equal' or
"exception" to the specifications shall be at the sole discretion of the Engineer. If
no exceptions are taken to the specifications or drawings the PCSS shall make a
statement as such. If there is no statement by the PCSS, then it is acknowledged
that no exceptions are taken.
3. Project schedule shall be prepared and submitted using Primavera, Microsoft
Project, or equal scheduling software. Schedule shall be prepared in Gantt chart
format clearly showing task linkages for all tasks and identifying critical path
elements. PCSS schedule must be based on the General Contractor schedule
and must meet all field installation, testing, and start-up milestones in that
schedule. The project schedule shall illustrate all major project milestones
including the following:
a. All subsequent project submittals shall be scheduled. Include in the time
allotment; the time required for Contractor submittal preparation, Engineer's
review time, and a minimum of two complete review cycles.
b. Proposed dates for all project coordination meetings.
c. Hardware purchasing, fabrication, and assembly (following approval of
related submittals)
d. Software purchasing and configuration (following approval of related
submittals)
e. Shipment of all instrument and control system equipment
f. Installation of all instrument and control system equipment
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-4
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
g. Testing: Schedule for all testing. Testing schedule shall include submittal of
test procedures a minimum of 30 days prior to commencement of testing.
Schedule shall also include submittal of completed test procedure forms for
review and approval by the Engineer prior to shipment, startup, or
subsequent project work.
h. Schedule for system cutover, startup, and/or going on-line for each major
system. At a minimum include the schedule for each process controller and
HMI server/workstation provided under this Contract.
i. Schedule for all training; including submittal and approval of O&M manuals,
factory training, and site training.
C. Coordination Meetings Agenda:
1. Agendas shall be submitted for the Coordination Meetings as specified herein.
Submit proposed Control System Coordination Meeting Agenda a minimum of
two weeks prior to the scheduled meeting date for review and comment by the
Engineer.
D. Input/Output (1/0) Address List Submittal
1. Submit a complete system Input/Output (1/0) address list for equipment
connected to the control system under this Contract.
2. 1/0 list shall be based on the P&ID's, the Drawings, the design 1/0 list (if included
within these specifications), and requirements outlined in the Specifications.
3. The 1/0 list shall be submitted in both a Microsoft Excel readable electronic file
format on a CD-ROM and an 8-1/2 inch by 11-inch hard copy.
4. The 1/0 list shall reflect all active and spare 1/0 points. Add points to
accommodate spare 1/0.
5. The 1/0 list shall be arranged such that each control panel has a dedicated
worksheet. At a minimum, 1/0 worksheet tables shall include the following
information:
a. TAG NUMBER(S): The identifier assigned to a device that performs a
function in the control system. As part of this information, the loop number of
the tag shall be broken out to allow for sorting by loop.
b. DESCRIPTION: A description of the function of the device (text that includes
signal source, control function, etc.) Include the text "Spare Points" for all I/O
module points that are not connected to equipment.
c. PHYSICAL LOCATION: The Control Panel designation of where the 1/0 point
is wired to.
d. PHYSICAL POINT ADDRESS: Rack, Slot, and Point (or Channel)
assignment for each 1/0 point.
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-5
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
e. LOGICAL POINT ADDRESS: If the PCSS is performing the PLC
programming, 1/0 address of each point. If the PCSS is not performing the
PLC programming, then leave this field blank for use by the PFSS.
f. 1/0 TYPE: use DO - Discrete Output, DI - Discrete Input, AO - Analog Output,
Al -Analog Input, PI - Pulse Input, or PO — Pulse Output.
g. RANGE/STATE: The range in engineering units corresponding to an analog
4-20 mA signal, or, the state at which the value of the discrete points are "1."
h. ENGINEERING UNITS: The engineering units associated with the Analog
1/O.
i. ALARM LIMITS: Include alarm limits based on the control descriptions and
the Drawings.
6. The 1/0 list shall be sorted in order by:
a. Physical location
b. 1/0 Type
c. Loop Number
d. Device Tag
7. After the 1/0 list is approved, do not modify the PLC 1/0 addresses without
approval by the Engineer.
8. Where multiple mechanical components are provided for process redundancy,
their field connections to 1/0 modules shall be arranged such that the failure of a
single 1/0 module will not disable all mechanical components of the redundant
system. This applies to all 1/0 types.
E. Field Instruments Submittal
1. Submit complete documentation of all field instruments using ISA-S20 data sheet
formats. Submit a complete Bill of Materials (BOM) or Index that lists all
instrumentation equipment ordered by the loop numbering system as shown in
the Contract Documents.
2. Submit separate data sheets for each instrument including:
a. Plant Equipment Number and ISA tag number per the drawings
b. Product (item) name used herein and on the Contract Drawings
c. Manufacturer's complete model number
d. Location of the device
e. Input/ output characteristics
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-6
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
f. Range, size, and graduations in engineering units.
g. Physical size with dimensions, enclosure NEMA classification and mounting
details in sufficient detail to determine compliance with the requirements of
the Contract Documents.
h. Materials of construction for enclosure and wetted parts.
i. Instrument or control device sizing calculations where applicable.
j. Certified calibration data for all flow metering devices.
k. Two-wire or four-wire device type as applicable.
3. Submit index and data sheets in electronic format as well as hard copies on 8-1/2
by 11 inches formats. Electronic format shall be in Microsoft Excel or Word.
Submit electronic copy on CD-ROM or DVD disk.
F. Hardware Submittal and Software Packages Submittal
1. For each hardware component indicated below, submit a cover page that lists, at
a minimum, date, specification number, product name, manufacturer, model
number, Location(s), and power required. Preferred format for the cover page is
ISA S20, general data sheet; however, other formats will be acceptable provided
they contain all required information.
2. Catalog cuts for supplied Programmable Logic Controller (PLC), process
controller equipment, remote telemetry units (RTU), including central processing
units, redundancy units, memory, input modules, output modules, modems,
network interface modules, mounting racks, and power supplies. Submit
descriptive literature for each hardware component that fully describes the units
being provided. Any deviation of the hardware systems from the preliminary
hardware submittal included in the Process Plan or Applications Development
System submittal shall be described in detail.
3. Catalog cuts for HMI servers, HMI workstations, historian servers, memory,
printers, mass storage devices, modems, peripherals, power supplies,
networking and all other hardware being provided. Submit descriptive literature
for each hardware component, which fully describes the units being provided.
4. Complete system architecture diagram showing in schematic form, the
interconnections between major hardware components including control centers,
panels, power supplies, consoles, computer and peripheral devices, networking
equipment, processors, 1/0 modules, local operator interfaces, and like
equipment. The system architecture shall be complete and shall depict all
required cables, media type between components, network protocol used at each
network level, details on connection requirements such as cable pin- outs, port
numbers, and rack slot numbers. The intent of this specification requirement is
for the PCSS to develop a diagram that is complete in every aspect to allow
purchase of all required equipment by part number, and to allow a qualified
technician to interconnect all equipment without having to refer to additional
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-7
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
manuals or literature. Minimum sheet size shall be 11"x17" and using a larger
sheet size or more than one sheet is acceptable.
5. Submit details of the controller development software package, the local operator
graphic panel development software package, and the HMI software application
packages to be used for each piece of equipment. Indicate all standard and
optional features provided. Confirm in the submittal that the licenses will be
assigned to the Owner at the time of purchase. Any deviation of the software
platforms from the preliminary software submittal included in the Project Plan
shall be described in detail.
G. Panel Layout Drawings and Wiring Diagrams Submittal
1. Where direct hardwired interfaces exist between the PCSS control panels and
vendor provided control panels furnished under other Divisions, the Contractor
shall provide to the PCSS the approved shop drawings and submittals in order
for the PCSS to provide complete wiring diagrams showing all wiring connections
in the 1/0 system. This includes but is not limited to terminal block numbering,
relay contact information, instruments, equipment, and control panel names.
These drawings will be included in the Final Documentation submittal. Leaving
this information blank on the Final Documentation drawings is not acceptable.
2. Panel Layout Drawings: Drawings shall be furnished for all panels, consoles, and
equipment enclosures specified. Panel assembly and elevation drawings shall be
drawn to scale and detail all equipment in or on the panel. Panel drawings shall
be 11"x17" minimum in size. As a minimum, the panel drawings shall include the
following:
a. Interior and exterior panel elevation drawings to scale.
b. Nameplate schedule.
c. Conduit access locations.
d. Panel construction details.
e. Cabinet assembly and layout drawings to scale. The assembly drawing shall
include a bill of material on the drawing with each panel component clearly
defined. The bill of material shall be cross-referenced to the assembly
drawing so that a non-technical person can readily identify any component of
the assembly by manufacturer and model number.
f. Fabrication and painting specifications including color (or color samples).
g. Submit construction details, NEMA ratings, intrinsically safe barrier
information, gas sealing recommendations, purging system details, etc. for
panels located in hazardous locations or interfacing to equipment located in
hazardous areas.
h. Heating and cooling calculations for each panel supplied indicating
conformance with cooling requirements of the supplied equipment and
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-8
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
environmental conditions. Calculations shall include the recommended type
of equipment required for both heating and cooling.
i. Submit evidence that all control panels shall be constructed in conformance
with UL 508 and bear the UL seal confirming the construction. Specify if UL
compliance and seal application shall be accomplished at the fabrication
location or by field inspection by UL inspectors. All costs associated with
obtaining the UL seal and any inspections shall be borne by the Contractor
and included in the Project Bid Price.
3. Panel Wiring Diagrams: Panel wiring diagrams depicting wiring within and on the
panel as well as connections to external devices. If ISA Loop Wiring Diagrams
are specified below, equipment external to the control panel and related external
connections do not need to be shown on the Panel Wiring Diagrams. Panel
wiring diagrams shall include power and signal connections, UPS and normal
power sources, all panel ancillary equipment, protective devices, wiring and wire
numbers, and terminal blocks and numbering. Field device wiring shall include
the device ISA-tag and a unique numeric identifier. The diagrams shall identify all
device terminal points that the system connects to, including terminal points
where 1/0 wiring lands on equipment not supplied by the PCSS. Wiring labeling
used on the drawings shall match that shown on the Contract Documents or as
developed by the PCSS and approved by the Engineer. 1/0 wiring shall be
numbered with rack number, slot number, and point number. Two-wire and four-
wire equipment shall be clearly identified and power sources noted. Submit final
wire numbering scheme. Panel drawings shall be 11" x17" minimum in size.
4. ISA Loop Wiring Diagrams: Detailed ISA loop wiring diagrams showing
requirements for each loop which is shown on the contract drawings. The Loop
Drawings shall be prepared in accordance with ISA Standard S5.4 latest edition
with the layout following Figures 5 and 6 (shown in the S5.4 Standard), titled
Minimum Required Items Plus Optional items". Loop drawings shall be 11"x17"
minimum in size. The information required on the Loop Drawings in order to
satisfy the "minimum" and 'optional" requirements is as follows:
a. Minimum Required Items — The following information shall be provided on
Loop Drawings in order to meet this requirement:
1) Identification of the loop and loop components shown on the P&IDs.
Other principal components of the loop to be shown and identified under
ISA-5.1, "Instrumentation Symbols and Identification".
2) Word description of loop functions within the title. If not adequate, use a
supplemental note. Identify any special features or functions of shutdown
and safety circuits.
3) Indication of the interrelation to other instrumentation loops, including
overrides, interlocks, cascaded set points, shutdowns and safety circuits.
4) All point-to-point interconnections with identifying numbers or colors of
electrical cables, conductors, pneumatic multitubes, and individual
pneumatic and hydraulic tubing. This identification of interconnections
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-9
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
includes junction boxes, terminals, bulkheads, ports, and grounding
connections.
5) General location of devices such as field, panel, auxiliary equipment,
rack, termination cabinet, cable spreading room, 1/0 cabinet, etc.
6) Energy sources of devices, such as electrical power, air supply, and
hydraulic fluid supply. Identify voltage, pressure, and other applicable
requirements. For electrical sources, identify circuit or disconnect
numbers.
7) Process lines and equipment sufficient to describe the process side of the
loop and provide clarity of control action. Include what is being measured
and what is being controlled.
8) Actions or fail-safe positions (electronic, pneumatic, or both) of control
devices such as controllers, switches, control valves, solenoid valves, and
transmitters (if reverse- acting). These are to be identified in accordance
with ISA-5.1, "Instrumentation Symbols and Identification".
b. Additional Required Items — The following information shall be provided on
Loop Drawings (in a tabular format as shown in Figures 5 and 6 of ISA 5.4) in
order to meet this requirement:
1) Process equipment, lines, and their identification numbers, source,
designation, or flow direction.
2) Reference to supplementary records and drawings, such as installation
details, P&IDs, location drawings, wiring diagrams or drawings, and
instrument specifications.
3) Specific location of each device, such as elevation, area, panel
subdivision, rack or cabinet number and location, 1/0 location.
4) Cross reference between loops that share a common discrete
component, such as multipen recorders, dual indicators, etc.
5) References to equipment descriptions, manufacturers, model numbers,
hardware types, specifications or data sheets, purchase order numbers.
6) Signal ranges and calibration information, including setpoint values for
switches, and alarm and shutdown devices.
7) Software reference numbers, such as 1/0 addresses, control block types
and names, network interfaces, point names.
8) Engraving or legend information that helps identify the instrument or
accessory. Per ISA-5.4-1991 11.
9) Accessories, tagged or otherwise identified, such as regulators, filters,
purge meters, manifold valves, root valves.
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-10
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
10)References to manufacturer's documentation such as schematics,
connection details, operating instructions.
11)Color code identification for conductors or tubes that use numbers for
differentiation.
H. Testing Plan Submittals
1. Test Procedure Submittals: Submit the procedures proposed to be followed for
each test. Procedures shall include test descriptions, forms, and checklists to be
used to control and document the required tests. Include sign-off forms for each
testing phase or loop with sign-off areas for the PCSS, Engineer, and Owner.
Refer to Section 40 50 01 for specific testing requirements, and submit separate
procedures for each specified test phase.
2. Test Documentation: Upon completion of each required test, document the test
by submitting a copy of the signed off test procedures. Testing shall not be
considered complete until the signed-off test procedures have been submitted
and favorably reviewed. Submittal of other test documentation, including
"highlighted" wiring diagrams with field technician notes, are not acceptable
substitutes for the formal test documentation.
3. Each loop shall have a Loop Status signoff form to organize and track its
inspection, adjustment and calibration. These forms shall include the following
information and check-off items:
a. Project Name.
b. Loop Number.
c. Detailed test procedure indicating exactly how the loop will be tested
including all required test equipment, necessary terminal block numbers, and
simulation techniques required.
d. Tag Number for each component.
e. Check-offs/signoffs for each component.
1) Tag/identification
2) Installation
3) Termination -wiring
4) Termination - tubing
5) Calibration/adjustment
f. Check-offs/signoffs for the loop.
1) Panel interface terminations
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-11
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2) 1/0 interface terminations
3) 1/0 signal operation
4) Inputs/outputs operational: received/sent, processed, adjusted
5) Total loop operation
6) Space for comments.
7) Sign off and date fields for the Contractor, the Engineer, and the PCSS.
4. Each active analog subsystem element shall have a Component Calibration
form. These forms shall have the following information including space for data
entry:
a. Project Name.
b. Loop Number.
c. ISA Tag Number and 1/0 Module Address.
d. Manufacturer.
e. Model Number/Serial Number.
f. Summary of Functional Requirements. For example:
1) For Indicators: Scale ranges
2) For Transmitters/Converters: Scale and chart ranges
3) For Computing Elements: Function
4) For Controllers: Action (direct/reverse) control modes (PID)
5) For Switching Elements: Unit range, differential (FIXED/ADJUSTABLE),
reset (AUTO/MANUAL)
6) For 1/0 Modules: Input or output
g. Calibrations; for example:
1) For Analog Devices: Required and actual inputs and outputs at 0, 50 and
100 percent of span.
2) For Discrete Devices: Required and actual trip points and reset points.
3) For Controllers: Mode settings (PID).
4) For 1/0 Modules: Required and actual inputs or outputs for 0, 50 and 100
percent of span.
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-12
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
h. Space for comments.
i. Sign off and date fields for the Contractor, the Engineer, and the PCSS.
I. Spares, Expendables, and Test Equipment Lists Submittal
1. This submittal shall include for each Subsystem:
a. A list of, and descriptive literature for, spares, expendables, and test
equipment as specified in Division 40.
b. A list of, and descriptive literature for, additional spares, expendables, and
test equipment recommended by the manufacturer.
c. Unit and total costs for the additional spare items specified or recommended
for each subsystem.
J. Final System Documentation
1. The Final System Documentation shall consist of operations and maintenance
manuals as specified herein. The manuals shall be bound in three-ring binders,
maximum size of three inches, with Drawings reduced to 11 inch by 17 inch, then
folded to 8.5 inch by 11 inch for inclusion. Each section shall have a uniquely
numbered tab divider, and each component within each section shall have a
separate binder tab divider.
2. The operations and maintenance manuals shall, at a minimum, contain the
following information:
a. Table of Contents
1) A Table of Contents shall be provided for the entire manual with the
specific contents of each volume clearly listed. The complete Table of
Contents shall appear in each volume.
b. Instrument and Equipment Lists
1) The following lists shall be developed in Excel and provided not only as a
hardcopy in O&M but also electronically on a CD.
2) An instrument list for all devices supplied including tag number,
description, specification section and paragraph number, manufacturer,
model number, serial number, range, span, location, manufacturer phone
number, local supplier name, local supplier phone number, completion
year replacement cost, and any other pertinent data.
3) An equipment list for all non-instrument devices supplied listing
description, specification section and paragraph number, manufacturer,
model number, serial number, location, manufacturer phone number,
local supplier name, local supplier phone number, completion year
replacement cost, and any other pertinent data.
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-13
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
c. Data Sheets with Vendor Operations and Maintenance Information
1) ISA S20 data sheets shall be provided for all field instruments.
2) Cover page for each device, piece of equipment, and OEM software that
lists, at a minimum, date, specification number, product name,
manufacturer, model number, Location(s), and power required. Preferred
format for the cover page is ISA S20, general data sheet; however, other
formats will be acceptable provided they contain all required information.
3) Final vendor O&M documentation for each device, piece of equipment, or
OEM software shall be either new documentation written specifically for
this project, or modified standard vendor documentation. All standard
vendor documentation furnished shall have all portions that apply clearly
indicated with arrows or circles. All portions that do not apply shall be
neatly lined out or crossed out. Groups of pages that do not apply at all to
the specific model supplied shall be removed.
4) For any component requiring dip switch settings or custom software
configuration, that information shall be included along with the
corresponding data sheets and O&M information.
d. As-Built Drawings
1) Complete as-built drawings, including all drawings and diagram specified
in this section under the "Submittals" section. These drawings shall
include all termination points on all equipment the system in connected to,
including terminal points of equipment not supplied by the PCSS.
2) As built documentation shall include information from submittals, as
described in this Specification, updated to reflect the as-built system. Any
errors in or modifications to the system resulting from the Factory and/or
Functional Acceptance Tests shall be incorporated in this documentation.
e. Original Licensed Software
1) Submit original software diskettes or CD-ROMs of all software provided
under this Contract. Submit original paper based and electronic
documentation for all software provided. Submit license agreement
information including serial numbers, license agreements, User
Registration Numbers and related information. All software provided
under this Contract shall be licensed to the Owner at the time of
purchase. Provide media in software sleeves within O&M manual.
f. Electronic O&M Information
1) In addition to the hard copy of O&M data, provide an electronic version of
all equipment manuals CDROM or DVD. Electronic documents shall be
supplied in Adobe Acrobat format.
2) Provide electronic files for all custom-developed manuals. Text shall be
supplied in both Microsoft Office format and Adobe Acrobat format.
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-14
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3) Provide electronic files for all drawings produced. Drawings shall be in
AutoCAD ".dwg" format and in Adobe Acrobat format. Drawings shall be
provided using the AutoCAD eTransmit feature to bind external
references, pen/line styles, and fonts into individual zip files along with the
drawing file.
4) Each computer system hardware device shall be backed up onto CDROM
or DVD after Substantial Completion and shall be turned over to the
Owner.
5) If specified in the training section, provide digital copies of all training
videos. Videos shall be in a format that is readable by standard DVD
players and by standard PC DVD drives. Format and shall be a minimum
of 800 by 600 pixels and shall include sound.
3. The cover and edge of each volume shall contain the following information:
a. Project Name (refer to Contract Documents)
b. Contract Number (refer to Contract Documents)
c. Instrumentation and Control System Hardware[or Applications Engineering]
Operations and Maintenance Manual
d. Specification Sections [List appropriate section]
e. Subcontractor Name
f. Date
g. Volume X of Y [Where X is the volume number and Y is the number of
volumes]
1.4 REFERENCE STANDARDS
A. Publications are referred to in the text by basic designation only. Where a date is
given for reference standards, that edition shall be used. Where no date is given for
reference standards, the latest edition in effect at the time of bid opening shall apply.
B. International Society of Automation (formerly the Instrumentation, Systems and
Automation Society) (ISA)
1. ISA S5.2 Binary Logic Diagrams for Process Operations
2. ISA S5.3 Graphic Symbols for Distributed Control/Shared Display
Instrumentation Logic and Computer Systems.
3. ISA S5.4, Instrument Loop Diagrams
4. ISA S20, Specification Forms for Process Measurement and Control Instruments,
Primary Elements and Control Valves.
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-15
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
5. ISA RP60.3, Human Engineering for Control Centers
6. ISA RP60.6, Nameplates, Labels, and Tags for Control Centers
C. National Electrical Manufacturers Association (NEMA)
D. National Fire Protection Agency (NFPA)
1. NFPA 70, National Electrical Code (NEC)
E. Underwriters Laboratories, Inc. (UL)
1. UL 508— Industrial Control Equipment
F. American Society for Testing and Materials (ASTM)
1. ASTM A269 - Standard Specification for Seamless and Welded Austenitic
Stainless Steel Tubing for General Service.
1.5 QUALITY ASSURANCE
A. The Process Control System Supplier (PCSS) shall be a "systems integrator"
regularly engaged in the design and the installation of instrumentation systems and
their associated subsystems as they are applied to the municipal water and
wastewater industry. For the purposes of this Specification Section, a "systems
integrator" shall be interpreted to mean an organization that complies with all of the
following criteria:
B. The PCSS shall maintain a permanent, fully staffed and equipped service facility
within 250 miles of the project site with full time employees capable of designing,
fabricating, installing, calibrating, and testing the systems specified herein. At a
minimum, the PCSS shall be capable of responding to on-site problems within 12
hours of notice. Provide an on-site response within 4 hours of notification starting at
two months before scheduled startup to two months after startup completion.
C. PCSS shall hold a valid UL-508 certification for their panel fabrication facility.
1.6 DELIVERY, STORAGE, AND HANDLING
A. Delivery, storage, and handling shall be in accordance with Division 01.
B. Shipping Precautions
1. After completion of shop assembly, factory test and approval of all equipment,
cabinets, panels and consoles shall be packed in protective crates and enclosed
in heavy duty (5 mil) polyethylene envelopes or secured sheeting to provide
protection from damage, dust and moisture. Dehumidifiers shall be placed inside
the polyethylene coverings. The equipment shall then be skid-mounted for final
transport. Lifting rings shall be provided for moving without removing protective
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-16
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
covering. Boxed weights shall be shown on shipping tags together with
instructions for unloading, transporting, storing and handling at the job site.
2. Manufacturer's special instructions for field handling, storage and installation
required for protection, shall be securely attached to the packaging for each
piece of equipment prior to shipment. The instructions shall be stored in
resealable plastic bags or other means of protection.
3. None of the HMI control and monitoring equipment shall be shipped to the site
until the control room areas comply with specified ambient temperature and
humidity. Have qualified personnel accept the equipment on delivery and
supervise unloading within the control room areas.
4. If any apparatus has been damaged, such damage shall be repaired at no
additional cost to the owner.
1.7 NOMENCLATURE AND IDENTIFICATION
A. Field Instrument Tags
1. A permanent stainless steel or other non-corrosive material tag firmly attached
and permanently and indelibly marked with the instrument tag number, as
indicated in the Drawings, shall be provided on each piece of equipment supplied
under this Section. Equipment shall be tagged before shipping to the site.
2. Provide 1/8-in by 3/8-in, Type 316 stainless steel button head machine screws.
3. All supplied field instrument transmitters and field instrument transmitter
elements shall have a stainless steel identification tag attached to each
transmitter and element prior to shipment. Tag shall be attached via stainless
steel chain or stainless steel wire (24 gauge inches. Tag shall include the ISA
alphanumeric instrument number as indicated in the P&ID, loop, and detail
drawings. The alphanumeric instrument number shall be stamped into the tag
and shall have a minimum of 3/16-in high alphanumeric characters.
B. Panel Nameplates
1. See Section 40 51 50.
1.8 WARRANTY
A. Provide warranty per Section 00 65 36, Warranties and Bonds, and as specified
herein.
1.9 PROJECT/SITE REQUIREMENTS
A. Environmental Requirements. Refer to Section 26 05 00 and the Electrical Drawings
for specific environmental and hazardous area classifications.
B. Elevation: Equipment shall be designed to operate at the project ground elevation.
C. Temperature:
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-17
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1. Outdoor areas' equipment shall operate [between - 30 to 50 C degrees ambient].
2. Equipment located in indoor locations shall operate between [10 to 35 C]
degrees ambient minimum.
3. Storage temperatures shall range from [0 to 50 C] degrees ambient minimum.
4. Additional cooling or heating shall be furnished if required by the equipment as
specified herein.
D. Relative Humidity: Air conditioned area equipment shall operate between 20 to 95
percent relative, non-condensing humidity. All other equipment shall operate
between 0 to 100 percent relative, condensing humidity.
PART 2 - PRODUCTS
2.1 PRODUCTS GENERAL
A. All instrumentation and electronic equipment shall be of the manufacturer's latest
design, utilizing printed circuitry and epoxy or equal coating to prevent contamination
by dust, moisture and fungus. The field mounted equipment and system components
shall be designed for installation in dusty, humid and slightly corrosive service
conditions.
B. All instruments shall be provided with mounting hardware and floor stands, wall
brackets, or instrument racks unless otherwise noted. Fasteners for securing control
panels and enclosures to walls and floors shall be either hot-dipped galvanized after
fabrication or stainless steel. Provide stainless steel fasteners only in corrosive areas
rated NEMA 4X on the Drawings or as defined under Division 26. Provide and size
anchors in accordance with Divisions 01 and 05 as required per the seismic
calculations. Provide minimum size anchor of 3/8-inch.
C. All indicators shall be linear in process units, unless otherwise noted. All transmitters
shall be provided with indicators in process units, accurate to two percent or better.
D. All equipment, cabinets and devices furnished shall be heavy-duty type, designed for
continuous industrial service. The system shall contain similar products of a single
manufacturer, and shall consist of equipment models, which are currently in
production. All equipment provided shall be of modular construction and shall be
capable of field expansion.
E. All electronic/digital equipment shall be provided with radio frequency interference
protection.
F. Electrical
1. Equipment shall operate on a 60 Hertz alternating current power source at a
nominal 120 volts, plus or minus 10 percent, except where specifically noted.
Regulators and power supplies required for compliance with the above shall be
provided between power supply and interconnected instrument loop. Where
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-18
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
equipment requires voltage regulation, constant voltage transformers shall be
supplied.
2. With the exception for field device network connected devices, all electronic
instrumentation shall utilize linear transmission signals of isolated 4 to 20 mA DC
(milliampere direct current) capable of driving a load up to 750 ohms, unless
specified otherwise. However, signals between instruments within the same
panel or cabinet may be 1-5 VDC (volts direct current).
3. Outputs of equipment that are not of the standard signals as outlined, shall have
the output immediately raised and/or converted to compatible standard signals
for remote transmission. No zero based signals will be allowed.
4. All switches shall have double-pole double-throw contacts rated at a minimum of
600 VA, unless noted otherwise.
5. Switches and/or signals indicating an alarm, failure or upset condition shall be
wired fail- safe to the SCADA system. A fail-safe condition is an open circuit
when in an alarm state.
6. Materials and equipment shall be UL approved. Where components are not
available with UL approval, integrate the device with ground fault protective
devices, isolation transformers, fuses, or other protective equipment necessary to
achieve compliance with UL 508 requirements.
7. All equipment furnished shall be designed and constructed so that in the event of
power interruption, the systems specified herein shall go through an orderly
shutdown with no loss of memory, and shall resume normal operation without
manual resetting when power is restored, unless otherwise noted.
8. All transmitter output signals shall include signal and power source isolation.
2.2 ELECTRICAL SURGE PROTECTION
A. General - Surge protection shall be provided to protect the electronic instrumentation
system from induced surges propagating along the signal and power supply lines
from lightning, utility, or the plant electrical system. The protection systems shall be
such that the protective level shall not interfere with normal operation, but shall be
lower than the instrument surge withstand level. Protection shall be maintenance free
and self-restoring. Devices shall have a response time of less than 50 nanoseconds
and be capable of handling a discharge surge current (at an 8x20ps impulse
waveform) of at least 8 kA. Ground wires for all instrumentation device surge
protectors shall be connected to a low resistance ground in accordance with Section
26 05 00.
B. Provide protection of all analog signal (4-20 mA) circuits where any part of the circuit
is outside of the building envelope. Circuits shall be protected at both the transmitter
and the control system end of the circuit. Protection devices located near the
transmitter shall be mounted in a separate enclosure, unless conduit mounted, and
shall be Phoenix Contact PT Series, MTL Surge Technologies (Telematic) TP48,
Citel TSP-10 series, or equal. Substitution of a single device to protect both 120 VAC
and 4-20 mA wires to an instrument is acceptable. Protection devices in control
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-19
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
panels shall be MTL Surge Technologies (Telematic) SD Series, Phoenix Contact PT
Series, Citel BP1-24, or equal.
C. Provide protection of all 120 VAC power feeds into control panels, instruments, and
control room equipment. Surge arresters shall be Transtector ACP-10OBW Series,
Phoenix Contact "Mains-PlugTrab", MCG Surge Protection 400 Series, or equal.
D. Non-Fiber Based Data Highway or Communications Circuits — Provide protection on
all communication and data highway circuits that leave a building or are routed
external to a building. Circuit protection shall be provided at both ends of the line.
Surge protection devices shall be Phoenix Contact PlugTrab Series, Transtector FSP
Series, MTL Surge Technologies (Telematic) NP Series, or equal.
E. Inductive Loads — At a minimum, provide coil surge suppression devices, such as
varistors or interposing relays, on all process controller outputs or switches rated 120
VA or less that drive solenoid, coil, or motor loads.
F. Telephone Circuits - At a minimum, provide Telephone Company approved line
protection units for all telephone lines used for telemetry or SCADA system use
under this Contract.
2.3 TUBING AND FITTINGS
A. All instrument air header takeoffs and branch connections less than 2-in shall be 316
stainless steel.
B. All instrument shut-off valves and associated fittings shall be supplied in accordance
with the piping specifications and all instrument installation details. The materials for
fittings and valves shall be compatible with process fluids. Where metallic fittings and
valves are compatible, wetted materials shall be Type 316 stainless steel.
C. The materials for instrument tubing shall be compatible with process fluids. Where
metallic tubing is compatible, tubing shall be fully annealed ASTM A269 Seamless
316 grade free of OD scratches having the following dimensional characteristics as
required to fit the specific installation:
1. 1/4-in to 1/2-in O.D. by 0.035 wall thickness
2. 5/8-in to 1-in O.D. by 0.049 wall thickness
3. 1-in O.D. by 0.065 wall thickness
4. 1-1/4-in O.D. by 0.065 wall thickness
5. 1-1/2-in O.D. by 0.083 wall thickness
6. 2-in O.D. by 0.095 wall thickness
D. All process connections to instruments shall be annealed 1/2-inches O.D. stainless
steel tubing, Type 316.
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-20
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
E. All tube tracks shall be supported by stainless steel and installed as per
manufacturer's installation instructions.
2.4 SPARE PARTS
A. Spare parts of the type and quantity as recommended by the manufacturer shall be
furnished for all devices furnished under these sections.
B. All spare parts shall be wrapped in bubble wrap, sealed in a polyethylene bag
complete with dehumidifier, then packed in cartons and labeled with indelible
markings. Complete ordering information including manufacturer's part number, part
ordering information including manufacturer, part number, part name, and equipment
name and number(s) for which the part is to be used shall be supplied with the
required spare parts. The spare parts shall be delivered and stored in a location
directed by the Engineer.
C. As a minimum, furnish the following spare parts for control panels:
1. Timers - Five of each type installed
2. Relays - Five of each type installed
3. Fuses and circuit breakers - 10% (minimum of 10 fuses and 2 circuit breakers) of
each type and size installed
4. Light bulbs - 10% (minimum of 10) of each type installed
5. Power supplies - one of each type installed.
6. Manufacturer's cables - one of each type installed.
7. Selector switches/pushbuttons - Two of each type installed including 5 contact
blocks.
8. Surge protection devices - One of each type installed.
9. Provide one quart of touch-up paint, for each type and color used for all RTU
cabinets, panels, and consoles supplied.
D. The following field Instrument related Spare Parts shall be furnished:
1. Miscellaneous: One year supply of items recommended by the manufacturer of
the equipment including all reagents, dissolved oxygen probes, batteries, and
calibration standards as needed to operate and maintain the furnished
equipment.
E. PLC components
1. One spare CPU of each type supplied for each plant
2. Two spare 1/0 modules of each type supplied for each plant
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-21
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
3. One spare specialty interface module of each type supplied for each plant
4. One spare power supply of each type supplied for each plant
PART 3 - EXECUTION
3.1 GENERAL INSTALLATION
A. Instrumentation and accessory equipment shall be installed in accordance with the
manufacturer's instructions. The locations of equipment, transmitters, alarms and
similar devices indicated are approximate only. Exact locations of all devices shall be
as approved by the Engineer during construction. Obtain in the field, all information
relevant to the placing of process control equipment and in case of any interference
with other work, proceed as directed by the Contractor and furnish all labor and
materials necessary to complete the work in an approved manner at no additional
cost to the Owner.
B. All equipment used in areas designated as hazardous shall be designed for the
Class, Group and Division as required for the locations as shown on the Drawings
and specified in Division 26. All work shall be in strict accordance with codes and
local rulings.
C. Unless specifically indicated, direct reading or electrical transmitting instrumentation
shall not be mounted on process piping. Instrumentation shall be mounted on
instrument racks or stands. All instrumentation connections shall be provided with
shutoff and drain valves. For differential pressure transmitters, 5-valve manifolds for
calibration, testing and blow down service shall also be provided. For chemical or
corrosive fluids, diaphragm seals with flushing connections shall be provided.
D. All piping and tubing to and from field instrumentation shall be provided with
necessary unions, calibrations and test tees, couplings, adaptors, and shut-off
valves. Process tubing shall be installed to slope from the instrument toward process
for gas measurement service and from the process toward the instrument for liquid
measurement service. Provide drain/vent valves or fittings at any process tubing
points where the required slopes cannot be maintained. Process tubing shall be
installed rigidly with supports to prevent significant vibrations.
E. Brackets and hangers required for mounting of equipment shall be provided. They
shall be installed as shown and not interfere with any other equipment.
F. The shield on each process instrumentation cable shall be continuous from source to
destination and be grounded at only one ground point for each shield.
G. Investigate each space in the building through which equipment must pass to reach
its final location. If necessary, ship material in sections sized to permit passing
through restricted areas in the building. Provide on-site service to oversee the
installation, the placing and location of system components, their connections to the
process equipment panels, cabinets and devices, subject to the Engineer's approval.
Certify that field wiring associated with his/her equipment is installed in accordance
with best industry practice. Schedule and coordinate work under this section with that
of the electrical work specified under applicable Sections of Division 26.
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-22
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
H. Installation of fiber optic cable within control panel and console assemblies. Refer to
cable manufacturer's specifications for bend radius. Use cable breakout assembly as
recommended by the cable manufacturer. Provide wire basket, strain relief as
required to meet manufacturer's strain requirements.
I. Provide local electrical shutoffs and disconnects for all 4-wire field instruments
requiring 120 VAC power. Electrical disconnects shall be suitably rated disconnect
switches or manual motor starters as specified under Division 26.
J. Provide sunshades for equipment mounted outdoors in direct sunlight. Sunshades
shall include standoffs to allow air circulation around the cabinet. Orient equipment
outdoors to face to the North or as required to minimize the impact of glare on LED,
LCD, or other digital readouts.
K. Loop Tuning - All electronic control stations incorporating PID controllers shall be
tuned following field installation and calibration of instrumentation and control system
components, but prior to commencement of the specified field tests. Field testing will
be immediately `failed' if loop tuning for the entire installed system is not complete.
1. Optimal loop tuning shall be achieved either by auto-tuning software or manually
by trial and error, Ziegler-Nichols step-response method, or other documented
process tuning method. Assigning common PID factors for identical loops
following field tuning of a single typical loop is acceptable. However, tuning
documentation shall be submitted for each loop individually as specified in Part 1
of these Specifications.
2. Determine and configure optimal tuning parameters to assure stable, steady
state operation of final control elements running under the control of field
mounted, dedicated PID controllers or software based PID controllers residing as
part of the programmable logic controller system. Each control loop that includes
anti-reset windup features shall be adjusted to provide optimum response
following startup from an integral action saturation condition.
3. Tune all PID control loops to eliminate excessive oscillating final control
elements. Loop parameters shall be adjusted to achieve 1/4 amplitude damping
or better. In addition, loop steady state shall be achieved at least as fast as the
loop response time associated with critical damping.
4. Loop performance and stability shall be verified in the field following tuning by
step changes to setpoint. Submit loop tuning methodology and verification as
part of the final system documentation as specified in Part 1.
5. For cascade loops, tune both sets of controllers so that the cascade loop
achieves the loop tuning characteristics specified herein.
3.2 TESTING
A. Refer to Section 40 50 01.
END OF SECTION
INSTRUMENTATION AND CONTROLS-GENERAL PROVISIONS
40 50 00-23
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 40 90 00
INSTRUMENTATION
PART 1 GENERAL
1.1 WORK INCLUDED
A. Supply and install sensing elements, transmitters, brackets, conduit, wiring and all
related items necessary to connect and integrate with the water distribution system.
1.2 RELATED WORK
A. Division 26— Electrical
B. Section 40 50 00 — Instrumentation and Controls-General Provisions
1.3 SUPPLIER'S QUALIFICATIONS
A. Each system shall be designed, coordinated, and supplied by a qualified supplier
who is regularly engaged in the business of designing and providing instrument and
control systems for municipal wastewater projects. The Contractor shall submit
proof of the following qualifications of his intended instrumentation supplier:
1. The names of manufacturers whose products are normally supplied.
2. That he has and will maintain competent service personnel to service the
equipment furnished.
3. That he has successfully provided similar work for at least 5 years.
4. The names of at least three references who are users of similar equipment
designed, fabricated, and furnished by the supplier. References shall include
a general description of the project scope.
1.4 COORDINATION
A. Instrument and control systems supplied under this section shall be designed and
coordinated for proper operation with related equipment and materials furnished by
other suppliers under other sections of these specifications and where applicable,
to related existing equipment. All instruments and control devices shall be applied
in full conformity with the drawings, specifications, engineering data, instructions,
and recommendations of the instrument or device manufacturer, and the related
equipment manufacturer.
B. Power and Instrument Signals. Unless noted otherwise, electrical power supply to
the instrumentation equipment will be unregulated 120 volts ac at the locations
indicated in the electrical sections. Unless otherwise noted or specified, all
transmitted electronic analog instrument signals shall be 4-20 mA dc.
INSTRUMENTATION
40 90 00-1
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/ce00cb0e-2d 14-4c2c-ae8e-
086fb9924bbf/WOPIServiceld_TP_EGNYTE_PLUS/wOPIUserld_189.ppeng.egnyte.com/40 90 00 Instrumentation.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1.5 SUBMITTALS
A. Submittals shall be in accordance with Section 01 33 00 — Submittal Procedures.
PART 2 PRODUCTS
2.1 ULTRASONIC FLOW METER
A. Each ultrasonic level transmitter shall be an all-solid-state electronic unit consisting
of a sensor assembly, a signal converter/transmitter, and an interconnecting cable.
The sensor shall be encapsulated in a chemical and corrosion resistant material
such as Kynar or CPVC, and shall be suitable for operation over a temperature
range of-20 F to +150 F with a relative humidity of 10 to 100 percent. The ultrasonic
level transmitter shall have automatic compensation for changes in air temperature
and density. The transmitter shall be designed to ignore momentary level spikes or
momentary loss-of-echo. A loss-of-echo condition shall be indicated on the
transmitter unit.
B. The ultrasonic level sensor and transmitter shall operate on a 4-20 mA signal. The
level sensor shall be located at the top of a 45 degrees V-Notch weir. The
transmitter shall be mounted in a NEMA 4 housing installed at the control panel with
pedestal supports for bolting to concrete pad. The sensor shall be capable of
continuous operation in the moist, corrosive atmosphere. The measuring equipment
shall be supplied as a fully operable unit and shall be fully calibrated. The level
sensor shall have an accuracy of 0.25% of span. The level sensor shall have a
digital display and shall operate on 120 Volt AC power. All programmed information
shall be retained in battery backed memory. The level sensor and transmitter shall
be Endress and Hauser Prosonic, Kistler-Morse, Milltronics, Polysonics, or
approved equivalent.
C. Flow measuring element shall be a 45 degree V-notch weir fabricated from minimum
114 inch thick fiberglass sheets. The weir plate shall have sharp cut edges and be
mounted vertically with gasketed bolt holes for height adjustment.
PART 3 EXECUTION
3.1 INSTALLATION
A. Installation Requirements: The services of the system supplier's technical
representative shall be provided as necessary to calibrate, test, and advise others
of procedures for adjustment and operation of the system.
1. Field Wiring - Field wiring materials and installation shall be in accordance
with the electrical section.
2. Field Piping - Field piping materials and installation shall be in accordance
with the pipe and fittings section.
3. Field-Mounted Instruments - Instruments shall be mounted so that they may
be readily approached and easily serviced.
INSTRUMENTATION
40 90 00-2
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/ce00cb0e-2d 14-4c2c-ae8e-
086fb9924bbf/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 90 00 Instrumentation.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
4. Field Calibration - A technical representative of the system supplier shall
calibrate each instrument indicating the results and final tuning adjustment
settings. The adjustments of each calibrated instrument shall be sealed or
marked, insofar as practical, so that further adjusting by unauthorized
personnel is discouraged. Instrument calibration shall be accomplished prior
to a checkout of the operations of a system.
5. Systems Check - A technical representative of the system supplier shall
participate in the checkout of metering and control systems. If interrelated
devices furnished by other suppliers, do not perform properly when placed in
service, the technical representative shall use suitable test equipment to
located the source of trouble or malfunction. A written report regarding the
results of such tests shall be furnished, if requested by the Engineer, as
necessary to resolve a question of responsibility for corrective measures.
6. Installation drawings shall be prepared for interconnecting wiring and piping
between the related equipment and the equipment furnished under this
section. The supplier shall coordinate the sensor mounting requirements and
shall furnish drawings, complete with dimensions and elevations, as specified
in Section 01 70 00— Project Closeout.
7. Coordination with other contractors and supervision of installation shall be
provided by the Contractor as required during construction.
END SECTION
INSTRUMENTATION
40 90 00-3
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/ce00cb0e-2d 14-4c2c-ae8e-
086fb9924bbf/WOPIServiceld_TP_EGNYTE_PLUS/wOPIUserld_189.ppeng.egnyte.com/40 90 00 Instrumentation.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
This Page is Intentionally Left Blank
INSTRUMENTATION
40 90 00-4
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/ce00cb0e-2d 14-4c2c-ae8e-
086fb9924bbf/WOPIServiceld_TP_EGNYTE_PLUS/wOPIUserld_189.ppeng.egnyte.com/40 90 00 Instrumentation.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 40 91 25
MAGNETIC FLOW METER
PART 1 GENERAL
1.1 WORK INCLUDED
A. Furnish and install magnetic flow meters with transmitter and power supply at the
locations indicated in the Plans.
1.2 RELATED WORK
A. Section 40 05 00 — Piping and Fittings
B. Section 40 05 23 —Valves and Appurtenances
C. Division 26 - Electrical
1.3 GENERAL
A. This unit shall be furnished and installed complete with all anchors and supports; all
mechanical and electrical equipment required for proper operation, and all additional
materials or construction required by manufacturers design.
1.4 SERVICE CONDITIONS
A. Flow meter shall include the following features as indicated below:
Working pressure, psi 150
Accuracy within flow range, percent ± 0.5
B. The new flow meters shall be fitted with a transmitter and power supply to provide a
4-20 mA signal to the plant PLC and to the remote indicator.
C. The new flow meter shall have a rate of flow indicator calibrated in gallons per
minute, and a digital totalizer.
1.5 SUBMITTALS
A. Complete data, and detailed drawings of the equipment.
B. As specified in Section 01 33 00— Submittals.
1.6 MATERIALS
A. All materials in contact with potable water shall be certified to ANSI/NSF Standard
61.
MAGNETIC FLOW METER
4091 25-1
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/7abfc781-b1 a2-4ff3-ae45-
78dc4e96efe0/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 91 25 Magnetic Flow Meter.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
PART 2 PRODUCTS
2.1 MAGNETIC FLOW METER
A. Meter size and location shall be as shown on the Plans. Meter shall be one of the
following, or Engineer approved equivalent:
1. Badger Magnetoflow with Primo amplifier,
2. Foxboro ABB MagMaster,
3. Danfoss Magflo with MAG 6000 signal converter.
B. Unless otherwise specified, meter shall use 120 VAC power.
C. The magnetic flow meter shall be a velocity sensing, electromagnetic type, flanged
tube meter with a microprocessor-based signal converter and sealed housing.
D. Meter tube shall be rated for 150 psi working pressure and shall be fabricated
stainless steel pipe and use 150 lb. AWWA Class "D" flat face steel flanges and
PTFE liner. Meter tubes shall have a constant nominal inside diameter offering no
obstruction to flow. Electrodes shall be 316 stainless steel.
E. Provision shall be made for providing a completely sealed environment for all coils,
electrode connections, and wiring harnesses, and shall be capable of submerged or
buried operation (NEMA 6).
F. Signal converter shall be, auto zeroing. The signal converter shall mount directly to
the meter. The converter shall indicate direction of flow and provide a flow rate
indication and a totalization of flow volume for both forward and reverse directions.
Both forward and reverse totalizers shall be electronically resettable. The converter
shall provide an isolated 4-20 mA output into an 800 ohm load, a frequency output
of 0-800 Hz, and a scaled pulse output. The microprocessor-based signal converter
shall have a self-diagnostic test mode and a backlit display that continuously
displays "Rate of Flow" and "Total Volume." The signal converter configuration
parameters shall be lockout protected, but is capable of being changed via the front
panel or with the use of a personal computer or electronic organizer with a 9-pin RS-
232 serial communications port. The converter shall be compatible with Microsoft
Windows or other software with terminal communications capabilities.
1. Converter shall be supplied with a programmable low-flow dropout and empty
pipe zero return.
G. Grounding rings if required shall be 316 stainless steel and shall be supplied with
the meter tube.
H. A blank pipe spool of the same laying length shall be provided to the Owner to place
in the piping in the event of the requirement to remove the meter for servicing.
MAGNETIC FLOW METER
4091 25-2
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/7abfc781-b1 a2-4ff3-ae45-
78dc4e96efe0/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 91 25 Magnetic Flow Meter.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
PART 3 EXECUTION
3.1 INSTALLATION
A. Equipment furnished and installed under this section shall be placed in operating
condition and unless exceptions are noted by the Engineer.
B. The new flow meters shall be installed in full conformity with Plans and
Specifications as well as the instructions and recommendations of the equipment
manufacture.
1. The transmitter and power supply shall be connected to the plant PLC.
C. A factory representative who has complete knowledge of equipment furnished
herein shall be provided for at least one (1) four hour period, at equipment start up,
to instruct representatives of the Owner and the Engineer on proper operation and
maintenance.
D. Following the completion of installation, the new flow meter shall be tested for proper
operation using clean water.
1. At least 2000 gallons shall be passed through the meter during the test.
Readings on totalizer shall be recorded to verify accuracy of meter.
END SECTION
MAGNETIC FLOW METER
4091 25-3
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/7abfc781-b1 a2-4ff3-ae45-
78dc4e96efe0/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 91 25 Magnetic Flow Meter.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
This Page is Intentionally Left Blank
MAGNETIC FLOW METER
4091 25-4
https://us-partner-integrations.egnyte.com/msoffice/wopi/files/7abfc781-b1 a2-4ff3-ae45-
78dc4e96efe0/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 91 25 Magnetic Flow Meter.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 40 96 31
SCADA CONTROL LOOP DESCRIPTIONS
PART 1 GENERAL
1.1 SECTION DESCRIPTION
A. This section, in conjunction with specific requirements contained in the P&ID
drawings, plans and specifications, describes the function of the project controls and
instrumentation. The contractor is responsible for providing a finished supervisory
control and data acquisition system and associated programming that can
accomplish all of the following functions and provides the necessary operator
interface to monitor the process, control the process, generate reports, and adjust
setpoints as necessary. The system will be based on remote terminal units,
manufacturer furnished equipment control panels, and a master control workstation.
B. The control functions described in this section are in addition to any control functions
described elsewhere on the plans or specifications.
C. All analog instruments shall include the following operator adjustable alarms:
1. Instrument fail
2. High-high
3. High
4. Low
5. Low-low
D. All software control switches shall include adjustable timer delays.
1.2 RELATED WORK
A. Section 40 50 00 — Instrumentation and Controls-General Provisions
B. Section 40 90 00 — Instrumentation
PART 2 CONTROL LOOP DESCRIPTIONS
2.1 PROCESS 00— MISCELANEOUS WELL FUNCTIONS
A. The new well shall be capable of being operated in two modes, selectable from the
existing electrical panel:
1. Tank supplied from Existing Well.
2. Tank supplied from Proposed Well.
SCADA CONTROL LOOP DESCRIPTIONS
40 96 31-1
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/4aga9f25-228a-43a9-b9e b-
418fbaf2d7ab/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 96 31 SCADA Control Loop Descriptions.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
B. Under no circumstances shall both wells operate simultaneously.
C. In Tank Supplied from Existing Well mode, the existing well shall operate
independently and pump water into the water storage tank while the proposed well
remains off.
D. In Tank Supplied from Proposed Well mode, the proposed well shall operate
independently and pump water into the water storage tank while the existing well
remains off.
E. Well start-up and shutdown: Provide a hand-off-automatic loop at the master control
system. Furthermore, provide a selector switch to toggle between Well No. 1 and
Well No. 2.
1. In hand mode, the Well selected via the toggle switch per Paragraph 2.1.A.5
shall start provided that startup is not inhibited by a high-high water storage
tank level.
2. In hand mode, the Well selected via the toggle switch per Paragraph 2.1.A.5
shall start provided that startup is not inhibited by a high water storage tank
level.
3. In off mode, both wells shall be off.
4. In automatic mode, the selected well shall be called on based on a low water
storage tank level and shall shut off based on a high water storage tank level
as measured by the existing water tank float switch. After shut off, the system
shall automatically switch the selected well so that the wells alternate
operation.
2.2 PROCESS 10 - WELL
A. The well pump solenoid shall open when the well is called on and shall remain open
for a programmable time after the well motor has started. The well motor shall be
inhibited for a period of time after the prelube solenoid has been opened.
B. The well shall shut off should the high or low pressure switch be activated following
an operator adjustable time delay.
C. The well pump shall operate in two modes: VFD operation and Soft Start(full speed)
operation. VFD mode shall be the default mode. Soft start mode shall be initiated
by the Operator should the VFD be out of service.
D. Well Pump VFD Operation Mode
1. Well pump speed shall be manually controlled to maintain a designated
pressure of<60%, operator adjustable
E. Soft Start Operation Mode
SCADA CONTROL LOOP DESCRIPTIONS
40 96 31-2
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/4aga9f25-228a-43a9-b9e b-
418fbaf2d7ab/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 96 31 SCADA Control Loop Descriptions.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
1. The well shall be called on and off based on the water tank elevation
measured by the existing tank float switch.
END SECTION
SCADA CONTROL LOOP DESCRIPTIONS
40 96 31-3
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/4aga9f25-228a-43a9-b9e b-
418fbaf2d7ab/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 96 31 SCADA Control Loop Descriptions.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
This Page is Intentionally Left Blank
SCADA CONTROL LOOP DESCRIPTIONS
40 96 31-4
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/4aga9f25-228a-43a9-b9e b-
418fbaf2d7ab/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 96 31 SCADA Control Loop Descriptions.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 40 97 15
PRESSURE GAUGES
PART 1 GENERAL
1.1 WORK INCLUDED
A. All analog dial-type pressure gauges and accessories to be furnished and installed
as indicated in the Contract Documents.
B. All labor, materials, equipment and incidentals necessary and required for their
completion.
1.2 RELATED WORK
A. Section 40 05 00 — Pipe & Fittings
B. Section 40 05 23 —Valves and Appurtenances
1.3 QUALITY ASSURANCE
A. Except as modified or supplemented herein, all gauges shall conform to the
requirements of ANSI B40.1.
B. Pressure gauges shall be the standard product of a single manufacturer regularly
engaged in the production of gauges of the types specified herein.
1.4 SUBMITTALS
A. As specified in Section 01 33 00— Submittal Procedures.
PART 2 PRODUCTS
2.1 ACCEPTABLE MANUFACTURERS
A. Pressure gauges shall be manufactured by Ashcroft, Weksler, or Engineer approved
equivalent.
PRESSURE GAUGES
40 97 15-1
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/802c330 b-a 84c-402e-a9a3-
fbc8608482a5/WOPIServiceld_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 97 15 Pressure Gauges.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
B. MATERIALS
1. Materials of construction shall be as follows:
Function Material
Bourdon tube Phosphor bronze
Movement Stainless steel
Ring Stainless steel or phenolic
Window Acrylic plastic or shatterproof glass
2.2 FABRICATION AND MANUFACTURE
A. Unless otherwise specified, gauges shall be indicating dial type with C-type bourdon
tube, rotary geared movement, phenolic open front turret case, and adjustable
pointer.
B. The dial shall be 4-1/2 inch size with white background and black markings. The
units of measurement shall be indicated on the dial face. Subdivisions of the scale
shall conform to the requirements of the governing standard. Pointer travel shall be
not less than 200 degrees nor more than 270 degrees of arc. Range shall be such
that the normal operating reading shall be near the midpoint of the range.
C. All stem mounted gauges shall be provided with 1/2 inch minimum NPT connections.
D. Unless otherwise specified, gauge accuracy shall be ANSI Grade A or better.
Overall accuracy for diaphragm seal protected and liquid filled gauges shall be ANSI
Grade B or better.
2.3 ACCESSORIES
A. Isolation Valves
1. Unless otherwise indicated on the drawings, each gauge shall be provided
with a threaded end ball type shutoff valve (gauge cock). Valves shall be of
brass or bronze construction, two piece end entry body, bronze or brass ball,
teflon or Viton stem seal. Valves shall be rated at not less than 250 psi and
shall be drip-tight in all directions.
B. Snubbers
1. Each pressure gauge shall be provided with a pressure snubber, and shall
be of a size and pressure range compatible with the gauge served.
2. Pressure snubbers shall be Operating and Maintenance Specialties "Ray
Snubbers", Ashcroft "Pulsation Dampers," or Engineer approved equivalent.
PRESSURE GAUGES
40 97 15-2
https://us-partner-i ntegrations.eg nyte.com/msoffice/wopi/files/802c330b-a84c-402e-a9a3-
fbc8608482a5/WOPIServiceId_TP_EGNYTE_PLUS/WOPIUserld_189.ppeng.egnyte.com/40 97 15 Pressure Gauges.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
C. Diaphragm Seals
1. A diaphragm seal shall be provided on all gauges as indicated in the
schedule.
2. Diaphragm seals shall be AISI Type 316 stainless steel diaphragm, zinc or
cadmium plated carbon steel upper housing, and bronze lower housing. The
upper housing shall be contoured to fit and provide a seat and seal for the
diaphragm and shall be designed to permit removal of the gauge with the
system under pressure. The lower housing shall be provided with a tapped
and plugged 1/4 inch NPT flushing connection. Diaphragm seals shall be
suitable for raw sewage.
3. Each diaphragm seal and the gauge served shall be factory assembled, filled
with glycerin or silicon oil and calibrated as a unit.
PART 3 EXECUTION
3.1 INSTALLATION
A. Gauges shall be installed at the locations indicated on the Plans. Pressures ranges
from 0 psi — 100 psi.
B. All gauges, snubber and diaphragm seals shall be installed in the vertical upright
position. Teflon thread tape or teflon thread sealer, shall be used in the assembly
of threaded connections. All connections shall be free from leaks.
C. Lines shall be purged of trapped air at gauge locations prior to installation of the
gauge or diaphragm seal.
END SECTION
PRESSURE GAUGES
40 97 15-3
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/802c330 b-a 84c-402e-a9a3-
fbc8608482a5MOPIServiceld_TP_EGNYTE_PLUSMOPIUserld_189.ppeng.egnyte.com/40 97 15 Pressure Gauges.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
This Page is Intentionally Left Blank
PRESSURE GAUGES
40 97 15-4
https://u s-partner-integrations.eg n yte.co m/m soffi ce/wo p i/fi I es/802c330 b-a 84c-402e-a9a3-
fbc8608482a5MOPIServiceld_TP_EGNYTE_PLUSMOPIUserld_189.ppeng.egnyte.com/40 97 15 Pressure Gauges.docx
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
SECTION 43 21 52
WELL PUMPING FACILITIES
PART 1 GENERAL
1.1 WORK INCLUDED
A. The Contractor shall be responsible for the following:
1. Furnish and install well pumps and column pipe.
2. Furnish and install above ground pump manifold within the fenced well site.
3. Furnish and install pump controls.
4. All components that may come in contact with the potable water must be
ANSI-NSF Standard 61 certified.
1.2 RELATED WORK
A. Section 09 90 00 — Painting and Coating
B. Section 33 01 00 — Piping and Fittings
C. Section 40 05 23 —Valves and Appurtenances
1.3 REFERENCES
A. American Water Works Association (AWWA)
B. Hydraulic Institute (HI)
C. American Society for Testing and Materials (ASTM)
D. American National Standards Institute (ASNSI)
E. National Electrical Manufacturers Association (NEMA)
1.4 SUBMITTALS
A. Submit shop drawings in accordance with the General Provisions.
B. As specified in Section 01 33 00 — Submittal Procedures
C. Submit manufacturer's catalog data and detail drawings showing all pump parts and
described by material of construction, specification (such as AISI, ASTM, etc.), and
grade or type. Show linings and coatings. Include total pump weight.
Well Pumping Facilities
4321 52-1
gAfresno_county of-1397\139723007 csa 43w raisin city groundwater well project\200 technical\290 specifications\div 43\43 21 52 well pumping facilities.doc
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
D. Submit pump manufacturer ISO-9001 certification.
E. Show shaft diameter and bearing spacing. Submit calculations showing shaft critical
frequency and determination of bearing spacings.
F. Submit catalog pump curves on which the specified operating points are marked.
Show efficiency and brake horsepower for the selected pump curve. Show required
submergence and NPSH.
G. Submit manufacturer's sample form for reporting performance test results at least
two weeks before the tests. The test form should contain the data presented in the
sample form in Section 6 of the ASME PTC 8.2.
H. Submit manufacturer's certified performance curves for review at least two weeks
prior to shipping the units from the factory. Show pump total head, brake
horsepower, pump efficiency, required submergence, and required NPSH. Provide
copies of the data recorded during the test and methods of data reduction for
determining certified test results.
I. Submit motor data.
J. Submit manufacturer's installation instructions.
K. Submit Operations and Maintenance Manual
1.5 QUALITY ASSURANCE
A. All components must be supplied by the same pump manufacturer including
bowls, impellers, column, shafting, heads, coupling, sleeves, seals, and motors.
The pump manufacturer shall have complete unit responsibility for meeting the
requirements of this specification.
B. Pump manufacturer shall have ISO-9001 certification. As an alternative, provide a
letter from the pump manufacturer accepting warranty responsibility for the entire
pump, motor, and baseplate unit.
C. Except as modified or supplemented herein, all submersible pumps shall conform
to the applicable requirements of ANSI/AWWA E102 and the Hydraulic Institute
Standards.
D. Welding shall comply with the ASME Boiler and Pressure Vessel code, Section IX.
Provide full penetration welds.
E. All materials and coatings in contact with potable water shall be ANSI/NSF-61
certified and comply with California AB 1953.
Well Pumping Facilities
4321 52-2
gAfresno_county of-1397\139723007 csa 43w raisin city groundwater well project\200 technical\290 specifications\div 43\43 21 52 well pumping facilities.doc
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
PART 2 PRODUCTS
2.1 PUMP BASE
A. Work shall be in conformance with Section 03 30 01 - Cast-in-Place Concrete, and
with the details shown on the Plans.
B. Vent piping and fittings shall be constructed as shown on the Plans and in
conformance with Section 40 05 00 — Pipe and Fittings.
2.2 WELL PUMP AND COLUMN PIPE
A. Pump shall be of the submersible type including motor and power cable, discharge
column, and well cap.
B. Pump manufacturer shall supply five (5) compete set of shop drawings, pump
curves, installation and operating instructions, and parts list with the pump
assembly and with compliance with Section 1.3, Submittals. These documents
shall become the property of the Owner and shall be delivered to the Owner by
Supplier upon completion of pump installation.
C. Pump shall conform with all local and state sanitary and safety regulations. Pump
and motor shall be capable of continuous operation. Pump and motor shall meet
the following conditions:
CSA 43W (Raisin City)
Pump Type Well 2
Franklin Electric, Grundfos, Goulds or Engineer
approved equal
Maximum Speed (rpm) 3,450
Design Flow (gpm) 200
Design Head (ft) 420
Minimum Bowl
Efficiency at Design 74%
Capacity
Maximum Motor HP 50
Well Pumping Facilities
4321 52-3
gAfresno_county of-1397\139723007 csa 43w raisin city groundwater well project\200 technical\290 specifications\div 43\43 21 52 well pumping facilities.doc
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
CSA 43W (Raisin City) Secondary Design Conditions
Flow (gpm) Total Head (ft) Minimum Efficiency (%)
140 485 69
175 452 73
240 354 70
D. The electric motor shall be a 3-phase, 60 Hz, 460 volt, water filled squirrel cage
induction type suitable for "across the line" starting, shall be capable of reduced
voltage starting. It shall be capable of continuous operation at nameplate rating,
submerged underwater, at a maximum water temperature of 86°F (300C). Its
maximum operating horsepower shall not exceed the nameplate horsepower plus
the allowable service factor and at no place on the pump curve shall the loading
exceed the service factor. The motor mounting dimensions shall comply with
NEMA interchangeability standards, where applicable. The motor rotor assembly
shall be dynamically balanced. The rotor shall be made of stainless steel..
E. To protect against motor overheating due to insufficient flow moving past the
motor, each well pump shall include a flow inducer sleeve or pump shroud. The
flow inducer sleeve shall be made of PVC or stainless steel and shall be fastened
to the wet end of the pump and extend all the way down past the end of the motor
to ensure water flows past the motor to reduce heat generated by the motor.
F. Thrust bearing shall be chosen to handle the continuous down thrust as specified
by the pump manufacturer with an AFBMA B-10 one year minimum or five-year
average life under design conditions. Provisions shall be made for momentary up
thrust equal to 30% of rated down thrust.
G. Interconnector made of closed grained cast iron or stainless steel, shall couple the
bowl unit to the motor. The interconnector shall include a bronze sleeve bearing
with a length to shaft diameter ratio of at least 3:1 to protect the motor from radial
loads. This bearing shall be protected from sand and grit by a labyrinth-type sand
slinger. The interconnector shall include a suction screen, which has a net open
area at least four times the area of the eye of the impeller. The screen shall be
made of corrosion resistant material.
Well Pumping Facilities
4321 52-4
gAfresno_county of-1397\139723007 csa 43w raisin city groundwater well project\200 technical\290 specifications\div 43\43 21 52 well pumping facilities.doc
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
H. The total length of the discharge column shall be pending until pilot hole
investigation has been completed. The column pipe shall be 4-inch. The pipe shall
be furnished in interchangeable sections not over 20 feet in length, and shall be
connected with threaded, sleeve-type couplings, and shall conform to American
Standard tapered pipe thread specification. The joints are to be butted to insure
perfect alignment after assembly.
I. The column check valve shall be expressly designed for submersible pump
installation and installed in the column pipe within 20 feet of the pump discharge
connection.
J. The column pipe shall be of ASTM A53 grade B steel pipe or ASTM A120 in
interchangeable sections not greater than 20 feet in length, with ends of each
section faced parallel and machined with 8 straight threads per inch permitting the
ends to butt and ensuring alignment when connected by standard mill steel
couplings. The weight on the column pipe shall be no less than that stated in
ANSI Specification E102, Section 4.10 "Discharge Pipe."
K. The power cable shall be sized such that the voltage drop will not exceed 3
percent at the motor rated full load current and voltage. Cables shall be designed
specifically for submersible pump service and shall consist of three copper
conductors and ground individually insulated and the whole covered with an outer
jacket. The length of submersible cable shall be long enough to reach the well
head junction box, with an additional 5 feet of spare cable.
L. Controls shall be mounted in an outdoor (NEMA 3R) cabinet shall include: Hand-
off-automatic selector switch, start-stop push button, standard magnetic contactor
and three adjustable ambient compensated quick-trip overload relays suitable for
submersible pump motor service. Settings for control shall be coordinated with
pump supplier.
2.3 WELL SEAL
A. A standard well seal plate designed for submersible installation shall be provided
at the top of the pump pedestal as shown on the Plans. The seal plate shall
consist of a compressible gasket between two steel plates with at least four bolts
to provide compression of the gasket. Well Cap shall rigidly support the total
weight of the motor, bowl assembly, column pipe, cable and column of water. The
cable outlet shall be designed to prevent entry of foreign matter into the well and
shall be equipped with a cable seal.
B. When the bolts are tightened, the gasket shall be compressed sufficiently to seal
against the well casing and around all pipes and cables that pass through the cap.
C. All un-used openings in the cap shall be sealed to prevent the entry of water.
Well Pumping Facilities
4321 52-5
gAfresno_county of-1397\139723007 csa 43w raisin city groundwater well project\200 technical\290 specifications\div 43\43 21 52 well pumping facilities.doc
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
2.4 LEVEL PROBES
A. Level probes and cables shall be installed to allow stopping of the pump if the well
water level reaches a depth of 50 ft above pump bowls and to allow re-start of the
pump when water level is at an operational depth.
B. Level probe cables shall be suitably attached to column pipe per manufacturer's
recommendations and shall be of sufficient length to reach the well head junction
box with an additional 5 feet of spare cable. Individual conductor and ground shall
be suitable marked to ensure correct connection to motor controller.
PART 3 EXECUTION
3.1 INSTALLATION
A. An experienced, competent, and authorized representative of the manufacturer shall
visit the site of the Work and Inspect, check, adjust if necessary, and approve the
equipment installation. The representative shall be present when the equipment is
placed in operation and shall revisit the job site as often as necessary until all trouble
is corrected and the equipment installation and operation are satisfactory in the
opinion of ENGINEER.
B. The manufacturer's representative shall furnish a written report certifying that the
equipment has been properly installed and lubricated; is in accurate alignment; is
free from any undue stress imposed by connecting piping or anchor bolts; and has
been operated under full load conditions and that it operated satisfactorily.
C. All costs of these services shall be included in the contract price for the number of
days and round trips to the site as required.
3.2 FIELD QUALITY CONTROL
A. Bump motor to ensure proper rotational direction before coupling the motor to the
pump.
B. Perform field vibration measurements during normal operation. Vibration levels shall
be within HI limits. Repair or replace pumps not meeting the HI vibration limits.
C. Collect flow and discharge pressure data from at least three different flow rates,
including the design flow rate. Compare the data with the factory performance curve
and notify the Engineer if the data varies by more than 5%.
3.3 DISINFECTION AND TEST OF WELL
A. After installation of well pumping facilities, well shall be pumped a minimum of 15
minutes. Water shall be discharged and conducted away from the well site to a
drainage way through suitable temporary hose.
B. After flushing, well shall be disinfected as specified in AWWA C 654.
Well Pumping Facilities
4321 52-6
gAfresno_county of-1397\139723007 csa 43w raisin city groundwater well project\200 technical\290 specifications\div 43\43 21 52 well pumping facilities.doc
COUNTY OF FRESNO
CSA 43W RAISIN CITY GROUNDWATER WELL PROJECT
C. After disinfection and flushing of chlorinated water, the water shall be tested for
coliform bacteria as specified in AWWA C 547.
END OF SECTION
Well Pumping Facilities
4321 52-7
gAfresno_county of-1397\139723007 csa 43w raisin city groundwater well project\200 technical\290 specifications\div 43\43 21 52 well pumping facilities.doc
Project Details
Contract Number 24-14-C
H J
W W W �Q z0 w
It
o
d W Q�' z W W
/ `, 2i z O
z w o U)
Z U) Q
0 Q CL° ,� 0 D
3AVS3NNO 'S � 0° J�w� _
Ho Q
I_- Z J rn rn z z
V � o�
Z > �t�U U)
U- —
Q �
N N
LL �
M
'3nd snm:jo 's
d' LLI
Q iQ
iW
lL W
z � o
c/) W
� a
'3AV 2dMNV310'S z o
� Z) o
U) O
Of
U C�
O
'3AV ONPA'S Q
U
CO
J
Q � U co
cn ~ y
U >.
m
Q o c5
w
Wz
Z '3AV WMA 'S
J
Q oQ
OnW
J � �
�i�04
C7
Z_
Z
Z
Q
QZui
U
U
C"M � 0 Z
O a
zU)
U O C7
W Z Q w O
Z � = w o LU
W J � vw a
m w
� � � o
LL
M Q W aww0
a
Z Z z
w C� U
FEE zv
V w
Bo �
a
z w W
ago > Q
� � � z w X
� a � z
� Z - w
w J
- ; L V yam _ `� o
M a ? Z
W �
o
� cn
4
Lu LU
pia �
M CY) Q O Q
z � c6
O
cl- 0 p
Z Z W
U
cn Q w
w of 2
� � U
Invoice ti co
County of Fresno Dummy Permit County of Fresno
Department of Public Works & Planning
Mailing Address: 2220 Tulare Street, 6th Floor Fresno, CA 93721
24-HR REQUEST LINE: 600-4131 LOCAL: 600-4560 O� 1 56 O
TOLL FREE: 800742-1011 FAX: 600-4201
INVOICE TO:
INVOICE NO: 312844
INVOICE DATE: August 12, 2024
PERMIT #: Folder 2024 010755 000 00 FC
REFERENCE #:
PROJECT LOCATION: 1 TEST CARUTHERS CA
PROJECT DESCRIPTION: INSTALL NEW WATER PIPING AND
ELECTRICAL FOR NEW WELL
FEE DESCRIPTION AMOUNT COMMENT
CA Bldg Standards Comm. Fee (SB-1473) $1.00
Wiring Outlets $3.40 Qty2
Workers Comp. $7.96
Call-In, Fax, Email or Internet $21.22
Appliances/Welders/Single Outlets $21.48 °ty1
Circuits (remodel only) $25.46 Qty2
Service/sub-panel 0 -200 amps $30.77 °ty1
Electrical Permit Issuance $40.31
Plumbing Permit Issuance $40.31
Minimum Electrical Permit fee $62.06
Minimum Plumbing Permit fee $62.06
Motors over 30 HP - 50 HP $67.90 °ty1
Microfilm/Copies $92.32
On Site Water Piping (ft) $106.08 Qty300
Special Service $148.50
TOTAL $730.83
County of Fresno Dummy Permit SUMMARY
ELECTRICAL PERMIT $251.38
OTHER $271.00
PLUMBING PERMIT $208.45
TOTAL $730.83
Total Billed: $730.83
Payment Received: $0.00
Balance Due: $730.83
FORM OF PAYMENT:
Check
Credit Card
Cash
DrawDown-Acct#
Roads Charge-Use Acct#
Submitted by: Ext:
SELF-DEALING TRANSACTION DISCLOSURE FORM
(1) Company Board Member Information:
Name: Date:
Job Title:
(2) Company/Agency Name and Address:
(3) Disclosure (Please describe the nature of the self-dealing transaction you are a party to)
(4) Explain why this self-dealing transaction is consistent with the requirements of Corporations
Code 5233 (a)
(5) Authorized Signature
Signature: Date:
SELF-DEALING TRANSACTION DISCLOSURE FORM INSTRUCTIONS
In order to conduct business with the County of Fresno (hereinafter referred to as "County"), members of
a contractor's board of directors (hereinafter referred to as "County Contractor"), must disclose any self-
dealing transactions that they are a party to while providing goods, performing services, or both for the
County. A self-dealing transaction is defined below:
'A self-dealing transaction means a transaction to which the corporation is a party and which one or
more of its directors has a material financial interest."
The definition above will be utilized for purposes of completing the disclosure form.
(1) Enter board member's name, job title (if applicable), and date this disclosure is being made.
(2) Enter the board member's company/agency name and address.
(3) Describe in detail the nature of the self-dealing transaction that is being disclosed to the County.
At a minimum, include a description of the following:
a. The name of the agency/company with which the corporation has the transaction; and
b. The nature of the material financial interest in the Corporation's transaction that the board
member has.
(4) Describe in detail why the self-dealing transaction is appropriate based on applicable provisions
of the Corporations Codes.
(5) Form must be signed by the board member that is involved in the self-dealing transaction
described in Sections (3) and (4).
ID OOK
CSA 43W RAISIN CITY GROUNDWATER WELL
6425 W BOWLES AVE, RAISIN CITY, CA 93652
BUDGET /ACCOUNT: 8870 / 8400 / 91762
co
FR ESQ Department of Public Works and Planning
CONTRACT NUMBER 24-14-C
BID BOOK TABLE OF CONTENTS
CSA 43W RAISIN CITY GROUNDWATER WELL
CONTRACT NUMBER 24-14-C
PROPOSAL TITLE
NUMBER(S)
NOT APPLICABLE INSTRUCTIONS FOR COMPLETING THE BID BOOK
1 PROPOSAL TO THE BOARD OF SUPERVISORS OF THE COUNTY OF FRESNO
2 BID ITEM LIST
3 EVALUATION OF BID ITEM LIST
4 BID SECURITY
5 NON-COLLUSION DECLARATION
6 PUBLIC CONTRACT CODE SECTION 10285.1 STATEMENT
7 PUBLIC CONTRACT CODE SECTION 10162 QUESTIONNAIRE AND PUBLIC CONTRACT
CODE 10232 STATEMENT
8 SUBCONTRACTORS
9 TITLE 13,CALIFORNIA CODE OF REGULATIONS§2449(I)GENERAL REQUIREMENTS FOR
IN-USE OFF-ROAD DIESEL-FUELED FLEETS
10-18 NOT USED
19 GUARANTY
INSTRUCTIONS FOR COMPLETING THE BID BOOK FOR NON-FEDERAL AID PROJECTS
General
Complete forms in the Bid book.
Submit an electronic bid online at http://www.BidExpress.com or submit a hardcopy bid:
1. Under sealed cover addressed to the Department and labeled with the name of the bidder, contract number,
the name of the project and the statement'Do Not Open Until The Time Of Bid Opening.'
2. Marked as a bid
3. Identifying the contract number and the bid opening date
Certain bid forms must be submitted with the bid and properly executed.
Certain other forms and information must be submitted either with the bid or within the prescribed period after bid
opening as specified elsewhere in these special provisions.
Failure to submit the forms and information as specified results in a nonresponsive bid.
If an agent other than the authorized corporation officer or a partnership member signs the bid, file a Power of
Attorney with the Department either before opening bids or with the bid. Otherwise, the bid may be
nonresponsive.
Bid Item List and Bid Comparison
Submit a bid based on the bid item quantities the Department shows on the Bid Item List. Bids will be evaluated
and the low bidder determined as indicated in the Notice to Bidders.
Bid Document Completion
Proposal items are identified by title and by the word "Proposal" followed by the number assigned to the proposal
item in question. Proposal items are included in the Bid Book.
Proposal to the Board of Supervisors of Fresno County— Proposal 1
Provided for information.
Bid Item List— Proposal 2
One or more sheet(s) or list(s) upon which the bidder completes the bid.
Fill out completely including a unit price and total for each unit price-based item and a total for each lump sum
item.
Do not make any additions such as "plus tax", "plus freight", or conditions such as "less 2% if paid by 15th".
Use ink or typewriter for paper bids.
Evaluation of Bid Item List—Proposal 3
Describes how inconsistences and irregularities are evaluated and corrected when Design Services reviews the
Bid Item List.
Bid Security and Signature— Proposal 4
Submit one of the following forms of bidder's security equal to at least 10 percent of the bid:
• Cash
• Cashier's check
• Certified check
• Signed bidder's bond by an admitted surety insurer
INSTRUCTIONS FOR COMPLETING THE BID BOOK FOR NON-FEDERAL AID PROJECTS: Page 2 of 4
Indicate type of bid security provided.
• Cash—Acceptable but not recommended. Cash is deposited in a clearing account and is returned to
bidders by County warrant. This process may take several weeks.
• Cashier's or Certified Checks. This type of security is held until the bid is no longer under consideration.
If submitted by a potential awardee, they will be returned when the contract is fully executed by the
bidder and bonds and insurance have been approved.
• Bid Bonds - Must be signed by the bidder and by the attorney-in-fact for the bonding company. Provide
notarized signature of attorney-in-fact accompanied by bonding company's affidavit authorizing attorney-
in-fact to execute bonds. An unsigned bid bond will be cause for rejection.
Bonding companies may provide their own bid bond forms. The Bid Security and Signature sections must be
completed by the bidder and submitted with their bid.
Acknowledge Addenda
Provide contractor's license information.
State business name and if business is a:
• Corporation - list officers
• Partnership- list partners
• Joint Venture- list members; if members are corporations or partnerships, list their officers or partners.
• Individual - list Owner's name and firm name style
Signature of Bidder-the following lists types of companies and corresponding authorized signers.
• Corporation - by an officer
• Partnership- by a partner
• Joint Venture- by a member
• Individual - by the Owner
If signature is by a Branch Manager, Estimator, Agent, etc., the bid must be accompanied by a power of attorney
authorizing the individual to sign the bid in question or to sign bids more generally, otherwise the bid may be
rejected.
• Business Address - Firm's Street Address
• Mailing Address - P.O. Box or Street Address
• Complete, sign, and return with bid.
Noncollusion Declaration —Proposal 5
Must be completed, signed, and returned with bid.
Public Contract Code Section 10285.1 Statement— Proposal 6
Select"has"or"has not" in accordance with instructions on form, return completed form with bid. Note that
signing the bid constitutes signing this statement.
Public Contract Code Section 10162 Questionnaire And Public Contract Code 10232 Statement—
Proposal 7
Select"yes"or"no" accordance with instructions on form, include explanation if"yes" is selected. Return
completed form with bid. Note that signing the bid constitutes signing this questionnaire and statement.
INSTRUCTIONS FOR COMPLETING THE BID BOOK FOR NON-FEDERAL AID PROJECTS: Page 3 of 4
Subcontractors— Proposal 8
Sheet(s) or spaces where bidders list subcontractors. List each subcontractor to perform work in an amount in
excess of 1/2 of 1 percent of the total bid or$10,000, whichever is greater(Pub. Contract Code §4100 et seq.).
The Subcontractor List submitted with the bid must show the name, location of business, work portions to be
performed, Department of Industrial Relations registration number, and the contractor's license number for each
subcontractor listed.
• Use subcontractor's business name style as registered with the License Board.
• Specify the city in which the subcontractor's business is located and the state if other than California.
• Description of the work to be performed by the subcontractor. Indicate with bid item numbers from the
bid item list and/or work descriptions similar to those on bid item list.
• List Department of Industrial Relations number and license number for each subcontractor.
Upon request from Design Services, provide the following additional information within 24 hours of bid opening if
not included on the Subcontractor List submitted with the bid:
• Complete physical address for each subcontractor listed.
• Percentage of the total bid or dollar amount associated with each subcontractor listed.
Title 13, California Code of Regulations § 2449(i) General Requirements for In-Use Off-Road Diesel-
Fueled Fleets— Proposal 9
Contractors, if applicable, must submit valid Certificates of Reported Compliance with their bid. Subcontractor
certificates will be due no later than 4:00 PM on the fifth (51h)calendar day after the bid opening if not submitted
with the bid.
Proposal 10 - Proposal 18—Not Used
Guaranty— Proposal 19
Does not need to be signed with the bid. Part of the contract which must be signed by the contractor when
contract is executed.
INSTRUCTIONS FOR COMPLETING THE BID BOOK FOR NON-FEDERAL AID PROJECTS: Page 4 of 4
PROPOSAL TO THE COUNTY OF FRESNO
hereinafter called the Owner
CSA 43W RAISIN CITY GROUNDWATER WELL
The work embraced herein shall be done in accordance with the 2023 Standard Specifications
and with the 2023 Standard Plans, of the State of California, Department of Transportation
insofar as the same may apply and in accordance with these special provisions.
Except to the extent that they may conflict with these special provisions, revised Standard
Specifications apply to the extent included in the section entitled "Project Details" of the book
entitled "Specifications."
The work to be done is shown on a set of Plans, Department File No. 11339, entitled: "Raisin
City Groundwater Well"
The undersigned, as bidder, declares that the only persons, or parties interested in this proposal
as principals are those named herein, that this proposal is made without collusion with any other
person, firm or corporation; that they have carefully examined the location of the proposed work,
the annexed proposed form of contract, and the plans therein referred to; and they propose and
agrees if this proposal is accepted, that they will contract with the Owner to provide all necessary
machinery, tools, apparatus and other means of construction, and to do all the work and furnish
all the materials specified in the contract in the manner and time therein prescribed, and
according to the requirements of the Engineer as therein set forth, and that they will take in full
payment therefor the following unit prices, to-wit:
Proposal 1
Contract Number 24-14-C
General Info
Total:
$1,091,006.00
Number Description
24-14-C CSA 43W Raisin City Groundwater Well
Deadline The work to be done consists of, in general, furnishing all labor, materials and equipment
10/31/2024 02:00 PM PDT necessary to drill and equip a water well at the location indicated on the plans and
connect to the existing water distribution main in the community of Raisin City, CA, in
Vendor accordance with the Plans and Specifications. Electrical work, grading, fence removal and
Zim Industries, Inc. installation and other appurtenant work as indicated on the plans and specifications is also
part of the work.
Submitted
Allows zero unit prices and labor
10/31/2024 01:54 PM PDT
Yes
Signed by
Allows negative unit prices and labor
Wes Zimmerer
Account Holder Wes Yes
Zimmerer
Opened
10/31/2024 02:06 PM PDT By
jbnavarro@fresnocountyca.gov
Page 1 of 29 10/31/2024
Attachment List
Project Website
RFC form, bid opening details, any Supplemental Information
including RFC responses, prebid conference information, etc.
Plans
Plans
Specifications
Specifications
Addendum 1 (http://www.fresnocountyca.gov/files/sharedassets/county/v/1/public-works-and-planning/design/construction-bidding-opportunities/24-14-c-
csa-43w-raisin-city-grou ndwater-well/add end u m-1.pdf)
Addendum 1
Addendum 1 - Plans
Addendum 1 - Plans
Page 2 of 29 10/31/2024
Proposal to the County of Fresno - Proposal 1
Proposal to the County of Fresno
hereinafter called the Owner
CSA 43W RAISIN CITY GROUNDWATER WELL
The work embraced herein shall be done in accordance with the 2023 Standard Specifications and with the 2023 Standard Plans,
of the State of California, Department of Transportation insofar as the same may apply and in accordance with these special
provisions.
Except to the extent that they may conflict with these special provisions, revised Standard Specifications apply to the extent
included in the section entitled "Project Details" of the book entitled "Specifications."
The work to be done is shown on a set of Plans, Department File No. 11339, entitled: "Raisin City Groundwater Well".
The undersigned, as bidder, declares that the only persons, or parties interested in this proposal as principals are those named
herein, that this proposal is made without collusion with any other person, firm or corporation; that they have carefully examined
the location of the proposed work, the annexed proposed form of contract, and the plans therein referred to; and they propose and
agree if this proposal is accepted, that they will contract with the Owner to provide all necessary machinery, tools, apparatus and
other means of construction, and to do all the work and furnish all the materials specified in the contract in the manner and time
therein prescribed, and according to the requirements of the Engineer as therein set forth, and that they will take in full payment
therefor the following unit prices, to-wit:
Page 3 of 29 10/31/2024
Bid Item List - Proposal 2
$1,091,006.00
Item Quantity Unit Item Description Item Price Extension
No.
1 1 LS Mobilization/Demobilization, Insurance, and Bonds $136,500.00 $136,500.00
2 1 LS Prepare and Implement WPCP $7,000.00 $7,000.00
3 1 LS Dust Control $1,500.00 $1,500.00
4 1 LS Job Site Management $15,000.00 $15,000.00
5 1 LS Traffic Control $1,500.00 $1,500.00
6 1 LS Clearing and Grubbing $5,000.00 $5,000.00
7 1 LS Site Demolition $7,500.00 $7,500.00
8 50 LF Furnish and Install 30" Diameter Conductor Casing $750.00 $37,500.00
9 650 LF Drill Pilot Hole (to 700 feet total depth) $120.00 $78,000.00
10 1 LS Perform Electric Log and Deviation Log $7,500.00 $7,500.00
11 3 EA Collect Depth Zone Samples $22,700.00 $68,100.00
12 650 LF Open Pilot Hole to 24" Diameter (to 700 feet total depth) $120.00 $78,000.00
13 442 LF Furnish and Install 12" Diameter Blank Casing $82.00 $36,244.00
14 230 LF Furnish and Install 12" Diameter Perforated Casing $125.00 $28,750.00
15 1 LS Furnish and Install 20-foot Compression Section $6,000.00 $6,000.00
16 397 LF Furnish and Install 3" Diameter Permanent Gravel Fill Pipe $16.00 $6,352.00
17 310 LF Furnish and Install Gravel Pack $70.00 $21,700.00
18 390 LF Furnish and Install Annular Seal $100.00 $39,000.00
19 48 HR Perform Preliminary Well Development $620.00 $29,760.00
20 1 LS Perform Pump Development and Pump Test (Mob/Demob pump $47,000.00 $47,000.00
and pump up to 40 hours)
21 20 HR Additional Pump Development and Pump Testing Time $400.00 $8,000.00
22 1 LS Perform Video Log $3,600.00 $3,600.00
Total: $1,091,006.00
Page 4 of 29 10/31/2024
Item Quantity Unit Item Description Item Price Extension
No.
23 1 LS Construct Well Pump Foundation $8,000.00 $8,000.00
24 1 LS Furnish and Install Submersible Well Pump and Motor $49,000.00 $49,000.00
25 500 LF Furnish and Install 4" Diameter Column Pipe $32.00 $16,000.00
26 1 LS Site Grading $2,500.00 $2,500.00
27 1 LS Site Piping, Valves, and Appurtenances $140,000.00 $140,000.00
28 1 LS Temporary Chain Link Fence $21,000.00 $21,000.00
29 1 LS Permanent Chain Link Fence $20,000.00 $20,000.00
30 1 LS Electrical, Controls, & Lighting $120,000.00 $120,000.00
31 1 LS Connection to Existing Water System $7,000.00 $7,000.00
32 1 LS Start-Up and Testing $1,500.00 $1,500.00
33 1 LS Operations and Maintenance Manuals $6,500.00 $6,500.00
34 1 LS Record Drawings $5,000.00 $5,000.00
35 25,000 $ Supplemental Work Allowance $1.00 $25,000.00
Total: $1,091,006.00
Page 5 of 29 10/31/2024
Evaluation of Bid Item List - Proposal 3
Abbreviations used in the bid proposal sheet are identified in Section 1-1.06, "Abbreviations," of these special provisions.
Bids are required for the entire work. Bids will be compared on the basis indicated in the Notice to Bidders. The bidder shall set
forth for each unit basis item of work a unit price and a total for the item, and for each lump sum item a total for the item, all in
clearly legible figures in the respective spaces provided for that purpose. In the case of unit basis items, the amount set forth
under the "Item Total" column shall be the product of the unit price bid and the estimated quantity for the item.
In case of discrepancy between the unit price and the total set forth for a unit basis item, the unit price shall prevail, except as
provided in (a) or (b), as follows:
(a) If the amount set forth as a unit price is unreadable or otherwise unclear, or is omitted, or is the same as the amount as
the entry in the item total column, then the amount set forth in the item total column for the item shall prevail and shall be
divided by the estimated quantity for the item and the price thus obtained shall be the unit price;
(b) (Decimal Errors) If the product of the entered unit price and the estimated quantity is exactly off by a factor of ten, one
hundred, etc., or one-tenth, or one-hundredth, etc. from the entered total, the discrepancy will be resolved by using the
entered unit price or item total, whichever most closely approximates percentage-wise the unit price or item total in the
Owner's Final Estimate of cost.
If both the unit price and the item total are unreadable or otherwise unclear, or are omitted, the bid may be deemed irregular.
Likewise, if the item total for a lump sum item is unreadable or otherwise unclear, or is omitted, the bid may be deemed irregular
unless the project being bid has only a single item and a clear, readable total bid is provided.
Symbols such as commas and dollar signs will be ignored and have no mathematical significance in establishing any unit price or
item total or lump sums. Written unit prices, item totals and lump sums will be interpreted according to the number of digits and, if
applicable, decimal placement. Cents symbols also have no significance in establishing any unit price or item total since all figures
are assumed to be expressed in dollars and/or decimal fractions of a dollar. Bids on lump sum items shall be item totals only; if
any unit price for a lump sum item is included in a bid and it differs from the item total, the items total shall prevail.
The foregoing provisions for the resolution of specific irregularities cannot be so comprehensive as to cover every omission,
inconsistency, error or other irregularity which may occur in a bid. Any situation not specifically provided for will be determined in
the discretion of the Owner, and that discretion will be exercised in the manner deemed by the Owner to best protect the public
interest in the prompt and economical completion of the work. The decision of the Owner respecting the amount of a bid, or the
existence or treatment of an irregularity in a bid, shall be final.
If this proposal shall be accepted and the undersigned shall fail to contract, as aforesaid, and to give the two bonds in the sums to
be determined as aforesaid, with surety satisfactory to the Owner, within eight (8) days not including Saturdays, Sundays and legal
holidays, after the bidder has received notice of award of the contract, the Owner, at its option, may determine that the bidder has
abandoned the contract, and thereupon this proposal and the acceptance thereof shall be null and void, and the forfeiture of such
security accompanying this proposal shall operate and the same shall be the property of the Owner.
Page 6 of 29 10/31/2024
Bid Security - Proposal 4
Bond Percentage
10.00%
Guarantee Method
Cash, Cashier's Check,
Certified Check, Paper Bid
Bond
Cash, Cashier's Check, Certified Check, Paper Bid Bond
Confirmation *
I have provided a Paper Bid Bond for the Bid Security Amount above prior to the solicitation
deadline.
You must either attach an electronic bid bond here or provide an original bid bond (or other form of bid security authorized by
Public Contract Code Section 20129(a)) to the office location according to the instructions in the Notice to Bidders prior to the bid
opening.
Page 7 of 29 10/31/2024
Addendum Acknowledgement - Proposal 4
Bidders must acknowledge all addenda. The Bidder acknowledges receipt of the following ADDENDA:
(Enter the number the Designer has assigned to each of the addenda that the Bidder is acknowledging)
Type N/A if no addenda were issued. Click "+" to add additional fields.
Addendum No. *
1
Dated
10/28/2024
Page 8 of 29 10/31/2024
Bidder Signature - Proposal 4
Business Name *
Zim Industries, Inc.
Note: If bidder or other interested person is a corporation, state legal name of corporation. If bidder is a co-partnership, state true
name of firm.
Type of Business
Corporation - list Officers
Business Owners and Officers Names
See attached
Note: If bidder or other interested person is:
• a corporation, list names of the president, secretary, treasurer and manager thereof
• a partnership, list names of all individual co-partners composing firm.
• an individual, state first and last name in full.
Names of Owners and Key Employees
See attached
Note: List majority owners of your firm. If multiple owners, list all. Also include anyone, including key employees, who are actively
promoting the contract. (SB1439)
Licensed in accordance with an act providing for the registration of Contractors:
Class *
A, C-57, C61/D21
Contractor License No. * Expires
440537 6/30/2025
Page 9 of 29 10/31/2024
DIR Registration Number
1000003978
Business Address
4532 E Jefferson Ave, Fresno, CA
Zip Code *
93725-9807
Mailing Address
4532 E Jefferson Ave, Fresno, CA
Zip Code *
93725-9807
Business Phone * Fax Number
(559) 834-1551
E-mail Address
wes@zimindustries.com
Signature of Bidder
Wesley Zimmerer
Dated *
10/31/2024
NOTE: If bidder is a corporation, the legal name of the corporation shall be set forth above together with the signature of the
officer or officers authorized to sign contracts on behalf of the corporation; if bidder is a co-partnership, the true name of the firm
shall be set forth above together with the signature of the partner or partners authorized to sign contracts on behalf of the co-
partnership; and if bidder is an individual, bidder signature shall be placed above. If signature is by an agent, other than an officer
of a corporation or a member of a partnership, a Power of Attorney must be on file with the Owner prior to opening bids or
submitted with the bid; otherwise, the bid will be disregarded as irregular and unauthorized.
Page 10 of 29 10/31/2024
Noncollusion Declaration - Proposal 5
TO BE EXECUTED BY BIDDER AND SUBMITTED WITH BID*
The undersigned declares:
I am the (Choose one of the following options):
Owner
If Corporate Officer please list Title:
President
of (Business Name):
Zim Industries, Inc.
the party making the foregoing bid.
The bid is not made in the interest of, or on behalf of, any undisclosed person, partnership, company, association, organization, or
corporation. The bid is genuine and not collusive or sham. The bidder has not directly or indirectly induced or solicited any other
bidder to put in a false or sham bid. The bidder has not directly or indirectly colluded, conspired, connived, or agreed with any
bidder or anyone else to put in a sham bid, or refrain from bidding. The bidder has not in any manner, directly or indirectly, sought
by agreement, communication, or conference with anyone to fix the bid price of the bidder or any other bidder, or to fix any
overhead, profit, or cost element of the bid price, or of that of any other bidder. All statements contained in the bid are true. The
bidder has not, directly or indirectly, submitted his or her bid price or any breakdown thereof, or the contents thereof, or divulged
information or data relative thereto, to any corporation, partnership, company, association, organization, bid depository, or to any
member or agent thereof, and has not paid, and will not pay, any person or entity for that purpose.
Any person executing this declaration on behalf of a bidder that is a corporation, partnership, joint venture, limited liability
company, limited liability partnership, or any other entity, hereby represents that he or she has full power to execute, and does
execute, this declaration on behalf of the bidder.
I declare under penalty of perjury under the laws of the State of California that the foregoing is true and correct and that this
declaration is executed on 2024,
Date: *
10/31/2024
at City, State:
Fresno, CA
Signature:
Curt B Zimmerer
(See Title 23 United States Code Section 112; Calif Public Contract Code Section 7106)
Page 11 of 29 10/31/2024
*NOTE: Completing, signing, and returning the Non-Collusion Declaration is a required part of the Proposal. Bidders are cautioned
that making a false certification may subject the certifier to criminal prosecution.
Page 12 of 29 10/31/2024
Public Contract Code - Proposal 6-7
Public Contract Code Section 10285.1 Statement - Proposal 6
In conformance with Public Contract Code Section 10285.1 (Chapter 376, Stats. 1985), the bidder hereby declares under penalty
of perjury under the laws of the State of California that the bidder
Choose an option: *
Has not been convicted
within the preceding three years of any offenses referred to in that section, including any charge of fraud, bribery, collusion,
conspiracy, or any other act in violation of any state or Federal antitrust law in connection with the bidding upon, award of, or
performance of, any public works contract, as defined in Public Contract Code Section 1101, with any public entity, as defined in
Public Contract Code Section 1100, including the Regents of the University of California or the Trustees of the California State
University. The term "bidder" is understood to include any partner, member, officer, director, responsible managing officer, or
responsible managing employee thereof, as referred to in Section 10285.1.
The above Statement is part of the Bid. Signing this Bid on the signature portion thereof shall also constitute signature of this
Statement. Bidders are cautioned that making a false certification may subject the certifier to criminal prosecution.
Public Contract Code Section 10162 Questionnaire - Proposal 7
In conformance with Public Contract Code Section 10162, the Bidder shall complete, under penalty of perjury, the following
questionnaire:
Has the bidder, any officer of the bidder, or any employee of the bidder who has a proprietary interest in the bidder, ever been
disqualified, removed, or otherwise prevented from bidding on, or completing a federal, state, or local government project because
of a violation of law or a safety regulation?
Choose an option:
No
If the answer is No, please type N/A. If the answer is Yes, explain the circumstances in the following space.
N/A
Public Contract Code Section 10232 Statement - Proposal 7
In conformance with Public Contract Code Section 10232, the Contractor hereby states under penalty of perjury, that no more than
Page 13 of 29 10/31/2024
one final unappealable finding of contempt of court by a federal court has been issued against the Contractor within the
immediately preceding two-years period because of the Contractor's failure to comply with an order of the National Labor Relations
Board.
Note: The above Statement and Questionnaire are part of the Bid. Signing this Bid on the signature portion thereof shall also
constitute signature of this Statement and Questionnaire. Bidders are cautioned that making a false certification may subject the
certifier to criminal prosecution.
Page 14 of 29 10/31/2024
BIDDER: Z'kln� !jU&Y_)(.U. -1-rf',
SUBCONTRACTORS:
The following named subcontractor(s) will perform with labor, or otherwise render services
to the general contractor in or about the construction of the work or improvement in an
amount in excess of one-half of one percent of the total bid presented herewith. Each listed
subcontractor's name, location of business and description of work, and both -their
contractor's license number and public works contractor registration number, issued pursuant
to Section 1725.5 of the Labor Code, are REQUIRED, by Section 4104 of the California
Public Contract Code, to be submitted prior to bid opening. (The "location of business" must
specify the city in which the subcontractor's business is located, and the state if other than
California.) All other requested information shall be submitted, either with the bid or within
24 hours after bid opening.
Please fill out as completely as possible when submitting your bid. Use subcontractor's
business name style as registered with the License Board.
FAILURE TO LIST SUBCONTRACTORS AS DIRECTED MAY RENDER THE BID NON-
RESPONSIVE, OR MAY RESULT IN ASSESSMENT OF A PENALTY AGAINST THE
BIDDER IN ACCORDANCE WITH SECTION 4110 OF THE CALIFORNIA PUBLIC
CONTRACT CODE.
SUBCONTRACTOR: It !�
Business Address: (A Zoe
ClassCbt 009License No. DIR Re istra Son No
Item No. or Descrip Po of Work: N eAl- ,— te a
Dollar Amount t5VO OR Per ent e of Total Bid
Email Address: Q i
SUBCONTRACTOR: C
Business Address: Gw
Class&A License No_';� le2 1/ �' D1IR��Regi tration No 00
Item No. or Description of Work: 10 -� o a r` —
Dollar Amount O Percentage of Total Bid
Email Address: A C `CSM Yv&/St
Proposal 8(a)
Contract Number 24-14-C
4�1P.S
SUBCONTRACTOR: z
Business Address: 5016u !ice (/ 1//��C
Class�O License No. � DIR Registtrr'ation No b.
Item No. or Description f ork: �4�Q�'/Y�Gf bu/,� -304311 3 133 dl
Dollar Amount OR Per en e of Total Bid
Email Address: C. ' Q e lec CQ
SUBCONTRACTOR:
Business Address:
Class License No. DIR Registration No.
Item No. or Description of Work:
Dollar Amount OR Percentage of Total Bid
Email Address:
SUBCONTRACTOR:
Business Address:
Class License No. DIR Registration No
Item No. or Description of Work:
Dollar Amount OR Percentage of Total Bid
Email Address:
SUBCONTRACTOR:
Business Address:
Class License No. DIR Registration No.
Item No. or Description of Work:
Dollar Amount OR Percentage of Total Bid
Email Address:
SUBCONTRACTOR:
Business Address:
Class License No. DIR Registration No
Item No. or Description of Work:
Dollar Amount OR Percentage of Total Bid
Email Address:
Proposal 8(b)
Contract Number 24-14-C
71 yr Tr4U v1,e.li
SUBCONTRACTOR:
Business Address:
Class License No. DIR Registration No.
Item No. or Description of Work:
Dollar Amount OR Percentage of Total Bid
Email Address:
SUBCONTRACTOR:
Business Address:
Class License No. DIR Registration No
Item No. or Description of Work:
Dollar Amount OR Percentage of Total Bid
Email Address:
SUBCONTRACTOR:
Business Address:
Class License No. DIR Registration No.
Item No. or Description of Work:
Dollar Amount OR Percentage of Total Bid
Email Address:
Proposal 8(c)
Contract Number 24-14-C
California Code of Regulations: General Requirements for In-Use Off-Road Diesel-Fueled
Fleets - Proposal 9
In conformance with Title 13 § 2449(i), bidders will be required to attach copies of valid Certificates of Reported Compliance for
the fleet selected for the contract and their listed subcontractors.
Before May 15th of each year, the prime contractor must collect a new valid Certificate of Reported Compliance for the current
compliance year, as defined in section 2449(n), from all fleets that have an ongoing contract with the prime contractor as of March
1 of that year. Prime contractors must not write contracts to evade this requirement. Annual renewals must be provided to the
Resident Engineer at least one week prior to the expiration date of the current certificate.
https://ww2.arb.ca.gov/resources/fact-sheets/fact-sheet-contracting-requirements
Choose all that apply:
❑✓ Bidder's Certificate of Reported Compliance has been attached to the bid.
❑Bidder does not have a fleet subject to this regulation as outlined in Section 2449(i)(1)-(4).
❑✓ Listed subcontractors' certificates have been attached or will be submitted within five (5) calendar days of the
bid opening.
✓❑The following subcontractors do not have a fleet subject to this regulation as outlined in Section 2449(i)(1)-(4):
Pacific Surveys, LLC
Page 18 of 29 10/31/2024
FAILURE TO PROVIDE THE CERTIFICATES OF REPORTED COMPLIANCE AS DIRECTED MAY RENDER THE BID NON-
RESPONSIVE.
Page 19 of 29 10/31/2024
Certification With Regard To The Performance Of Previous Contracts Or Subcontracts
Subject To The Equal Opportunity Clause And The Filing Of Required Reports - Proposal 10
The bidder or proposed subcontractor hereby certifies that they
Please choose an option below
have participated
in a previous contract or subcontract subject to the equal opportunity clause, as required by Executive Orders 10925, 11114, or
11246, and that they
Please select an option below
have filed
with the Joint Reporting Committee, the Director of the Office of Federal Contract Compliance, a Federal Government contracting
or administering agency, or the former President's Committee on Equal Employment Opportunity, all reports due under the
applicable filing requirements.
Company *
Zim Industries, Inc.
By: *
Curt B Zimmerer
Title *
President
Date *
10/31/2024
NOTE: The above certification is required by the Equal Employment Opportunity Regulations of the Secretary of Labor (41 CFR
60-1.7(b) (1), and must be submitted by bidders and proposed subcontractors only in connection with contracts and subcontracts
which are subject to the equal opportunity clause. Contracts and subcontracts which are exempt from the equal opportunity clause
are set forth in 41 CFR 60-1.5. (Generally only contracts or subcontracts of $10,000 or under are exempt.) Currently, Standard
Form 100 (EEO-1) is the only report required by the Executive Orders or their implementing regulations.
Currently, Standard Form 100 (EEO-1) is the only report required by the Executive Orders or their implementing regulations.
Proposed prime contractors and subcontractors who have participated in a previous contract or subcontract subject to the
Executive Orders and have not filed the required reports should note that 41 CFR 60-1.7(b) (1) prevents the award of contracts
and subcontracts unless such contractor submits a report covering the delinquent period or such other period specified by the
Director, Office of Federal Contract Compliance, U. S. Department of Labor.
Page 20 of 29 10/31/2024
Page 21 of 29 10/31/2024
Title 49, Code Of Federal Regulations, Part 29 - Debarment And Suspension Certification -
Proposai 11
The bidder or proposed subcontractor under penalty of perjury, certifies that, except as noted below, he/she or any person
associated therewith in the capacity of owner, partner, director, officer, manager:
is not currently under suspension, debarment, voluntary exclusion, or determination of ineligibility by any federal agency;
has not been suspended, debarred, voluntarily excluded or determined ineligible by any federal agency within the past 3
years;
does not have a proposed debarment pending; and
has not been indicted, convicted, or had a civil judgment rendered against it by a court of competent jurisdiction in any matter
involving fraud or official misconduct within the past 3 years.
If no exceptions enter "No Exceptions." If there are any exceptions to this certification, insert the exceptions in
the following space:
No Exceptions
Exceptions will not necessarily result in denial of award, but will be considered in determining bidder responsibility.
For any exception noted above, indicate below to whom it applies, initiating agency, and dates of action:
Note: Providing false information may result in criminal prosecution or administrative sanctions.
The above certification is part of the Proposal. Signing the Proposal on the signature portion thereof shall also constitute signature
of this Certification.
By my signature on this proposal, I certify, under penalty of perjury under the laws of the State of California and the United States
Page 22 of 29 10/31/2024
of America, that the Title 23 United States Code, Section 112 Non-Collusion Declaration and the Title 49 Code of Federal
Regulations, Part 29 Debarment and Suspension Certification are true and correct.
Company *
Zim Industries, Inc.
By *
Curt B Zimmerer
Date *
10/31/2024
Title *
President
Page 23 of 29 10/31/2024
Nonlobbying Certification For Federal-Aid Contracts - Proposal 12
The prospective participant certifies, by signing and submitting this bid or proposal, to the best of his or her knowledge and belief,
that:(1) No Federal appropriated funds have been paid or will be paid, by or on behalf of the undersigned, to any person for
influencing or attempting to influence an officer or employee of any Federal agency, a Member of Congress, an officer or
employee of Congress, or an employee of a Member of Congress in connection with awarding of any cooperative agreement, and
the extension, continuation, renewal, amendment, or INSTALLATION of any Federal contract, grant, loan, or cooperative
agreement.
(2) If any funds other than Federal appropriated funds have been paid or will be paid to any person for influencing or attempting to
influence an officer of any Federal agency, a Member of Congress, an officer or employee of Congress, or an employee of a
Member of Congress in connection with this Federal contract, grant, loan, or cooperative agreement, the undersigned shall
complete and submit Standard Form-LLL, "Disclosure of Lobbying Activities," in accordance with its instructions.
This certification is a material representation of fact upon which reliance was placed when this transaction was made or entered
into. Submission of this certification is a prerequisite for making or entering into this transaction imposed by Section 1352, Title 31,
U.S. Code. Any person who fails to file the required certification shall be subject to a civil penalty of not less than $10,000 and not
more than $100,000 for each such failure.
The prospective participant also agrees by submitting his or her bid or proposal that he or she shall require that the language of
this certification be included in all lower tier subcontracts, which exceed $100,000 and that all such subrecipients shall certify and
disclose accordingly.
Bidder *
Zim Industries, Inc.
By *
Wes Zimmerer
Date *
10/31/2024
Title *
President
Page 24 of 29 10/31/2024
Disclosure of Lobbying Form - Proposal 13
OMB 0348-0046 Disclosure of Lobbying Activities - Proposal 13 (223 KB)
Disclosure of Lobbying Activities
Page 25 of 29 10/31/2024
Proposal 14-18
NOT USED
Page 26 of 29 10/31/2024
Guaranty - Proposal 19
Optional: Vendor is not required to complete.
(This guaranty shall be executed by the successful bidder in accordance with instructions in the special provisions. The bidder may
execute the guaranty on this page at the time of submitting their bid.)
GUARANTY
To the Owner: County of Fresno
CONTRACT NUMBER
The undersigned guarantees the construction and installation of the following work included in this project: 24-14-C
ALL WORK
Should any of the materials or equipment prove defective or should the work as a whole prove defective, due to faulty
workmanship, material furnished or methods of installation, or should the work or any part thereof fail to operate properly as
originally intended and in accordance with the plans and specifications, due to any of the above causes, all within twelve (12)
months after date on which this contract is accepted by the Owner, the undersigned agrees to reimburse the Owner, upon
demand, for its expenses incurred in restoring said work to the condition contemplated in said project, including the cost of any
such equipment or materials replaced and the cost of removing and replacing any other work necessary to make such replacement
or repairs, or, upon demand by the Owner, to replace any such material and to repair said work completely without cost to the
Owner so that said work will function successfully as originally contemplated.
The Owner shall have the unqualified option to make any needed replacement or repairs itself or to have such replacements or
repairs done by the undersigned. In the event the Owner elects to have said work performed by the undersigned, the undersigned
agrees that the repairs shall be made and such materials as are necessary shall be furnished and installed within a reasonable
time after the receipt of demand from the Owner.
Date: *
10/31/2024
Name (Printed):
Curt B Zimmerer
Signature: *
Curt B Zimmerer
Title: *
President
Contractor:
Zim Industries, Inc.
Page 27 of 29 10/31/2024
Required Documents
Name Omission Terms Submitted
File
Zim's CARB
CARB Certification of Reported Compliance - Certificate of
Bidder - Proposal 9 Does not have a fleet subject to this regulation. Reported
Valid CARB Certification of Reported Compliance Compliance
- Bidder Expiring
2-28-2025.pdf
I am not
CARB Certification(s) of Reported Compliance - enclosing this
Subcontractors - Proporal 9 Due by 4pm on the 5th calendar day after bid document
Valid CARB Certification(s) of Reported opening or no listed subcontractors have a fleet because the
Compliance - Subcontractors subject to this regulation. omission terms
have been
met.
I am not
OMB 0348-0046 Disclosure of Lobbying Activites enclosing this
- Proposal 13 document
Complete this form to disclose lobbying activities Submit disclosure if needed. because the
pursuant to 31 U.S.C. 1352 omission terms
have been
met.
3 Required Documents
Page 28 of 29 10/31/2024
Additional Documents (Use if needed)
Name Omission Terms Submitted
File
Optional: Vendor is not required to complete.
Zim's Bid
Proposal for
24-14-C CSA
Not Required Extra space not needed 43W Raisin
Extra Space if needed City
Groundwater
Well
Project.pdf
I am not
enclosing this
Not Required document
Extra Space if needed Extra space not needed because the
omission terms
have been
met.
I am not
enclosing this
Not Required document
Extra Space if needed Extra space not needed because the
omission terms
have been
met.
3 Required Documents
Page 29 of 29 10/31/2024
AGREEMENT
THIS AGREEMENT made at Fresno, in Fresno County, California, by and between Zim Industries, Inc.
hereinafter called the Contractor, and the County of Fresno hereinafter called the Owner.
WITNESSETH: That the Contractor and the Owner, for the consideration hereinafter named, agree as
follows:
ARTICLE I. The Contractor agrees to furnish all labor and materials, including tools, implements, and
appliances required, but excluding such materials as are mentioned in the specifications to be furnished
by the Owner, and to perform all the work in a good and workmanlike manner, free from any and all liens
and claims of mechanics, materialmen, teamsters, subcontractors, artisans, machinists, and laborers
required for:
CSA 43W RAISIN CITY GROUNDWATER WELL
6425 W BOWLES AVE, RAISIN CITY, CA 93652
CONTRACT NUMBER: 24-14-C
All in strict compliance with the plans, drawings and specifications therefor prepared by the Owner, and
other contract documents relating thereto.
ARTICLE II. The Contractor and the Owner agree that the Notice to Bidders and Special Provisions,
the Wage Scale (Prevailing Wages), the Plans and Drawings, Addenda and Bulletins thereto, and the
Proposal (Bid Book) hereto attached, together with this Agreement, form the contract, and they are as
fully a part of the contract as if hereto attached or herein repeated.
All portions of the Standard Specifications of the State of California, Department of Transportation, dated
2015, which are not in conflict with this contract shall be deemed a part of the specifications as though
fully therein set forth; provided, however, that revisions to the said Standard Specifications shall apply
only to the extent, if any, included in the Project Details of these specifications or as otherwise
incorporated directly herein. No part of said specifications which is in conflict with any portion of this
agreement, or which is not actually descriptive of the work to be done thereunder, or of the manner in
which said work is to be executed, shall be considered as any part of this agreement, but shall be utterly
null and void.
ARTICLE III. The Owner agrees to pay the Contractor in current funds for the performance of the
contract the sum of ONE MILLION NINETYONE THOUSAND AND SIX DOLLARS AND 00/100
($1,091,006.00) it being understood that said price is based upon the estimated quantities of materials
to be used as set forth in the Proposal, except where provisions are made in the contract documents
whereby the estimated quantities shall constitute the final quantity; that upon completion of the project
the final contract prices shall be revised by change order, if necessary, to reflect the true quantities used
at the stated unit price thereof as contained in the Contractor's Proposal hereto attached. Payments on
account thereof will be made as set forth in the special provisions.
ARTICLE IV. If the Contractor should be adjudged a bankrupt, or if he or she should make a general
assignment for the benefit of his or her creditors, or if a receiver should be appointed on account of his
Contract Number 24-14-C
or her insolvency, or if he or she or any of his or her subcontractors should persistently violate any of
the provisions of the contract, or if he or she should persistently or repeatedly refuse or should fail,
except in cases for which extension of time is provided, to supply enough properly skilled workmen or
proper materials, or if he or she should fail to make prompt payment to subcontractors or for material or
labor, or persistently disregard laws, ordinances or the instructions of the Engineer, then the Owner may,
upon certificate of the Engineer when sufficient cause exists to justify such action, serve written notice
upon the Contractor and his surety of its intention to terminate the contract, and unless within five days
after the serving of such notice, such violations shall cease and satisfactory arrangements for correction
thereof be made, the contract shall, upon the expiration of said five days, cease and terminate.
In the event of any such termination, the Owner shall immediately serve written notice thereof upon the
surety and the Contractor, and the surety shall have the right to take over and perform the contract,
provided, however, that if the surety within ten (10) days after the serving upon it of notice of termination
does not give the Owner written notice of its intention to take over and perform the contract or does not
commence performance thereof within the ten (10) days stated above from the date of the serving of
such notice, the Owner may take over the work and prosecute the same to completion by contract or by
any other method it may deem advisable, for the account and at the expense of the Contractor, and the
Contractor and his surety shall be liable to the Owner for any excess cost occasioned the Owner thereby,
and in such event the Owner may without liability for so doing, take possession of and utilize in
completing the work such materials, appliances, plant and other property belonging to the Contractor as
may be on the site of the work and necessary therefor. In such case the Contractor shall not be entitled
to receive any further payment until the work is finished. If the unpaid balance of the contract price shall
exceed the expenses of finishing the work, including compensation for additional managerial and
administrative services, such excess shall be paid to the Contractor. If such expense shall exceed such
unpaid balance, the Contractor shall pay the difference to the Owner. The expense incurred by the
Owner, as herein provided and damage incurred through the Contractor's default, shall be certified by
the Engineer.
ARTICLE V. To the fullest extent permitted by law with respect to any work required to be done under
this contract, the Contractor will indemnify and hold harmless the COUNTY OF FRESNO, STATE OF
CALIFORNIA, CONSULTANTS and all other participating public agencies, whether or not said agencies
are named herein, who have jurisdiction within the areas in which the work is to be performed, and all
officers and employees of the Owner, the County, the State, the United States and said other
participating agencies, from any and all costs and expenses, attorney fees and court costs, damages,
liabilities, claims and losses occurring or resulting to COUNTY in connection with the performance, or
failure to perform, by CONTRACTOR, its officers, agents or employees under this Agreement, and from
any and all costs and expenses, attorney fees and court costs, damages, liabilities, claims and losses
occurring or resulting to any person, firm or corporation who may be injured or damaged by the
performance, or failure to perform, of CONTRACTOR, its officers, agents or employees under this
Agreement. In addition, CONTRACTOR agrees to indemnify COUNTY for Federal, State of California
and/or local audit exceptions resulting from non-compliance herein on the part of CONTRACTOR.
CONTRACTOR agrees to indemnify, save, hold harmless, and at COUNTY'S request, defend the
COUNTY, its officers, agents, and employees from any and all costs and expenses, damages, liabilities,
claims, and losses occurring or resulting to COUNTY in connection with the performance, or failure to
perform, by CONTRACTOR, its officers, agents, or employees under this Agreement, and from any and
all costs and expenses, damages, liabilities, claims, and losses occurring or resulting to any person,
firm, or corporation who may be injured or damaged by the performance, or failure to perform, of
CONTRACTOR, its officers, agents, or employees under this Agreement.
Contract Number 24-14-C
The Certificate of Insurance shall be issued in duplicate, to the COUNTY OF FRESNO and all other
participating agencies, whether or not said agencies are named herein, who contribute to the cost of the
work or have jurisdiction over areas in which the work is to be performed and all officers and employees
of said agencies while acting within the course and scope of their duties and responsibilities.
In the event CONTRACTOR fails to keep in effect at all times insurance coverage as herein provided,
the COUNTY may, in addition to other remedies it may have, suspend or terminate this Agreement upon
the occurrence of such event.
All policies shall be with admitted insurers licensed to do business in the State of California. Insurance
purchased shall be purchased from companies possessing a current AM Best Company rating of A FSC
VI or better.
Without limiting the COUNTY'S right to obtain indemnification from CONTRACTOR or any third parties,
CONTRACTOR, at its sole expense, shall maintain in full force and effect, the following insurance
policies or a program of self-insurance, including but not limited to, an insurance pooling arrangement
or Joint Powers Agreement (JPA) throughout the term of the Agreement:
A. Commercial General Liability
Commercial General Liability Insurance with limits not less than those shown in the following table:
Liabilit Insurance Requirements
Total bid For each Aggregate for products/completed General b Umbrella or
occurrence operation aggregate excess liabilityc
<_ $1,000,000 $1,000,000 $2,000,000 $2,000,000 $5,000,000
> $1,000,000
<_ $10,000,000 $1,000,000 $2,000,000 $2,000,000 $10,000,000
> $10,000,000
<_ $25,000,000 $2,000,000 $2,000,000 $4,000,000 $15,000,000
> $25,000,000 $2,000,000 $2,000,000 $4,000,000 $25,000,000
'Combined single limit for bodily injury and property damage.
bThis limit must apply separately to your work under this Contract.
°The umbrella or excess policy must contain a clause stating that it takes effect (drops down) in the
event the primary limits are impaired or exhausted.
This policy shall be issued on a per occurrence basis. COUNTY may require specific coverages including
completed operations, products liability, contractual liability, Explosion-Collapse-Underground, fire legal
liability, or any other liability insurance deemed necessary because of the of the nature of this contract.
Such Commercial General Liability insurance shall name the County of Fresno, its officers, agents, and
employees, individually and collectively, as additional insured, but only insofar as the operations under
this Agreement are concerned. Such coverage for additional insured shall apply as primary insurance
and any other insurance, or self-insurance, maintained by COUNTY, its officers, agents and employees
shall be excess only and not contributing with insurance provided under CONTRACTOR's policies
herein. This insurance shall not be cancelled or changed without a minimum of thirty (30) days advance
written notice given to COUNTY. CONTRACTOR shall obtain endorsements to the Commercial General
Liability insurance policy naming COUNTY as an additional insured and providing for a thirty (30) day
prior written notice of cancellation or change in terms or coverage.
Contract Number 24-14-C
Within eight(8) days from date CONTRACTOR executes this Agreement, CONTRACTOR shall provide
certificates of insurance and endorsement as stated above for all of the foregoing policies, as required
herein, to the County of Fresno, or to designservices(a)_fresnocountyca.gov, stating that such insurance
coverages have been obtained and are in full force; that the County of Fresno, its officers, agents and
employees will not be responsible for an premiums on the policies; that such Commercial General
Liability insurance names the County of Fresno, its officers, agents, and employees, individually and
collectively, as additional insured, but only insofar as the operations under this Agreement are
concerned; that such coverage for additional insured shall apply as primary insurance an any other
insurance, or self- insurance shall not be cancelled or changed without a minimum of thirty (30) days
advance, written notice given to COUNTY.
CONTRACTOR shall obtain endorsements to the Commercial General Liability insurance naming the
County of Fresno, its officers, agents, and employees, individually and collectively, as additional insured,
but only insofar as the operations under this Agreement are concerned. Such coverage for additional
insured shall apply as primary insurance and any other insurance, or self-insurance, maintained by
COUNTY, its officers, agents, and employees shall be excess only and not contributing with insurance
provided under CONTRACTOR'S policies herein. This insurance shall not be cancelled or changed
without a minimum or thirty (30) days advance written notice given to COUNTY.
B. Automobile Liability
Comprehensive Automobile Liability Insurance with limits of not less than One Million Dollars
($1,000,000) per accident for bodily injury and property damage. Coverage should include owned and
non-owned vehicles used in connection with this Agreement and all applicable endorsements.
C. Professional Liability
If CONTRACTOR is a licensed professional or employs professional staff, (e.g., Architect, Engineer,
Surveyor, etc.) in providing services, Professional Liability Insurance with limits of not less than One
Million Dollars ($1,000,000.00) per occurrence, Three Million Dollars ($3,000,000.00) annual aggregate
with a provision for 3 year tail coverage.
D. Worker's Compensation
A policy of Worker's Compensation insurance as may be required by the California Labor Code.
ARTICLE VI. Contractor represents that he has secured the payment of Worker's Compensation in
compliance with the provisions of the Labor Code of the State of California and during the performance
of the work contemplated herein will continue so to comply with said provisions of said Code. Contractor
shall supply the Owner with certificates of insurance, in duplicate, evidencing that Worker's
Compensation Insurance is in effect and providing that the Owner will receive ten days' notice of
cancellation. If Contractor self-insures Worker's Compensation, Certificate of Consent to Self-insure
should be provided the Owner.
ARTICLE VII. The Contractor shall forthwith furnish in duplicate, a faithful performance bond in an
amount equal to 100% of the contract price and a payment bond in an amount equal to 100% of the
contract price, both bonds to be written by a surety company acceptable to the Owner and in the form
prescribed by law.
Contract Number 24-14-C
The payment bond shall contain provisions such that if the Contractor or his subcontractors shall fail to
pay (a) amounts due under the Unemployment Insurance Code with respect to work performed under
the contract, or (b) any amounts required to be deducted, withheld and paid over to the Employment
Development Department and to the Franchise Tax Board from the wages of the employees of the
Contractor and subcontractors pursuant to Section 13020 of the Unemployment Insurance Code with
respect to such work and labor, then the surety will pay these amounts. In case suit is brought upon the
payment bond, the surety will pay a reasonable attorney's fee to be fixed by the court.
ARTICLE VIII. This project is subject to compliance monitoring and enforcement by the Department of
Industrial Relations.
Except as provided in Labor Code section 1725.5(f), no contractor or subcontractor may be listed on a
bid proposal for a public works project unless registered with the Department of Industrial Relations
pursuant to Labor Code section 1725.5 [with limited exceptions from this requirement for bid purposes
only under Labor Code section 1771.1(a)].
Except as provided in Labor Code section 1725.5(f), no contractor or subcontractor may be awarded a
contract for public work on a public works project or engage in the performance of work on any public
works project unless registered with the Department of Industrial Relations pursuant to Labor Code
section 1725.5.
Contractor shall comply with all applicable laws and regulations relating to wages and employment,
including all requirements imposed by the California Department of Industrial Relations (DIR).
Contractor shall cooperate with County to furnish timely all information necessary for County's
completion of the form required to be submitted by County when registering the Project on the DIR
website; and County thereafter shall provide to Contractor the "Project ID Number" assigned by DIR in
order to facilitate Contactor's submission to DIR of its certified payrolls for the Project, in the manner
required and using such form as may be prescribed by DIR, in accordance with the provisions of Labor
Code section 1771.4(a)(3).
ARTICLE IX: Governing Law—Venue for any action arising out of or relating to this Agreement shall be
in Fresno County, California. This Agreement shall be governed by the laws of the State of California.
ARTICLE X: EXECUTIVE ORDER N-6-22: Under Executive Order N-6-22 as a contractor,
subcontractor, or grantee, compliance with the economic sanctions imposed in response to Russia's
actions in Ukraine is required, including with respect to, but not limited to, the federal executive orders
identified in the EO and the sanctions identified on the U.S. Department of the Treasury website
(https://ofac.treasurV.gov/sanctions-programs-and-country-information/russia-related-sanctions).
Failure to comply may result in the termination of contracts or grants, as applicable. Specially Designated
Nationals and Blocked Persons List (SDN) (https:Hsanctionslist.ofac.treas.gov/Home/SdnList).
Contract Number 24-14-C
This Contract, 24-14-C, was awarded by the Board of Supervisors on December 17, 2024. It has been
reviewed by the Department of Public Works and Planning and is in proper order for signature of the
Chairman of the Board of Supervisors.
IN WITNESS WHEREOF, they have executed this Agreement this o7Sth day of
Jan NGru
zl w• �h of�S�rt cs. Sh C COUNTY OF FRESNO